FRESH AIR

DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION

FOR

Determining if You Have a Confined or Unconfined Space

Use this worksheet to determine if you have a confined or unconfined space.

COMBUSTION

Space: Includes the room in which you will install heater plus any adjoining rooms with

AND

doorless passageways or ventilation grills between the rooms.

 

 

 

 

 

VENTILATION

1. Determine the volume of the space (length x width x height).

Length x Width x Height =

___________________

cu. ft. (volume of space)

Continued

Example:

Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) =

 

 

 

2560 cu. ft. (volume of space)

 

 

 

If additional ventilation to adjoining room is supplied with grills or openings, add the

 

volume of these rooms to the total volume of the space.

 

 

 

2. Divide the space volume by 50 cubic feet to determine the maximum BTU/Hr the space

 

can support.

 

 

 

 

 

 

 

 

____________ (volume of space) ÷ 50 cu. ft. = (Maximum BTU/Hr

 

the space can support)

 

 

 

 

 

 

 

Example: 2560 cu. ft. (volume of space) ÷ 50 cu. ft. =51.2 or 51,200 (maximum

 

BTU/Hr the space can support)

 

 

 

 

 

 

 

3. Add the BTU/Hr of all fuel burning appliances in the space.

 

 

Vent-free heater

 

 

___________________ BTU/Hr

 

 

Gas water heater*

 

 

___________________ BTU/Hr

 

 

Gas furnace

 

 

 

___________________ BTU/Hr

 

 

Vented gas heater

 

 

___________________ BTU/Hr

 

 

Gas fireplace logs

 

 

___________________ BTU/Hr

 

 

Other gas appliances*

+ ___________________ BTU/Hr

 

 

Total

 

= ___________________ BTU/Hr

 

Example:

Gas water heater

 

 

40,000

 

BTU/Hr

 

 

Vent-free heater

 

+

18,000

 

BTU/Hr

 

 

Total

 

=

 

 

 

BTU/Hr

 

 

 

58,000

 

*Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and vents to the outdoors.

4.Compare the maximum BTU/Hr the space can support with the actual amount of BTU/ Hr used.

_________________

BTU/Hr (maximum the space can support)

_________________

BTU/Hr (actual amount of BTU/Hr used)

Example: 51,200

BTU/Hr (maximum the space can support)

58,000

BTU/Hr (actual amount of BTU/Hr used)

The space in the above example is a confined space because the actual BTU/Hr used is more than the maximum BTU/Hr the space can support. You must provide additional fresh air. Your options are as follows:

A.Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoining room or add ventilation grills between rooms. See Ventilation Air From Inside Building, page 7.

B.Vent room directly to the outdoors. See Ventilation Air From Outdoors, page 8.

C.Install a lower BTU/Hr heater, if lower BTU/Hr size makes room unconfined.

If the actual BTU/Hr used is less than the maximum BTU/Hr the space can support, the space is an unconfined space. You will need no additional fresh air ventilation.

WARNING

WARNING ICON

G 001

You must provide additional ventilation air in a confined space.

6

100098

Image 6
Contents OWNER’S Operation and Installation Manual What to do if YOU Smell GASContents Safety InformationSafety Information Unpacking Product IdentificationLocal Codes ProductVentilation Fresh AIR ForCombustion Producing Adequate VentilationFresh AIR Determining FRESH-AIR Flow for Heater LocationDetermining if You Have a Confined or Unconfined Space Fresh AIR for Combustion and Ventilation Ventilation AIRVentilation Air From Inside Building Ventilation AIR Ventilation Air From OutdoorsCheck GAS Type Installing To WallInstallation Items Locating HeaterCeiling Floor163/4 RP30B CGP18B Removing Front Panel Of Heater Installing Heater to WallMounting Bracket Methods For Attaching Mounting Bracket To WallMarking Screw Locations Attaching Mounting Bracket To WallInstalling Bottom Mounting Screws Placing Heater On Mounting BracketSupply Connecting To GASQualified service person must connect heater to gas supply Follow all local codesConnections Pressure Testing GAS Supply Piping SystemChecking GAS Servicing. Correct all leaks at oncePressure Testing Heater GAS Connections CheckingHeater What to do if YOU Smell GASOperating Heater PilotBurner OperatingInspecting Pilot Flame PatternCorrect Flame Pattern AT High Position Inspecting BurnerBurner Flame Pattern Incorrect Flame Pattern AT High PositionTrouble Shooting CleaningMaintenance ODS/PILOT and BurnerTROUBLE- Shooting From Ing statement at TopTechnical Service Service HintsRP30B CGP18B Parts Not Under Warranty Replacement PartsParts Under Warranty CentralsAccessories Manual ShutoffFloor Mounting Stand GA4000B ODS/PILOT RP30B Parts List KEY Part Number Description QTY12-2 12-1 CGP18B Parts List Warranty Information Limited Warranty VENT-FREE Heaters