Goodman Mfg GPG13 White-Rodgers Model 36F22, White-Rodgers 36G22 Gas Supply And Manifold Check

Page 13

If having waited for five minutes and no gas smell is noted, move the gas control valve switch to the ON position.

9.Replace the heat exchanger door on the side of the unit.

10. Open the manual gas valve external to the unit. 11. Turn on the electrical power supply to the unit. 12. Set the thermostat to desired setting.

Gas Valve

 

On/Off

 

Selector

 

Switch

 

INLET

OUTLET

 

White-Rodgers Model 36F22

INLET

OUTLET

Gas Valve

On/Off

Selector

Switch

White-Rodgers 36G22

Gas Supply And Manifold Check

Gas supply pressure and manifold pressure with the burners operating must be as specified on the rating plate.

Gas Inlet Pressure Check

Gas inlet pressure must be checked and adjusted in accordance to the type of fuel being consumed.

With Power And Gas Off:

1.Connect a water manometer or adequate gauge to the inlet pressure tap of the gas valve.

Inlet gas pressure can also be measured by removing the cap from the dripleg and installing a predrilled cap with a hose fitting.

With Power And Gas On:

2.Put unit into heating cycle and turn on all other gas consuming appliances.

 

Inlet Gas Pressure

Natural

Min. 5.0" W.C., Max. 10.0" W.C.

Propane

Min. 11.0" W.C., Max. 13.0" W.C.

NOTE: Inlet Gas Pressure Must Not Exceed the Maximum Value Shown.

If operating pressures differ from above, make necessary pressure regulator adjustments, check piping size, etc., and/ or consult with local utility.

Gas Line

Gas

Shutoff

Valve

Gas Line

To Furnace

Open To

Atmosphere

Drip Leg Cap

With Fitting

Manometer Hose

Manometer

Measuring Inlet Gas Pressure

Alternate Method

Manifold Pressure Check

The gas valve has a tapped opening to facilitate measurement of the manifold pressure. A “U” Tube manometer having a scale range from 0 to 12 inches of water should be used for this measurement. The manifold pressure must be measured with the burners operating.

To adjust the pressure regulator, remove the adjustment screw or cover on the gas valve. Turn out (counterclockwise) to decrease pressure, turn in (clockwise) to increase pressure. Only small variations in gas flow should be made by means of the pressure regulator adjustment. In no case should the final manifold pressure vary more than plus or minus 0.3 inches water column from the specified nominal pressure. Any major changes in flow should be made by changing the size of the burner orifices. The measured input rate to the furnace must not exceed the rating specified on the unit rating plate.

For natural gas, the manifold pressure must be between 3.2 and 3.8 inches water column (3.5 nominal).

For propane gas, the manifold pressure must be between 9.7 and 10.3 inches water column (10.0 nominal).

Gas Input (Natural Gas Only) Check

To measure the gas input use a gas meter and proceed as follows:

1.Turn off gas supply to all other appliances except the unit.

2.With the unit operating, time the smallest dial on the meter for one complete revolution. If this is a 2 cubic foot dial, divide the seconds by 2; if it is a 1 cubic foot dial, use the seconds as is. This gives the seconds per cubic foot of gas being delivered to the unit.

3.INPUT=GAS HTG VALUE x 3600 / SEC. PER CUBIC FOOT Example: Natural gas with a heating value of 1000 BTU per cubic foot and 34 seconds per cubic foot as determined by Step 2, then:

Input = 1000 x 3600 / 34 = 106,000 BTU per Hour. NOTE: BTU content of the gas should be obtained from the gas supplier. This measured input must not be greater than shown on the unit rating plate.

4.Relight all other appliances turned off in step 1. Be sure all pilot burners are operating.

13

Image 13
Contents Ansi Z21.47CSA-2.3 Central Furnaces GPG13Index Safety Instructions Replacement PartsUnit Location Outside Slab InstallationRoof Curb Installation Rooftop InstallationGeneral Information GAS Piping Rigging DetailsRigging Natural Gas ConnectionGAS Piping Checks Proper Piping PracticePropane Gas Pipe Sizing Low Voltage Wiring Electrical WiringTypical Propane Gas Piping Y2 C R Y1 W G Typical Thermostat and Unit 24 V Wiring Hookup Filter Installation Duct Cover Installation Down Discharge Applications Circulating AIR and Filters Condensate Drain VentingNormal Sequences of Operation Be removed before operating unit Heat Anticipator Setting STARTUP, ADJUSTMENTS, and ChecksPG1348,60***1A only Rollout Protection ControlWith Power And Gas On With Power And Gas OffWhite-Rodgers Model 36F22 White-Rodgers 36G22 Gas Supply And Manifold CheckBlower Speed Adjustments Temperature Rise CheckMain Burner Flame Check External Static Pressure CheckTroubleshooting Pressure Switch Stuck Closed Pressure Switch Stuck OpenShort Cycle Compressor Delay Internal Control FailureFlame Sensor MaintenanceManifold Assembly Accessories and Functional PartsFunctional Parts List Burner FlameHeating Timing Chart Ignition Control Diagnostic Indicator ChartCooling Timing Chart Circulator BlowerAppendix Unit Dimensions GPG1324,30,36,421A Wiring Diagram GPG1324,30,36,421A Wiring Diagram GPG13481A Wiring Diagram B4312004 Rev. a GPG13601A Wiring Diagram B4312005 Rev. a GPG13363A Wiring Diagram 0140G00085P Comp GPG1348,603A Wiring Diagram0140G00087 GND Comp GPG13364A Wiring Diagram0140G00088 GPG1348,604A Wiring Diagram 0140G00089 GPG1348,601B Wiring Diagram INSTALLER/SERVICEMAN Thermostat Field Wiring Recommended Filter Sizes Minimum ClearancesThis page Left Blank Intentionally This page Left Blank Intentionally Quality Makes the Difference That’s why we know. . .There’s No Better Quality