C. Assembly of Crown 60/100mm Concentric Venting

(IMPORTANT - Skip to Section D for 80/125mm Concentric Vent Assembly)

WARNING

Failure to follow the instructions could result in flue gas leakage into the combustion air or indoor air, resulting in unsafe or unreliable operation.

Do not lubricate concentric gaskets with anything other than water.

Do not attempt to cut any piping except as permitted in this section. When cutting these sections, make sure all cuts are square and allow for proper insertion.

Do not attempt to try to mix this concentric pipe with other venting systems.

1)Concentric vent components supplied with the boiler are packed inside the boiler carton and include the following:

a)80/125 x 60/100mm reducing elbow (Crown PN 230521).

b)60/100mm terminal section (straight section with a terminal and overall length of 27 3/4” (Crown PN 230520).

c)Two (2) Rubber wall grommets (Crown PN 230522).

2)Unless the 80/125 straight riser (PN 230515) is used, start by attaching the reducing elbow to the boiler collar. To do so, remove the clamp from the large end of the reducing elbow and set aside. Apply a small amount of water to the brown gasket on the boiler collar. Push the elbow onto the boiler collar until the bead on the elbow contacts the top edge of the collar (Figure 7.20).

3)Reinstall the clamp removed in Step (2) so that the elbow is secured to the boiler collar.

4)If no additional sections of concentric pipe are required, attach the terminal section to the elbow. In most cases, it will need to be cut before doing so. Use the following procedure to cut the pipe:

a)Measure distance “L” from the outside surface of the exterior wall to the end of the elbow as shown in Figure 7.21.

b)Add 2-1/8” to distance “L”. Carefully mark this length on the pipe as shown in Figure 7.22.

c)Press in the two tabs holding the plastic terminal in the terminal section (Figure 7.22). Carefully pull out the terminal and the inner pipe.

d)Cut the outer pipe only at the point marked in Step (b) using aviation shears, a hacksaw, or an abrasive wheel cutter. Be careful to cut the pipe square. De burr the cut end with a file or emery cloth.

e)Cut the plastic inner pipe so that it will protrude 3/8” beyond the outer pipe when reinstalled in the terminal section (Figure 7.23). Use a fine tooth hacksaw or a PVC saw to cut the plastic pipe and be careful to cut the pipe square. De burr the cut edge of the plastic pipe with a file, razor blade, or fine sandpaper.

f)Reinstall the inner pipe in the terminal section. Slip the outside wall grommet over the terminal section and position so that it covers the joint between the outer pipe and the terminal (Figure 7.24).

g)Make a mark on the terminal section 1” from the cut end of the outer pipe as shown in Figure 7.24.

h)Pass the terminal section through the wall from the outside. Push the remaining wall grommet over the terminal section on the inside of the wall. Push the terminal section into the elbow until the mark made in Step (g) is no longer visible. If necessary, the brown gasket in the inner pipe may be lubricated with a few drops of water.

i)The terminal section must be attached to the elbow with a single #10 x 1/2” sheet metal screw ( not supplied) at the top of the elbow. Drill a 1/8” hole in the location shown in Figure 7.25. Use a short drill bit or a drill stop to ensure that the drill bit does not penetrate the pipe by more than 3/8”. Install a #10 x 1/2” screw in this hole. Do not use a screw longer than 1/2” long.

j)If not already done, make sure that both wall grommets are firmly against the interior and exterior wall surfaces. Seal any cracks or other openings near the terminal through which exhaust could enter the building.

5)If additional pieces of pipe are used, install them starting at the boiler elbow. Support each section of straight pipe at its female end.

22

Image 13
Contents Page VII Venting Page Summary of Horizontal Venting Options Horizontal Concentric Venting Vent Option 1,3 Vent Option Manufacturer Vent Size Component Part Number 6c Positioning Vent Terminal Under Overhangs Snorkel Terminal Configuration VENT/ AIR Intake Fitting Equivalent Length 10 Vertical Twin Pipe Vent System Vent Option Removing an Existing Boiler From a Common Chimney Page 21 Dimension L 22 Cutting Outer Pipe 25 Attaching 60/100mm Terminal Section 30a Cuttable Straight Section 31 Cutting Straight Pipe 32a Joining Cuttable Pipe 33a Dimension L, 80/125mm Horizontal Terminal 33c Cutting Inner Pipe of 80/125mm Horizontal Terminal 34 Installation of Snorkel Terminal 35a Dimension H 35b Cutting Vertical Terminal 36 Chimney Chase Installation Assembly of Stainless Steel Venting 47 CORR/GUARD Connection to Vent Collar

BWC120, BWC070, BWC090 specifications

Crown Boiler Company has established itself as a leader in the heating industry, providing reliable and efficient solutions for residential and commercial applications. Among their innovative product line, the BWC series, which includes the BWC120, BWC070, and BWC090 models, showcases advanced technology and design features that cater to the diverse needs of consumers.

The BWC series is designed to deliver exceptional heating performance while being user-friendly and efficient. One of the main features of these models is their compact design, making them suitable for installations in tight spaces, such as basements and utility rooms. This space-saving advantage does not compromise their power or heating capacity, as each model is engineered to handle a variety of heating demands.

A prominent technology in the BWC series is the high-efficiency, modulating condensing design. This allows the boilers to adjust their output based on the heating requirements of the space, leading to significant energy savings. By utilizing a variable-speed blower and an integrated control system, these boilers can operate at lower heating outputs when the demand is lower, ultimately improving overall efficiency and reducing fuel costs.

The BWC120, with an output of 120 MBH, is ideal for larger homes or light commercial applications, providing robust heating capabilities. The BWC090 offers a slightly lower output at 90 MBH, catering to moderately sized homes. Meanwhile, the BWC070 targets smaller residential settings with an output of 70 MBH, ensuring that there is a fitting option for a variety of heating needs.

In addition to their efficiency and compact design, the BWC models are equipped with advanced safety features, including built-in temperature and pressure relief valves. These safety measures give homeowners peace of mind, knowing that their heating system is operating safely and reliably.

Durability is another characteristic that defines the BWC series. Constructed with high-quality materials and designed to withstand the rigors of everyday use, these boilers are built to last. The easy-to-service construction ensures that routine maintenance is straightforward, thereby enhancing longevity and reliability.

In summary, the Crown Boiler BWC120, BWC070, and BWC090 models combine efficiency, advanced technology, and safety features, making them an excellent choice for anyone in the market for dependable heating solutions. Their adaptability to various heating needs, along with their space-saving designs, makes them suitable for a wide range of applications, ensuring comfort and reliability for years to come.