Desa FAS-5B Ventilation AIR, Ventilation Air From Inside Building, Ventilation Air From Outdoors

Page 6

INFRARED NATURAL GAS HEATER

FRESH AIR FOR COMBUSTION AND VENTILATION

Continued

VENTILATION AIR

Ventilation Air From Inside Building

This fresh air would come from an adjoining unconfined space. When ventilating to an adjoining unconfined space, you must pro- vide two permanent openings: one within 12" of the ceiling and one within 12" of the floor on the wall connecting the two spaces (see options 1 and 2, Figure 2). You can also remove door into adjoining room (see op- tion 3, Figure 2). Follow the National Fuel Gas Code NFPA 54/ANS Z223.1, Section

Ventilation

 

Grills

Or

into Adjoining

Remove

Room,

Door into

Option 1

Adjoining

 

Room,

 

Option 3

12"

Ventilation Grills

Into Adjoining Room,

Option 2

5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.

WARNING: Rework work- sheet, adding the space of the adjoining unconfined space. The combined spaces must have enough fresh air to supply all appliances in both spaces.

12"

Figure 2 - Ventilation Air from Inside Building

Ventilation Air From Outdoors

Provide extra fresh air by using ventilation grills or ducts. You must provide two per- manent openings: one within 12" of the ceiling and one within 12" of the floor. Connect these items directly to the outdoors or spaces open to the outdoors. These spaces include attics and crawl spaces.

IMPORTANT: Do not provide openings for inlet or outlet air into attic if attic has a thermostat-controlled power vent. Heated air entering the attic will activate the power vent.

Ventilated

Outlet Attic

Air

Outlet

 

Air

To Attic

 

To

Crawl

Space

Inlet

Air

Inlet Air

 

Ventilated

 

 

Crawl Space

 

 

Figure 3 - Ventilation Air from Outdoors

6

105566

Image 6
Contents Infrared VENT-FREE Natural GAS Heater What to do if YOU Smell GASSafety Information Infrared Natural GAS HeaterLocal Codes Product FeaturesProduct Identification UnpackingUnusually Tight Construction Fresh AIR for Combustion and VentilationProducing Adequate Ventilation Confined and Unconfined SpaceFresh AIR for Combustion Ventilation Determining FRESH-AIR Flow for Heater LocationDetermining if You Have a Confined or Unconfined Space Ventilation AIR Ventilation Air From Inside BuildingVentilation Air From Outdoors Locating Heater InstallationInstallation Items Check GAS TypeRemoving Front Panel Of Heater Models FA-3B and FA-5B Installing Heater to WallMounting Bracket Methods For Attaching Mounting Bracket To WallInstalling Bottom Mounting Screws Attaching Mounting Bracket To WallPlacing Heater On Mounting Bracket Connecting to GAS Supply Typical Inlet Pipe DiametersPressure Testing Heater Gas Connections For Your Safety Read Before LightingPressure Testing Gas Supply Piping System Operating HeaterTo Select Heating Level Manual Lighting ProcedureLighting Instructions To Turn OFF GAS to ApplianceThermostat Models FAS-3B and FAS-5B Cleaning and Maintenance Inspecting BurnerTroubleshooting Observed Problem Possible Cause RemedyInfrared Natural GAS Heater Top Service Publications Technical SpecificationsService Hints Replacement PartsManual Shutoff Valve GA5010 AccessoriesParts Centrals FAN Kits UH1000FB and UHS1000FBBurner Assembly ODS/Pilot Assembly Illustrated Parts BreakdownFA-3B Parts List KEY FA-3B DescriptionFA-5B KEY FA-5B Description ODS/Pilot Assembly Burner Assembly FAS-3BKEY FAS-3B Description QTY FAS-5B KEY FAS-5B Description QTY Warranty Information International