Desa VN10, VN6C Unusually Tight Construction, Determining FRESH-AIR Flow for Heater Location

Page 4

VANGUARD VN6C AND VN10

NATURAL GAS HEATER

AIR FOR COMBUSTION AND VENTILATION

Continued

UNUSUALLY TIGHT

CONSTRUCTION

The air that leaks around doors and win- dows may provide enough fresh air for combustion and ventilation. However, in buildings of unusually tight construction, you must provide additional fresh air.

Unusually tight construction is defined as construction where: a.walls and ceilings exposed to

the outside atmosphere have a continuous water vapor re- tarder with a rating of one perm (6x10-11kg per pa-sec-m2) or less with openings gasketed or sealed and

b.weather stripping has been added on openable windows and doors and

c.caulking or sealants are ap- plied to areas such as joints around window and door frames, between sole plates and floors, between wall-ceil- ing joints, between wall panels, at penetrations for plumbing, electrical, and gas lines, and at other openings.

If your home meets all of the three criteria above, you must provide ad- ditional fresh air. See Ventilation Air From Outdoors, page 5.

If your home does not meet all of the three criteria above, proceed to Deter- mining Fresh-Air Flow For Heater Lo- cation.

Confined and Unconfined Space

The National Fuel Gas Code (ANSIZ2123.1, 1992 Section 5.3) defines a confined space as a space whose volume is less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw) of the aggregate input rating of all appliances installed in that space and an unconfined space as a space whose volume is not less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw) of the aggregate input rating of all appliances installed in that

space. Rooms communicating directly with the space in which the appliances are in- stalled*, through openings not furnished with doors, are considered a part of the unconfined space.

*Adjoining rooms are communicating only if there are doorless passageways or ventila- tion grills between them.

DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION

Determining if You Have a Confined or Unconfined Space

Use this worksheet to determine if you have a confined or unconfined space.

Space: Includes the room in which you will install heater plus any adjoining rooms with doorless passageways or ventilation grills between the rooms.

1.Determine the volume of the space (length x width x height).

Length x Width x Height =

__________ cu. ft. (volume of space)

Example:

Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) = 2560 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or open- ings, add the volume of these rooms to the total volume of the space.

2.Divide the space volume by 50 cubic feet to determine the maximum Btu/Hr the space can support.

________ (volume of space) ÷ 50 cu.

ft. = (Maximum Btu/Hr the space can support)

Example: 2560 cu. ft. (volume of space) ÷ 50 cu. ft. = 51.2 or 51,200 (maximum Btu/Hr the space can sup- port)

3.Add the Btu/Hr of all fuel burning ap- pliances in the space.

Vent-free heater __________ Btu/Hr Gas water heater* ________ Btu/Hr

Gas furnace _____________ Btu/Hr Vented gas heater _________ Btu/Hr Gas fireplace logs ________ Btu/Hr

Other gas appliances*+ ____

Btu/Hr

Total

= ____

Btu/Hr

Example:

 

 

 

Gas water heater

 

40,000

Btu/Hr

Vent-free heater

+

10,000

Btu/Hr

 

=

 

 

Total

50,000

Btu/Hr

*Do not include direct-vent gas appli- ances. Direct-vent draws combustion air from the outdoors and vents to the outdoors.

4.Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

__________ Btu/Hr (maximum the

space can support)

__________ Btu/Hr (actual amount of

Btu/Hr used)

Example: 46,100 Btu/Hr (maximum the space can support)

50,000 Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a con- fined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows:

A.Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoining room or add ventila- tion grills between rooms. See Ventila- tion Air From Inside Building, page 5.

B.Vent room directly to the outdoors. See Ventilation Air From Outdoors, page 5.

C.Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no additional fresh air ventilation.

WARNING: If the area in which the heater may be operated is smaller than that defined as an unconfined space, provide ad- equate combustion and ventila- tion air by one of the methods described in the National Fuel Gas Code, ANSI Z223.1, 1992, Section 5.3 or applicable local codes.

4

101851

Image 4
Contents Infrared VENT-FREE Natural GAS Heater Models VN6C and VN10Safety Information Vanguard VN6C and VN10 Natural GAS HeaterProduct Features Product IdentificationAIR for Combustion and Ventilation Local CodesUnusually Tight Construction Determining FRESH-AIR Flow for Heater LocationConfined and Unconfined Space Determining if You Have a Confined or Unconfined SpaceVentilation Air From Inside Building Ventilation AIRVentilation Air From Outdoors Installing to Wall Installation ItemsInstalling Heater to Wall Check GAS TypeInstalling TWO Mounting Screws Installing Bottom Mounting ScrewPlacing Heater on Mounting Screws Removing Front Panel of HeaterConnecting to GAS Supply Gas ConnectionOperating Checking GAS ConnectionsHeater Operating Heater Lighting InstructionsTo Select Heating Level To Turn OFF GAS To ApplianceCleaning and Maintenance Inspecting BurnerTroubleshooting Observed Problem Possible Cause RemedyTroubleshooting Gas leak. See Warning statement be Technical Service Service Publications Replacement PartsSpecifications Service HintsParts List VN6CVN10 Vanguard VN6C and VN10 Natural GAS Heater 101851 Warranty Information