Carrier 48HC installation instructions Plan for Unit Location, Roof Mount, Operating Weights

Page 9

INSTALLATION

Jobsite Survey

Complete the following checks before installation.

1.Consult local building codes and the NEC (National Electrical Code) ANSI/NFPA 70 for special installa- tion requirements.

2.Determine unit location (from project plans) or select unit location.

3.Check for possible overhead obstructions which may interfere with unit lifting or rigging.

Step 1 — Plan for Unit Location

Select a location for the unit and its support system (curb or other) that provides for the minimum clearances required for safety. This includes the clearance to combustible surfaces, unit performance and service access below, around and above unit as specified in unit drawings. See Fig. 4.

NOTE: Consider also the effect of adjacent units.

96” (2438)

36” (914)

42” (1067)

42” (1067)

36” (914)

C10638

Fig. 4 - Service Clearance Dimensional Drawing

Be sure that the unit is installed such that snow will not block the combustion air intake or flute outlet.

Unit may be installed directly on wood flooring or on Class A, B, or C roof-covering material when roof curb is used.

Do not install unit in an indoor location. Do not locate air inlets near exhaust vents or other sources of contaminated air. For proper unit operation, adequate combustion and ventilation air must be provided in accordance with Section 5.3 (Air for Combustion and Ventilation) of the National Fuel Gas Code, ANSI Z223.1 (American National Standards Institute) and NFPA (National Fire Protection Association) 54 TIA--54--84--1. In Canada, installation must be in accordance with the CAN1--B149 installation codes for gas burning appliances.

Although unit is weatherproof, avoid locations that permit water from higher level runoff and overhangs to fall onto the unit.

Locate mechanical draft system flue assembly at least 4 ft (1.2 m) from any opening through which combustion products could enter the building, and at least 4 ft (1.2 m) from any adjacent building (or per local code). Locate the flue assembly at least 10 ft (3.05 m) from an adjacent unit’s fresh air intake hood if within 3 ft (0.91 m) of same elevation (or per local code). When unit is located adjacent to public walkways, flue assembly must be at least 7 ft (2.1 m) above grade.

Select a unit mounting system that provides adequate height to allow installation of condensate trap per requirements. Refer to Step 11 — Install External Condensate Trap and Line – for required trap dimensions.

Roof Mount —

Check building codes for weight distribution requirements. Unit operating weight is shown in Table 1.

48HC

Table 1 – Operating Weights

48HC**

 

 

 

UNIT LB (KG)

 

17

20

24

 

 

 

 

 

 

Base Unit

1892 (858)

2102 (954)

2247

(1019)

 

 

 

 

 

 

 

Economizer

245

(111)

245

(111)

245

(111)

 

 

 

 

 

 

 

Powered Outlet

32

(15)

32

(15)

32

(15)

 

 

 

 

 

 

 

Humidi--- MiZerR System

83

(38)

83

(38)

88

(40)

Curb

 

 

 

 

 

 

14--- in/356 mm

273

(124)

273

(124)

273

(124)

24--- in/610 mm

350

(159)

350

(159)

350

(159)

 

 

 

 

 

 

 

28

2292 (1040)

245(111)

32(15)

92(42)

273(124)

350(159)

9

Image 9
Contents Installation Instructions Safety Considerations Unit Dimensional Drawing 17 Size Unit C10897 Unit Dimensional Drawing 20 and 24 Size Units C10893 Unit Dimensional Drawing 28 Size Unit C10901 Operating Weights Plan for Unit LocationRoof Mount Plan for Sequence of Unit Installation Inspect unitProvide Unit Support Roof Curb Details 17 Size Unit Roof Curb Details 20 and 24 Size Units Roof Curb Details 28 Size Unit Rig and Place Unit Field Fabricate DuctworkInstall Outside Air Hood Factory Option Horizontal Duct ConnectionPositioning on Curb Install Gas Piping Install Flue Hood and Combustion Air HoodTo assemble the outside air hood Gas Supply LineNatural Gas Supply Line Pressure Ranges Typical 3/4-in NPT Field Supplied Piping PartsOrifice Hole Factory-Option Thru-Base ConnectionsInstall External Condensate Trap and Line Field Power SupplyMake Electrical Connections All Units Units with Factory-Installed DisconnectPowered Convenience Outlet Wiring Units without Thru-Base Connections Field Control WiringThermostat Unit without Thru-Base Connection KitTypical Low-Voltage Control Connections Transformer Connection for 208-v Power SupplyHumidi-MiZer Space RH Controller Humidi-MiZerRControl ConnectionsTo connect the Carrier humidistat HL38MG029 To connect the Thermidistat device 33CS2PPRH-01OAT RRS Srtn PremierLink Controller PremierLinkt Factory-OptionPremierLink Wiring Schematic PremierLink Wiring Schematic with Humidi-MiZerR Field Connections Supply Air Temperature SAT SensorEconoMi$er2 PremierLink Sensor UsageThermostat Mode Space Sensor ModeSpace Sensors Configure the Unit for Thermostat ModeIndoor Air Quality CO2 Sensor Economizer ControlsTo wire the sensor Space Relative Humidity Sensor InstallationSupply Fan Status Switch Filter Status SwitchPower Exhaust output Smoke Detector/Fire Shutdown FSDConnecting CCN Bus Color Code Recommendations CCN Communication BusRecommended Cables RTU Open Multi-Protocol Control Board RTU Open Control SystemRTU Open System Control Wiring Diagram RTU Open System Control Wiring Diagram with Humidi-MiZerR Type of I/O Connection PIN Name Numbers Dedicated Inputs RTU Open Controller Inputs and OutputsRTU Open T-55 Sensor Connections Space Temperature SPT SensorsRelative Humidity Sensors Space or Duct Mounted Space Relative Humidity Sensor Typical WiringConnecting Discrete Inputs Duct Relative Humidity Sensor Typical WiringGeneral Communication Wiring ProtocolsRTU Open Troubleshooting Local AccessOutdoor Air Enthalpy Control LEDsDifferential Enthalpy Control Wiring Return Air Sensor Tube InstallationSmoke Detectors Unit Wire/Fuse or Hacr Breaker Sizing Data To install the return air sensor sampling tubeSmoke Detector Test Magnet Additional Application DataUnit NOM IFM FAN Motor Exhaust Unbalanced 3-Phase Supply Voltage Install Accessories Adjust Factory-Installed OptionsEconoMi$er IV Occupancy Switch Pre-Start and Start-Up48HC Catalog No 48HC---11SI

48HC specifications

The Carrier 48HC is a highly efficient rooftop HVAC unit designed for commercial applications that prioritize both performance and energy savings. This unit embodies Carrier's commitment to innovation by integrating advanced technologies and features that address the modern demands of building climate control.

One of the standout features of the Carrier 48HC is its exceptional energy efficiency. Employing the latest in variable-speed compressor technology, the unit adjusts its output based on the specific cooling needs of the space, which not only enhances comfort levels but also significantly reduces energy consumption. This feature is crucial for businesses looking to lower their operational costs while minimizing their environmental impact.

The Carrier 48HC is also equipped with a comprehensive range of control options. Through its intelligent control systems, users can utilize features such as demand ventilation, which optimizes indoor air quality while maintaining energy efficiency. The integration with building management systems (BMS) further enhances operational effectiveness, allowing real-time monitoring and adjustments from a centralized point.

Additionally, the 48HC is designed with durability in mind. Its robust construction resists harsh weather conditions and ensures long-lasting performance. The unit features advanced corrosion-resistant materials and coatings, which prolong its lifespan and reduce maintenance needs. This durability makes the 48HC a reliable choice for varying environments, whether it’s an industrial setting or a more delicate commercial space.

The unit’s compact design also deserves mention, as it facilitates easier installation on rooftops without taking up excessive space. The modular design allows for customization, enabling businesses to tailor their systems to fit specific heating and cooling requirements.

In terms of comfort, the Carrier 48HC employs efficient air distribution technology that ensures even airflow throughout the space. This greatly enhances occupant comfort by eliminating hot or cold spots, promoting a consistent indoor climate.

Finally, the 48HC complies with stringent environmental regulations and standards. With options for environmentally-friendly refrigerants, it supports businesses in their sustainability efforts while operating effectively under current regulations.

In summary, the Carrier 48HC stands out in the crowded HVAC market due to its advanced technology, energy efficiency, durability, and adaptability for commercial applications, making it a top choice for those looking to invest in a reliable and effective climate control solution.