Goodman Mfg GPG13 Internal Control Failure, External Lockout, Pressure Switch Stuck Open

Page 16

ABNORMAL OPERATION - HEATING

Internal Control Failure

If the integrated ignition control in this unit encounters an internal fault, it will go into a “hard” lockout and turn off the diagnostic LED. If diagnostic LED indicates an internal fault, check power supply to unit for proper voltage, check all fuses, circuit breakers and wiring. Disconnect electric power for five seconds. If LED remains off after restoring power, replace control.

External Lockout

An external lockout occurs if the integrated ignition control determines that a measurable combustion cannot be established within three (3) consecutive ignition attempts. If flame is not established within the seven (7) second trial for ignition, the gas valve is deenergized, 15 second inter-purge cycle is completed, and ignition is reattempted. The control will repeat this routine three times if a measurable combustion is not established. The control will then shut off the induced draft blower and go into a lockout state.

If flame is established but lost, the control will energize the circulator blower at the heat speed and then begin a new ignition sequence. If flame is established then lost on subsequent attempts, the control will recycle for four (4) consecutive ignition attempts (five attempts total) before locking out.

The diagnostic fault code is 1 flash for a lockout due to failed ignition attempts or flame dropouts. The integrated control will automatically reset after one hour, or it can be reset by removing the thermostat signal or disconnecting the electrical power supply for over five seconds. If the diagnostic LED indicates an external lockout, perform the following checks:

Check the supply and manifold pressures

Check the gas orifices for debris

Check gas valve for proper operation

Check secondary limit

A dirty filter, excessive duct static, insufficient air flow, a faulty limit, or a failed circulator blower can cause this limit to open. Check filters, total external duct static, circulator blower motor, blower motor speed tap (see wiring diagram), and limit. An interruption in electrical power during a heating cycle may also cause the auxiliary limit to open. The automatic reset secondary limit is located on top of the circulator blower assembly.

Check rollout limit

If the burner flames are not properly drawn into the heat exchanger, the flame rollout protection device will open. Possible causes are restricted or blocked flue passages, blocked or cracked heat exchanger, a failed induced draft blower, or insufficient combustion air. The rollout protection device is a manual reset limit located on the burner bracket. The cause of the flame rollout must be determined and corrected before resetting the limit.

Check flame sensor

A drop in flame signal can be caused by nearly invisible coating on the sensor. Remove the sensor and carefully clean with steel wool.

Check wiring

Check wiring for opens/shorts and miswiring. Important: If you have to frequently reset your gas/electric package unit, it means that a problem exists that should be corrected. Contact a qualified servicer for further information.

Pressure Switch Stuck Open

A pressure switch stuck open can be caused by a faulty pressure switch, faulty wiring, a disconnected or damaged hose, a blocked or restricted flue, or a faulty induced draft blower.

If the control senses an open pressure switch during the pre- purge cycle, the induced draft blower only will be energized. If the pressure switch opens after ignition has begun the gas valve is deenergized, the circulator blower heat off cycle begins, and the induced draft blower remains on. The diagnostic fault code is two flashes.

Pressure Switch Stuck Closed

A stuck closed pressure switch can be caused by a faulty pressure switch or faulty wiring. If the control encounters a pressure switch stuck closed, the induced draft blower remains off. The diagnostic LED code for this fault is three (3) flashes.

Open Thermal Protection Device

If the primary limit switch opens, the gas valve is immediately deenergized, the induced draft and air circulating blowers are energized. The induced draft and air circulator blowers remain energized until the limit switch recloses. The diagnostic fault code for an open limit is four (4) flashes.

A primary limit will open due to excessive supply air temperatures. This can be caused by a dirty filter, excessive duct static, insufficient air flow, or a faulty limit. Check filters, total external duct static, blower motor, blower motor speed tap (see wiring diagram), and limit. This limit will automatically reset once the temperature falls below a preset level.

Flame Detected with Gas Valve Closed

If flame is detected with the gas valve deenergized, the combustion and air circulator blowers are energized. The diagnostic fault code is five (5) flashes for this condition. The control can be reset by removing the power supply to the unit or it will automatically reset after one hour. Miswiring is the probable cause for this fault.

ABNORMAL OPERATION - COOLING

Short Cycle Compressor Delay

The automatic ignition control has a built-in feature that prevents damage to the compressor in short cycling situations. In the event of intermittent power losses or intermittent thermostat operation, the ignition control will delay output to the compressor contactor for three minutes from the time power is restored. (Compressor is off a total of three minutes). The diagnostic LED will flash six (6) times to indicate the compressor contactor output is being delayed.

NOTE: Some electronic thermostats also have a built-in compressor short cycle timer that may be longer than the three minute delay given above. If you are using an electronic thermostat and the compressor has not started after three minutes, wait an additional five minutes to allow the thermostat to complete its short cycle delay time.

16

Image 16
Contents GPG13 Ansi Z21.47CSA-2.3 Central FurnacesIndex Replacement Parts Safety InstructionsOutside Slab Installation Unit LocationRoof Curb Installation Rooftop InstallationGeneral Information Rigging Details GAS PipingRigging Natural Gas ConnectionProper Piping Practice GAS Piping ChecksPropane Gas Pipe Sizing Low Voltage Wiring Electrical WiringTypical Propane Gas Piping Typical Thermostat and Unit 24 V Wiring Hookup Y2 C R Y1 W GFilter Installation Duct Cover Installation Down Discharge ApplicationsCirculating AIR and Filters Condensate Drain VentingNormal Sequences of Operation STARTUP, ADJUSTMENTS, and Checks Be removed before operating unit Heat Anticipator SettingPG1348,60***1A only Rollout Protection ControlWith Power And Gas Off With Power And Gas OnWhite-Rodgers Model 36F22 White-Rodgers 36G22 Gas Supply And Manifold CheckTemperature Rise Check Blower Speed AdjustmentsMain Burner Flame Check External Static Pressure CheckTroubleshooting Pressure Switch Stuck Open Pressure Switch Stuck ClosedShort Cycle Compressor Delay Internal Control FailureMaintenance Flame SensorAccessories and Functional Parts Manifold AssemblyFunctional Parts List Burner FlameIgnition Control Diagnostic Indicator Chart Heating Timing ChartCooling Timing Chart Circulator BlowerAppendix Unit Dimensions GPG1324,30,36,421A Wiring Diagram GPG1324,30,36,421A Wiring Diagram GPG13481A Wiring Diagram B4312004 Rev. a GPG13601A Wiring Diagram B4312005 Rev. a GPG13363A Wiring Diagram 0140G00085P GPG1348,603A Wiring Diagram Comp0140G00087 GPG13364A Wiring Diagram GND Comp0140G00088 GPG1348,604A Wiring Diagram 0140G00089 GPG1348,601B Wiring Diagram INSTALLER/SERVICEMAN Thermostat Field Wiring Minimum Clearances Recommended Filter SizesThis page Left Blank Intentionally This page Left Blank Intentionally That’s why we know. . .There’s No Better Quality Quality Makes the Difference

GPG13 specifications

Goodman Manufacturing is a prominent name in the HVAC industry, known for providing high-quality heating and cooling systems. Among their diverse lineup, the Goodman GPG13 stands out as a reliable packaged gas/electric unit. This model is particularly designed for residential and light commercial applications, ensuring a perfect blend of efficiency, comfort, and affordability.

One of the primary features of the Goodman GPG13 is its energy efficiency. The unit has a Seasonal Energy Efficiency Ratio (SEER) rating that helps homeowners reduce their energy costs while providing optimal cooling performance during warmer months. With a cooling capacity ranging from 2.5 to 5 tons, it effectively meets the cooling requirements of various sizes of homes or commercial spaces.

The Goodman GPG13 employs advanced technology to guarantee reliable operation. Its quiet operation is a significant advantage, thanks to the sound-dampening design of the unit’s compressor and fan. Moreover, the unit is equipped with a high-efficiency scroll compressor, which is known for its durability and consistent performance. This technology not only enhances the unit’s longevity but also ensures that homeowners enjoy a peaceful indoor environment.

In terms of construction, the Goodman GPG13 is built to last. The unit features a heavy-gauge galvanized steel cabinet with a powder-coated finish, which protects it from the elements and corrosion. This sturdy design ensures that the GPG13 can withstand various environmental conditions without compromising performance. Additionally, it has an easy-access control panel, simplifying maintenance and servicing tasks.

Another noteworthy characteristic of the Goodman GPG13 is its environmentally friendly refrigerant, R-410A. Unlike older refrigerants, R-410A has a lower environmental impact and contributes to ozone layer protection. This focus on environmental responsibility is essential in today’s green-conscious society and reflects Goodman’s commitment to sustainable practices.

The GPG13 is also equipped with a reliable multi-speed blower motor that enhances comfort by providing consistent airflow throughout the space. This capability allows homeowners to maintain desired temperatures while maximizing energy savings.

Overall, the Goodman GPG13 packaged gas/electric unit is an excellent choice for those seeking efficiency, durability, and comfort in their heating and cooling systems. With its range of advanced features and technologies, it stands as a testament to Goodman Manufacturing's dedication to quality and customer satisfaction in HVAC solutions.