Goodman Mfg GPG13 installation manual Proper Piping Practice, GAS Piping Checks

Page 7

Refer to the Proper Piping Practice drawing for the general layout at the unit. The following rules apply:

1.Use black iron pipe and fittings for the supply piping. The use of a flex connector and/or copper piping is permitted as long as it is in agreement with local codes.

2.Use pipe joint compound on male threads only. Pipe joint compound must be resistant to the action of the fuel used.

3.Use ground joint unions.

4.Install a drip leg to trap dirt and moisture before it can enter the gas valve. The drip leg must be a minimum of three inches long.

5.Use two pipe wrenches when making connection to the gas valve to keep it from turning.

6.Install a manual shut-off valve in a convenient location (within six feet of unit) between the meter and the unit.

7.Tighten all joints securely.

8.The unit must be connected to the building piping by one of the following methods:

Rigid metallic pipe and fittings

Semirigid metallic tubing and metallic fittings (Aluminum alloy tubing must not be used in exterior locations)

Listed gas appliance connectors used in accordance with the terms of their listing that are completely in the same room as the equipment

In the prior two methods above the connector or tubing must be protected from physical and thermal damage. Aluminum alloy tubing and connectors must be coated to protect against external corrosion when in contact with masonry, plaster or insulation or are subject to repeated wettings by liquids (water - not rain water, detergents or sewage)

MANUAL

SHUT-OFF

VALVE

DRIP LEG

GROUND JOINT UNION

(INSTALLED AHEAD OF GAS VALVE)

GROMMET

Proper Piping Practice

NOTE: The unit gas supply entrance is factory sealed with plugs. Keep plugs in place until gas supply is ready to be installed. Once ready, replace the plugs with the supplied grommets and install gas supply line.

GAS PIPING CHECKS

CAUTION

TO PREVENT PROPERTY DAMAGE OR PERSONAL INJURY DUE TO FIRE, THE FOLLOWING INSTRUCTIONS MUST BE PERFORMED REGARDING GAS CONNECTIONS AND PRESSURE TESTING:

THE UNIT AND ITS GAS CONNECTIONS MUST BE LEAK TESTED BEFORE PLACING IN OPERATION. BECAUSE OF THE DANGER OF EXPLOSION OR FIRE, NEVER USE A MATCH OR OPEN FLAME TO TEST FOR LEAKS. NEVER EXCEED SPECIFIED PRESSURES FOR TESTING. HIGHER PRESSURE MAY

DAMAGE GAS VALVE AND CAUSE OVERFIRING WHICH MAY RESULT IN PREMATURE HEAT EXCHANGE FAILURE.

THIS UNIT AND ITS SHUT-OFF VALVE MUST BE DISCONNECTED FROM

THE GAS SUPPLY DURING ANY PRESSURE TESTING OF THAT SYSTEM AT TEST PRESSURES IN EXCESS OF 1/2 PSIG (3.48 KPA).

THIS UNIT MUST BE ISOLATED FROM THE GAS SUPPLY SYSTEM BY CLOSING ITS MANUAL SHUT-OFF VALVE DURING ANY PRESSURE

TESTING OF THE GAS SUPPLY PIPING SYSTEM AT TEST PRESSURES EQUAL TO OR LESS THAN 1/2 PSIG (3.48 KPA).

WARNING

TO AVOID PROPERTY DAMAGE OR PERSONAL INJURY, BE SURE THERE IS

NO OPEN FLAME IN THE VICINITY DURING AIR BLEEDING.

There will be air in the gas supply line after testing for leaks on a new installation. Therefore, the air must be bled from the line by loosening the ground joint union until pure gas is expelled. Tighten union and wait for five minutes until all gas has been dissipated in the air. Be certain there is no open flame in the vicinity during air bleeding procedure. The unit is placed in operation by closing the main electrical disconnect switch for the unit.

PROPANE GAS INSTALLATIONS

WARNING

TO AVOID PROPERTY DAMAGE, PERSONAL INJURY OR DEATH DUE TO FIRE OR EXPLOSION CAUSED BY A PROPANE GAS LEAK, INSTALL A GAS DETECTING WARNING DEVICE. SINCE RUST CAN REDUCE THE LEVEL OF ODORANT IN PROPANE GAS, A GAS DETECTING WARNING DEVICE IS THE ONLY RELIABLE WAY TO DETECT A PROPANE GAS LEAK. CONTACT A LOCAL PROPANE GAS SUPPLIER ABOUT INSTALLING A GAS DETECTING WARNING DEVICE.

IMPORTANT NOTE: Propane gas conversion kits must be installed to convert units to propane gas.

All propane gas equipment must conform to the safety standards of the National Board of Fire Underwriters (See NBFU Manual 58).

For satisfactory operation, propane gas supply pressure must be within 9.7 - 10.3 inches W.C. at the manifold with all gas appliances in operation. Maintaining proper gas pressure depends on three main factors:

1.Vaporization rate, which depends on (a) temperature of the liquid, and (b) wetted surface area of the container or containers.

2.Proper pressure regulation.

3.Pressure drop in lines between regulators, and between second stage regulator and the appliance. Pipe size required will depend on length of pipe run and total load of all appliances.

7

Image 7
Contents Ansi Z21.47CSA-2.3 Central Furnaces GPG13Index Safety Instructions Replacement PartsUnit Location Outside Slab InstallationRoof Curb Installation Rooftop InstallationGeneral Information Natural Gas Connection Rigging DetailsGAS Piping RiggingGAS Piping Checks Proper Piping PracticePropane Gas Pipe Sizing Low Voltage Wiring Electrical WiringTypical Propane Gas Piping Y2 C R Y1 W G Typical Thermostat and Unit 24 V Wiring HookupFilter Installation Duct Cover Installation Down Discharge ApplicationsCirculating AIR and Filters Condensate Drain VentingNormal Sequences of Operation Rollout Protection Control STARTUP, ADJUSTMENTS, and ChecksBe removed before operating unit Heat Anticipator Setting PG1348,60***1A onlyWhite-Rodgers 36G22 Gas Supply And Manifold Check With Power And Gas OffWith Power And Gas On White-Rodgers Model 36F22External Static Pressure Check Temperature Rise CheckBlower Speed Adjustments Main Burner Flame CheckTroubleshooting Internal Control Failure Pressure Switch Stuck OpenPressure Switch Stuck Closed Short Cycle Compressor DelayFlame Sensor MaintenanceBurner Flame Accessories and Functional PartsManifold Assembly Functional Parts ListCirculator Blower Ignition Control Diagnostic Indicator ChartHeating Timing Chart Cooling Timing ChartAppendix Unit Dimensions GPG1324,30,36,421A Wiring Diagram GPG1324,30,36,421A Wiring Diagram GPG13481A Wiring Diagram B4312004 Rev. a GPG13601A Wiring Diagram B4312005 Rev. a GPG13363A Wiring Diagram 0140G00085P Comp GPG1348,603A Wiring Diagram0140G00087 GND Comp GPG13364A Wiring Diagram0140G00088 GPG1348,604A Wiring Diagram 0140G00089 GPG1348,601B Wiring Diagram INSTALLER/SERVICEMAN Thermostat Field Wiring Recommended Filter Sizes Minimum ClearancesThis page Left Blank Intentionally This page Left Blank Intentionally Quality Makes the Difference That’s why we know. . .There’s No Better Quality

GPG13 specifications

Goodman Manufacturing is a prominent name in the HVAC industry, known for providing high-quality heating and cooling systems. Among their diverse lineup, the Goodman GPG13 stands out as a reliable packaged gas/electric unit. This model is particularly designed for residential and light commercial applications, ensuring a perfect blend of efficiency, comfort, and affordability.

One of the primary features of the Goodman GPG13 is its energy efficiency. The unit has a Seasonal Energy Efficiency Ratio (SEER) rating that helps homeowners reduce their energy costs while providing optimal cooling performance during warmer months. With a cooling capacity ranging from 2.5 to 5 tons, it effectively meets the cooling requirements of various sizes of homes or commercial spaces.

The Goodman GPG13 employs advanced technology to guarantee reliable operation. Its quiet operation is a significant advantage, thanks to the sound-dampening design of the unit’s compressor and fan. Moreover, the unit is equipped with a high-efficiency scroll compressor, which is known for its durability and consistent performance. This technology not only enhances the unit’s longevity but also ensures that homeowners enjoy a peaceful indoor environment.

In terms of construction, the Goodman GPG13 is built to last. The unit features a heavy-gauge galvanized steel cabinet with a powder-coated finish, which protects it from the elements and corrosion. This sturdy design ensures that the GPG13 can withstand various environmental conditions without compromising performance. Additionally, it has an easy-access control panel, simplifying maintenance and servicing tasks.

Another noteworthy characteristic of the Goodman GPG13 is its environmentally friendly refrigerant, R-410A. Unlike older refrigerants, R-410A has a lower environmental impact and contributes to ozone layer protection. This focus on environmental responsibility is essential in today’s green-conscious society and reflects Goodman’s commitment to sustainable practices.

The GPG13 is also equipped with a reliable multi-speed blower motor that enhances comfort by providing consistent airflow throughout the space. This capability allows homeowners to maintain desired temperatures while maximizing energy savings.

Overall, the Goodman GPG13 packaged gas/electric unit is an excellent choice for those seeking efficiency, durability, and comfort in their heating and cooling systems. With its range of advanced features and technologies, it stands as a testament to Goodman Manufacturing's dedication to quality and customer satisfaction in HVAC solutions.