Carrier 48HC Install Flue Hood and Combustion Air Hood, Install Gas Piping, Gas Supply Line

Page 16

To assemble the outside air hood:

1.Remove hood top panel from shipping position on unit end.

2.Install four angles to the upper end panel using the screws provided.

3.Apply seal strip to mating flanges on the side plates of the hood (see Fig. 14).

The combustion air hood is attached to the back of the burner access panel. Remove the two screws securing the hood to the back of the burner access panel. Using the two screws, re-attach the hood to the front of the burner access panel as shown in Fig. 16.

48HC

Apply Seal Strip to the front of this flange

Apply Seal Strips to the back of these flanges

2

Seal Strips

5

6

 

 

 

Apply Seal Strips

3

Apply Seal Strip

 

to the back of

 

 

these surfaces

 

to the front of

 

 

 

this flange

 

 

 

7

 

7

 

 

 

 

 

2

 

 

4

4

 

4

5

 

 

4

 

 

 

 

 

 

 

 

6

 

 

 

Apply Seal Strip

 

 

 

to the back of

 

1

 

this flange

Item #

Description

Qty

 

1

Angles

4

 

2

Side Plates

2

 

3

Hood

1

 

4

Outdoor Air Screens

4

 

5

Side Filter Supports

2

 

6

Side Drip Angles

2

 

7

Top Diverters

2

 

Combustion

Flue Hood

Air Hood

 

C10744

Fig. 16 - Flue Hood and Combustion Air Hood Details

C09079

Fig. 14 - Hood Part Identification and Seal Strip

Application Areas

4.Secure side plates to panel using the screws provided.

5.Apply seal strip to mating flange of the hood (see Fig. 14).

6.Secure top flange using screws provided in kit.

7.Install outdoor air screens by sliding them into the channel formed by the four angles installed in step 2. Make sure that the screens extend across the entire length of the hood.

8.Install side filter supports using the screws provided.

9.Install side drip angles using the screws provided.

10.Run a continuous length of seal strip across the hood covering the engagement holes in the lower hood.

11.Install top diverter using the screws provided.

12.On units with barometric relief, remove screws at bot- tom of relief damper. Do not discard damper door.

C09090

Fig. 15 - Hood Assembly – Completed

Step 9 — Install Flue Hood and Combustion Air Hood

The flue hood is shipped screwed to the fan deck inside the burner compartment. Remove the burner access panel and then remove the flue hood from its shipping location. Using the screws provided, install flue hood in the location shown in Fig. 16.

Step 10 — Install Gas Piping

Installation of the gas piping must be in accordance with local building codes and with applicable national codes. In U.S.A., refer to NFPA 54/ANSI Z223.1 National Fuel Gas Code (NFGC). In Canada, installation must be accordance with the CAN/CSA B149.1 and CAN/CSA B149.2 installation codes for gas burning appliances.

This unit is factory equipped for use with Natural Gas fuel at elevations up to 2000 ft (610 m) above sea level. Unit may be field converted for operation at elevations above 2000 ft (610 m) and/or for use with liquefied petroleum fuel. See accessory kit installation instructions regarding these accessories.

NOTE: Furnace gas input rate on rating plate is for installation up to 2000 ft (610 m) above sea level. In U.S.A. the input rating for altitudes above 2000 ft (610 m) must be derated by 4% for each 1000 ft (305 m) above sea level. In Canada the input rating must be derated by 10% for altitudes of 2000 ft (610 m) to 4500 ft (1372 m) above sea level.

For natural gas applications, gas pressure at unit gas connection must not be less than 5 in. wg (1246 Pa) or greater than 13 in. wg (3240 Pa) while the unit is operating. For liquified petroleum applications, the gas pressure must not be less than 11 in. wg (2740 Pa) or greater than 13 in. wg (3240 Pa) at the unit connection.

Gas Supply Line —

The gas supply pipe enters the unit adjacent to the burner access panel on the front side of the unit, through the grommeted hole. The gas connection to the unit is made to the 3/4 in. FPT gas inlet port on the unit gas valve.

Table 2 lists typical 3/4 inch NPT (National Pipe Thread) field supplied pipe fittings required for Thru-Base gas supply, starting from the unit gas valve (see Fig. 17).

16

Image 16
Contents Installation Instructions Safety Considerations Unit Dimensional Drawing 17 Size Unit C10897 Unit Dimensional Drawing 20 and 24 Size Units C10893 Unit Dimensional Drawing 28 Size Unit C10901 Plan for Unit Location Operating WeightsRoof Mount Inspect unit Plan for Sequence of Unit InstallationProvide Unit Support Roof Curb Details 17 Size Unit Roof Curb Details 20 and 24 Size Units Roof Curb Details 28 Size Unit Field Fabricate Ductwork Rig and Place UnitHorizontal Duct Connection Install Outside Air Hood Factory OptionPositioning on Curb Install Flue Hood and Combustion Air Hood Install Gas PipingTo assemble the outside air hood Gas Supply LineTypical 3/4-in NPT Field Supplied Piping Parts Natural Gas Supply Line Pressure RangesFactory-Option Thru-Base Connections Orifice HoleField Power Supply Install External Condensate Trap and LineMake Electrical Connections Units with Factory-Installed Disconnect All UnitsPowered Convenience Outlet Wiring Field Control Wiring Units without Thru-Base ConnectionsThermostat Unit without Thru-Base Connection KitTransformer Connection for 208-v Power Supply Typical Low-Voltage Control ConnectionsHumidi-MiZerRControl Connections Humidi-MiZer Space RH ControllerTo connect the Carrier humidistat HL38MG029 To connect the Thermidistat device 33CS2PPRH-01OAT RRS Srtn PremierLinkt Factory-Option PremierLink ControllerPremierLink Wiring Schematic PremierLink Wiring Schematic with Humidi-MiZerR Supply Air Temperature SAT Sensor Field ConnectionsEconoMi$er2 PremierLink Sensor UsageSpace Sensor Mode Thermostat ModeConfigure the Unit for Thermostat Mode Space SensorsEconomizer Controls Indoor Air Quality CO2 SensorSpace Relative Humidity Sensor Installation To wire the sensorFilter Status Switch Supply Fan Status SwitchPower Exhaust output Smoke Detector/Fire Shutdown FSDCCN Communication Bus Connecting CCN Bus Color Code RecommendationsRecommended Cables RTU Open Control System RTU Open Multi-Protocol Control BoardRTU Open System Control Wiring Diagram RTU Open System Control Wiring Diagram with Humidi-MiZerR RTU Open Controller Inputs and Outputs Type of I/O Connection PIN Name Numbers Dedicated InputsSpace Temperature SPT Sensors RTU Open T-55 Sensor ConnectionsSpace Relative Humidity Sensor Typical Wiring Relative Humidity Sensors Space or Duct MountedDuct Relative Humidity Sensor Typical Wiring Connecting Discrete InputsCommunication Wiring Protocols GeneralLocal Access RTU Open TroubleshootingLEDs Outdoor Air Enthalpy ControlDifferential Enthalpy Control Return Air Sensor Tube Installation WiringSmoke Detectors To install the return air sensor sampling tube Unit Wire/Fuse or Hacr Breaker Sizing DataSmoke Detector Test Magnet Additional Application DataUnit NOM IFM FAN Motor Exhaust Unbalanced 3-Phase Supply Voltage Adjust Factory-Installed Options Install AccessoriesEconoMi$er IV Occupancy Switch Pre-Start and Start-Up48HC Catalog No 48HC---11SI

48HC specifications

The Carrier 48HC is a highly efficient rooftop HVAC unit designed for commercial applications that prioritize both performance and energy savings. This unit embodies Carrier's commitment to innovation by integrating advanced technologies and features that address the modern demands of building climate control.

One of the standout features of the Carrier 48HC is its exceptional energy efficiency. Employing the latest in variable-speed compressor technology, the unit adjusts its output based on the specific cooling needs of the space, which not only enhances comfort levels but also significantly reduces energy consumption. This feature is crucial for businesses looking to lower their operational costs while minimizing their environmental impact.

The Carrier 48HC is also equipped with a comprehensive range of control options. Through its intelligent control systems, users can utilize features such as demand ventilation, which optimizes indoor air quality while maintaining energy efficiency. The integration with building management systems (BMS) further enhances operational effectiveness, allowing real-time monitoring and adjustments from a centralized point.

Additionally, the 48HC is designed with durability in mind. Its robust construction resists harsh weather conditions and ensures long-lasting performance. The unit features advanced corrosion-resistant materials and coatings, which prolong its lifespan and reduce maintenance needs. This durability makes the 48HC a reliable choice for varying environments, whether it’s an industrial setting or a more delicate commercial space.

The unit’s compact design also deserves mention, as it facilitates easier installation on rooftops without taking up excessive space. The modular design allows for customization, enabling businesses to tailor their systems to fit specific heating and cooling requirements.

In terms of comfort, the Carrier 48HC employs efficient air distribution technology that ensures even airflow throughout the space. This greatly enhances occupant comfort by eliminating hot or cold spots, promoting a consistent indoor climate.

Finally, the 48HC complies with stringent environmental regulations and standards. With options for environmentally-friendly refrigerants, it supports businesses in their sustainability efforts while operating effectively under current regulations.

In summary, the Carrier 48HC stands out in the crowded HVAC market due to its advanced technology, energy efficiency, durability, and adaptability for commercial applications, making it a top choice for those looking to invest in a reliable and effective climate control solution.