Desa FAS-3B Operating Heater, Checking GAS Connections, For Your Safety Read Before Lighting

Page 11

OWNER’S MANUAL

INSTALLATION

Continued

CHECKING GAS

CONNECTIONS

WARNING: Test all gas pip- ing and connections for leaks after installing or servicing. Cor- rect all leaks at once.

WARNING: Never use an open flame to check for a leak. Apply a mixture of liquid soap and water to all joints. Bubbles forming show a leak. Correct all leaks at once.

Pressure Testing Gas Supply Piping System

Test Pressures In Excess Of 1/2 PSIG (3.5 K Pa)

1.Disconnect heater and its individual manual shutoff valve from gas supply piping system. Pressures in excess of 1/2 PSIG will damage heater regulator.

2.Cap off open end of gas pipe where manual shutoff valve was connected.

3.Pressurize supply piping system by ei- ther using compressed air or opening main gas valve located on or near gas meter.

4.Check all joints of gas supply piping system. Apply mixture of liquid soap and water to gas joints. Bubbles form- ing show a leak.

5.Correct all leaks at once.

6.Reconnect heater and manual shutoff valve to gas supply. Check reconnected fittings for leaks.

Test Pressures Equal To or Less Than 1/2 PSIG (3.5 K Pa)

1.Close manual shutoff valve (see Fig- ure 14).

2.Pressurize supply piping system by ei- ther using compressed air or opening main gas valve located on or near gas meter.

3.Check all joints from gas meter to manual shutoff valve (see Figure 15). Apply mix- ture of liquid soap and water to gas joints. Bubbles forming show a leak.

4.Correct all leaks at once.

Pressure Testing Heater Gas Connections

1.Open manual shutoff valve (see Figure 14).

2.Open main gas valve located on or near gas meter.

3.Make sure control knob of heater is in the OFF position.

4.Check all joints from manual shutoff valve to control valve (see Figure 15). Apply mixture of liquid soap and wa- ter to gas joints. Bubbles forming show a leak.

5.Correct all leaks at once.

6.Light heater (see Operating Heater, page 12 for non-thermostat models or page 13 for thermostat models). Check the rest of the internal joints for leaks.

7.Turn off heater (see To Turn Off Gas to Appliance, page 13 for non-thermo- stat models or page 14 for thermostat models).

8.Replace front panel.

Open

Manual

Shutoff

Valve

CPlosed

Figure 14 - Manual Shutoff Valve

Control Valve Location

Thermostat Models

Gas Meter

Manual

Shutoff

Valve

Control Valve Location

Non-Thermostat Models

Figure 15 - Checking Gas Joints

OPERATING

HEATER

NON-THERMOSTAT MODELS FA-3B AND FA-5B

FOR YOUR SAFETY

READ BEFORE

LIGHTING

WARNING: If you do not fol- low these instructions exactly, a fire or explosion may result caus- ing property damage, personal injury or loss of life.

A.This appliance has a pilot which must be lighted by hand. When lighting the pilot, follow these instructions exactly.

B.BEFORE LIGHTING smell all around the appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.

WHAT TO DO IF YOU SMELL GAS

Do not try to light any appliance.

Do not touch any electric switch; do not use any phone in your building.

Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.

If you cannot reach your gas sup- plier, call the fire department.

C.Use only your hand to push in or turn the gas control knob. Never use tools. If the knob will not push in or turn by hand, don’t try to repair it, call a qualified service technician or gas supplier. Force or attempted repair may result in a fire or explosion.

D.Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been un- der water.

Continued

105566

11

Image 11
Contents What to do if YOU Smell GAS Infrared VENT-FREE Natural GAS HeaterInfrared Natural GAS Heater Safety InformationUnpacking Product FeaturesProduct Identification Local CodesConfined and Unconfined Space Fresh AIR for Combustion and VentilationProducing Adequate Ventilation Unusually Tight ConstructionDetermining if You Have a Confined or Unconfined Space Fresh AIR for Combustion VentilationDetermining FRESH-AIR Flow for Heater Location Ventilation Air From Outdoors Ventilation AIRVentilation Air From Inside Building Check GAS Type InstallationInstallation Items Locating HeaterMethods For Attaching Mounting Bracket To Wall Installing Heater to WallMounting Bracket Removing Front Panel Of Heater Models FA-3B and FA-5BPlacing Heater On Mounting Bracket Installing Bottom Mounting ScrewsAttaching Mounting Bracket To Wall Typical Inlet Pipe Diameters Connecting to GAS SupplyOperating Heater For Your Safety Read Before LightingPressure Testing Gas Supply Piping System Pressure Testing Heater Gas ConnectionsTo Turn OFF GAS to Appliance Manual Lighting ProcedureLighting Instructions To Select Heating LevelThermostat Models FAS-3B and FAS-5B Inspecting Burner Cleaning and MaintenanceObserved Problem Possible Cause Remedy TroubleshootingInfrared Natural GAS Heater Top Replacement Parts SpecificationsService Hints Service Publications TechnicalFAN Kits UH1000FB and UHS1000FB AccessoriesParts Centrals Manual Shutoff Valve GA5010FA-3B Burner Assembly ODS/Pilot AssemblyIllustrated Parts Breakdown KEY FA-3B Description Parts ListFA-5B KEY FA-5B Description FAS-3B ODS/Pilot Assembly Burner AssemblyKEY FAS-3B Description QTY FAS-5B KEY FAS-5B Description QTY International Warranty Information