Crown Boiler BWC070, BWC120, BWC090 installation manual 30a Cuttable Straight Section

Page 17

D. Assembly of Crown 80/125mm Concentric Venting

(IMPORTANT - See Section C for 60/100mm Concentric Vent Assembly)

WARNING

Failure to follow the instructions could result in flue gas leakage into the combustion air or indoor air, resulting in unsafe or unreliable operation.

Do not lubricate concentric gaskets with anything other than water.

Do not attempt to cut any piping except as permitted in this section. When cutting these sections, make sure all cuts are square and allow for proper insertion.

Do not attempt to try to mix this concentric pipe with other venting systems.

1)The 60/100mm terminal section and concentric reducing elbow supplied with the boiler are not used in 80/125mm vent systems. The components listed in Table 7.4b are required for 80/125mm installations and are not supplied with the boiler. Before starting assembly of an 80/125mm vent system, make sure that the planned installation is in accordance with the “Vent System Design” section of this manual and that all required 80/125mm vent components are on hand. These components are available through Crown distributors.

2)Cutting Straight Pipe - The following straight pipe sections may be cut:

Part #

Description

230517

19 1/2” Straight

230515

39” Straight

These sections have a plain male end (without beads - see Figure 7.30a). They are always cut from the male end. Sections not shown on the above list may not be cut. These sections have beads on the male end (Figure 7.30b).

FIGURE 7.30a: CUTTABLE STRAIGHT SECTION

FIGURE 7.30b: NON CUTTABLE STRAIGHT SECTION

26

Image 17
Contents Page VII Venting Page Summary of Horizontal Venting Options Horizontal Concentric Venting Vent Option 1,3 Vent Option Manufacturer Vent Size Component Part Number 6c Positioning Vent Terminal Under Overhangs Snorkel Terminal Configuration VENT/ AIR Intake Fitting Equivalent Length 10 Vertical Twin Pipe Vent System Vent Option Removing an Existing Boiler From a Common Chimney Page 21 Dimension L 22 Cutting Outer Pipe 25 Attaching 60/100mm Terminal Section 30a Cuttable Straight Section 31 Cutting Straight Pipe 32a Joining Cuttable Pipe 33a Dimension L, 80/125mm Horizontal Terminal 33c Cutting Inner Pipe of 80/125mm Horizontal Terminal 34 Installation of Snorkel Terminal 35a Dimension H 35b Cutting Vertical Terminal 36 Chimney Chase Installation Assembly of Stainless Steel Venting 47 CORR/GUARD Connection to Vent Collar