Goodman Mfg ANSI Z21.47CSA-2.3 Roof Curb POST-INSTALLATION Checks, Roof TOP Duct Connections

Page 7

removal, to allow service access and to insure proper venti- lation and condenser airflow. The unit must not be installed beneath any obstruction. The unit should be installed re- mote from all building exhausts to inhibit ingestion of exhaust air into the unit fresh air intake.

INSULATED

PANELS

ROOF CURB INSTALLATION

ROOF CURB POST-INSTALLATION

CHECKS

After installation, check the top of the curb, duct connection frame and duct flanges to make sure gasket has been ap- plied properly. Gasket should be firmly applied to the top of the curb perimeter, duct flanges and any exposed duct con- nection frame. If gasket is loose, re-apply using strong weather resistant adhesive.

PROTRUSION

Inspect curb to ensure that none of the utility services (elec- tric) routed through the curb protrude above the curb.

CAUTION

IF PROTRUSIONS EXIST, DO NOT ATTEMPT TO SET UNIT ON CURB. INFORMATION SHOWN.

ROOF TOP DUCT CONNECTIONS

Install all duct connections on the unit before placing the unit on rooftop.

RIGGING DETAILS

WARNING

TO PREVENT PROPERTY DAMAGE, THE UNIT SHOULD REMAIN IN AN UPRIGHT POSITION DURING ALL RIGGING AND MOVING OPERATIONS. TO FACILITATE LIFTING AND MOVING WHEN A CRANE IS USED, PLACE THE UNIT IN AN ADEQUATE CABLE SLING.

CAUTION

DO NOT LIFT UNITS TWO AT A TIME. PROVISIONS FOR FORKS HAVE BEEN INCLUDED IN THE UNIT BASE FRAME. MINIMUM FORK LENGTH IS 72” TO PREVENT DAMAGE TO THE UNIT.

Provisions for forks have been included in the unit base frame. No other fork locations are approved.

WARNING

TO PREVENT POSSIBLE EQUIPMENT DAMAGE, PROPERTY DAMAGE, PERSONAL INJURY OR DEATH, THE FOLLOWING BULLET POINTS MUST BE OBSERVED WHEN INSTALLING THE UNIT.

Unit must be lifted by the four lifting holes located at the base frame corners.

Lifting cables should be attached to the unit with shackles.

The distance between the crane hook and the top of the unit must not be less than 60”.

Two spreader bars must span over the unit to prevent damage to the cabinet by the lift cables. Spreader bars must be of sufficient length so that cables do not come in contact with the unit during transport. Remove wood struts mounted beneath unit base frame before setting unit on roof curb. These struts are intended to protect unit base frame from fork lift damage. Removal is accomplished by extracting the sheet metal retainers and pulling the struts through the base of the unit. Refer to rigging label on the unit.

Important: If using bottom discharge with roof curb, duct- work should be attached to the curb prior to installing the unit. Ductwork dimensions are shown in Roof Curb Installa- tion Instructions.

Refer to the Roof Curb Installation Instructions for proper curb installation. Curbing must be installed in compliance with the National Roofing Contractors Association Manual.

Lower unit carefully onto roof mounting curb. While rigging unit, center of gravity will cause condenser end to be lower than supply air end.

7

Image 7
Contents CPG Series Safety Instructions Replacement PartsGeneral Information High Voltage Unit Location Electrical Entrance Locations Before installing this unitUnit Clearances ClearancesRigging Details Roof Curb POST-INSTALLATION ChecksRoof Curb Installation Roof TOP Duct ConnectionsCorner & Center of Gravity Locations Electrical WiringDrop Power and LOW Voltage Block LocationsCPG240 GAS Heat GAS Supply PipingProper Piping Practice Natural Gas ConnectionTypical Propane GAS Piping Propane GAS InstallationsVenting Condensate Drain Connection Circulating AIR and FiltersDrain Connection Moving Machinery Hazard STARTUP, ADJUSTMENTS, and ChecksRecommended Pounds of Force PER Belt Drive Belt Tension AdjustmentRollout Protection Control With Power And Gas On Burn Hazard Normal Sequence of Operation Heat Exchanger and Burner Orifice SpecificationsCheck rollout limit TroubleshootingInput Rating AIR Flow AdjustmentsMaintenance Motor Sheave AdjustmentsBurner Flame CPG180 Standard Belt Drive Appendix a Blower Performance Data Belt Drive High Static Appendix B Electrical Data Vertical Discharge TOP View Appendix C Unit DimensionsIIC 0140L00955 REV a IIC 0140L00957 REV a