Carrier 48HC installation instructions Unit NOM IFM FAN Motor Exhaust

Page 48

48HC

Table 11 - Unit Wire/Fuse or HACR Breaker Sizing Data (cont)

 

 

 

COMBUSTION

POWER

 

 

 

 

w/ PWRD C.O.

 

 

 

UNIT

NOM.

IFM

FAN MOTOR

EXHAUST

 

NO P.E.

 

 

 

w/ P.E. (pwrd fr/ unit)

 

 

 

 

 

 

 

 

 

 

 

 

V---Ph---Hz

TYPE

FLA

FLA

MCA

FUSE or

 

DISC. SIZE

MCA

FUSE or

DISC. SIZE

 

 

 

HACR

 

 

 

HACR

 

 

 

 

 

 

 

 

BRKR

 

FLA

LRA

 

BRKR

FLA

LRA

 

 

STD

 

 

73.1

90.0

 

77

398

84.9

100.0

90

418

 

208/230---3---60

MED

0.52

5.9

75.8

100.0

 

80

415

87.6

100.0

93

435

 

 

HIGH

 

 

80.6

100.0

 

85

424

92.4

100.0

99

444

48HC*D17

 

 

 

 

 

 

 

 

 

 

 

 

 

 

STD

 

 

37.1

45.0

 

39

236

43.3

50.0

46

248

460---3---60

MED

0.3

3.1

38.5

50.0

 

41

245

44.7

50.0

48

257

 

 

 

 

HIGH

 

 

41.1

50.0

 

44

249

47.3

60.0

51

261

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

STD

 

 

27.9

35.0

 

29

186

32.7

40.0

35

194

 

575---3---60

MED

0.24

2.4

27.9

35.0

 

29

186

32.7

40.0

35

194

 

 

HIGH

 

 

30.7

40.0

 

33

200

35.5

45.0

38

208

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

STD

 

 

80.5

100

 

85

445

92.3

100

98

465

 

208/230---3---60

MED

0.52

5.9

85.3

100

 

90

454

97.1

110

104

474

 

 

HIGH

 

 

90.7

100

 

96

464

102.5

125

110

484

48HC*D20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

STD

 

 

38.8

50

 

41

247

45

50

48

259

460---3---60

MED

0.3

3.1

41.4

50

 

44

251

47.6

60

51

263

 

 

 

 

HIGH

 

 

44.2

50

 

47

256

50.4

60

54

268

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

STD

 

 

27.9

35

 

29

188

32.7

40

35

196

 

575---3---60

MED

0.24

2.4

30.7

40

 

33

202

35.5

45

38

210

 

 

HIGH

 

 

34.1

40

 

36

200

38.9

45

42

208

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

STD

 

 

93.5

110.0

 

99

549

105.3

125.0

112

569

 

208/230---3---60

MED

0.52

5.9

98.9

125

 

105

559

110.7

125

119

579

 

 

HIGH

 

 

112.4

125

 

120

633

124.2

150

133

653

48HC*D24

 

 

 

 

 

 

 

 

 

 

 

 

 

 

STD

 

 

50.8

60.0

 

54

279

57.0

70.0

61

291

460---3---60

MED

0.3

3.1

53.6

60

 

57

284

59.8

70

64

296

 

 

 

 

HIGH

 

 

59.6

70

 

64

321

65.8

80

71

333

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

STD

 

 

37.2

45.0

 

39

206

42.0

50.0

45

214

 

575---3---60

MED

0.24

2.4

40.6

50

 

43

204

45.4

50

49

212

 

 

HIGH

 

 

41.1

50

 

44

231

45.9

50

49

239

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

STD

 

 

122.2

150.0

 

127

589

134.0

175.0

140

609

 

208/230---3---60

MED

0.52

5.9

127.6

175

 

133

599

139.4

175

147

619

 

 

HIGH

 

 

140.3

175

 

148

673

152.1

200

161

693

48HC*D28

 

 

 

 

 

 

 

 

 

 

 

 

 

 

STD

 

 

56.2

70.0

 

59

305

62.4

80.0

66

317

 

 

 

 

 

 

460---3---60

MED

0.3

3.1

59

70

 

62

310

65.2

80

70

322

 

 

HIGH

 

 

65

80

 

69

347

71.2

80

76

359

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

STD

 

 

42.1

50.0

 

44

230

46.9

60.0

50

238

 

575---3---60

MED

0.24

2.4

45.5

60

 

48

228

50.3

60

54

236

 

 

HIGH

 

 

46

60

 

49

255

50.8

60

54

263

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE: See page 49 for table legend and notes.

48

Image 48
Contents Installation Instructions Safety Considerations Unit Dimensional Drawing 17 Size Unit C10897 Unit Dimensional Drawing 20 and 24 Size Units C10893 Unit Dimensional Drawing 28 Size Unit C10901 Operating Weights Plan for Unit LocationRoof Mount Plan for Sequence of Unit Installation Inspect unitProvide Unit Support Roof Curb Details 17 Size Unit Roof Curb Details 20 and 24 Size Units Roof Curb Details 28 Size Unit Field Fabricate Ductwork Rig and Place UnitInstall Outside Air Hood Factory Option Horizontal Duct ConnectionPositioning on Curb Install Flue Hood and Combustion Air Hood Install Gas PipingTo assemble the outside air hood Gas Supply LineTypical 3/4-in NPT Field Supplied Piping Parts Natural Gas Supply Line Pressure RangesFactory-Option Thru-Base Connections Orifice HoleInstall External Condensate Trap and Line Field Power SupplyMake Electrical Connections Units with Factory-Installed Disconnect All UnitsPowered Convenience Outlet Wiring Field Control Wiring Units without Thru-Base ConnectionsThermostat Unit without Thru-Base Connection KitTransformer Connection for 208-v Power Supply Typical Low-Voltage Control ConnectionsHumidi-MiZerRControl Connections Humidi-MiZer Space RH ControllerTo connect the Carrier humidistat HL38MG029 To connect the Thermidistat device 33CS2PPRH-01OAT RRS Srtn PremierLinkt Factory-Option PremierLink ControllerPremierLink Wiring Schematic PremierLink Wiring Schematic with Humidi-MiZerR Supply Air Temperature SAT Sensor Field ConnectionsEconoMi$er2 PremierLink Sensor UsageSpace Sensor Mode Thermostat ModeConfigure the Unit for Thermostat Mode Space SensorsEconomizer Controls Indoor Air Quality CO2 SensorSpace Relative Humidity Sensor Installation To wire the sensorFilter Status Switch Supply Fan Status SwitchPower Exhaust output Smoke Detector/Fire Shutdown FSDConnecting CCN Bus Color Code Recommendations CCN Communication BusRecommended Cables RTU Open Control System RTU Open Multi-Protocol Control BoardRTU Open System Control Wiring Diagram RTU Open System Control Wiring Diagram with Humidi-MiZerR RTU Open Controller Inputs and Outputs Type of I/O Connection PIN Name Numbers Dedicated InputsSpace Temperature SPT Sensors RTU Open T-55 Sensor ConnectionsSpace Relative Humidity Sensor Typical Wiring Relative Humidity Sensors Space or Duct MountedDuct Relative Humidity Sensor Typical Wiring Connecting Discrete InputsCommunication Wiring Protocols GeneralLocal Access RTU Open TroubleshootingOutdoor Air Enthalpy Control LEDsDifferential Enthalpy Control Wiring Return Air Sensor Tube InstallationSmoke Detectors To install the return air sensor sampling tube Unit Wire/Fuse or Hacr Breaker Sizing DataSmoke Detector Test Magnet Additional Application DataUnit NOM IFM FAN Motor Exhaust Unbalanced 3-Phase Supply Voltage Adjust Factory-Installed Options Install AccessoriesEconoMi$er IV Occupancy Switch Pre-Start and Start-Up48HC Catalog No 48HC---11SI

48HC specifications

The Carrier 48HC is a highly efficient rooftop HVAC unit designed for commercial applications that prioritize both performance and energy savings. This unit embodies Carrier's commitment to innovation by integrating advanced technologies and features that address the modern demands of building climate control.

One of the standout features of the Carrier 48HC is its exceptional energy efficiency. Employing the latest in variable-speed compressor technology, the unit adjusts its output based on the specific cooling needs of the space, which not only enhances comfort levels but also significantly reduces energy consumption. This feature is crucial for businesses looking to lower their operational costs while minimizing their environmental impact.

The Carrier 48HC is also equipped with a comprehensive range of control options. Through its intelligent control systems, users can utilize features such as demand ventilation, which optimizes indoor air quality while maintaining energy efficiency. The integration with building management systems (BMS) further enhances operational effectiveness, allowing real-time monitoring and adjustments from a centralized point.

Additionally, the 48HC is designed with durability in mind. Its robust construction resists harsh weather conditions and ensures long-lasting performance. The unit features advanced corrosion-resistant materials and coatings, which prolong its lifespan and reduce maintenance needs. This durability makes the 48HC a reliable choice for varying environments, whether it’s an industrial setting or a more delicate commercial space.

The unit’s compact design also deserves mention, as it facilitates easier installation on rooftops without taking up excessive space. The modular design allows for customization, enabling businesses to tailor their systems to fit specific heating and cooling requirements.

In terms of comfort, the Carrier 48HC employs efficient air distribution technology that ensures even airflow throughout the space. This greatly enhances occupant comfort by eliminating hot or cold spots, promoting a consistent indoor climate.

Finally, the 48HC complies with stringent environmental regulations and standards. With options for environmentally-friendly refrigerants, it supports businesses in their sustainability efforts while operating effectively under current regulations.

In summary, the Carrier 48HC stands out in the crowded HVAC market due to its advanced technology, energy efficiency, durability, and adaptability for commercial applications, making it a top choice for those looking to invest in a reliable and effective climate control solution.