Carrier 48HC installation instructions Relative Humidity Sensors Space or Duct Mounted

Page 41

isolated 24 vac power source to the sensor and to connect the sensor to the control board terminals.

To connect the sensor to the control, identify the positive (4 to 20 mA) and ground (SIG COM) terminals on the sensor. See Fig. 46. Connect the 4-20 mA terminal to RTU Open terminal J4-2 and connect the SIG COM terminal to RTU Open terminal J4-3. See Fig. 63.

IAQ Sensor

4-20mA J4-2

SIG COM J4-3 24 VAC

C10738

Fig. 63 - RTU Open / Indoor CO2 Sensor

(33ZCSENCO2) Connections

Outdoor Air Quality Sensor (PNO 33ZCSENCO2 plus weatherproof enclosure) —

The outdoor air CO2 sensor is designed to monitor carbon dioxide (CO2) levels in the outside ventilation air and interface with the ventilation damper in an HVAC system. The OAQ sensor is packaged with an outdoor cover. See Fig. 48. The outdoor air CO2 sensor must be located in the economizer outside air hood.

Wiring the Outdoor Air CO2 Sensor: A dedicated power supply is required for this sensor. A two-wire cable is required to wire the dedicated power supply for the sensor. The two wires should be connected to the power supply and terminals 1 and 2.

To connect the sensor to the control, identify the positive (4 to 20 mA) and ground (SIG COM) terminals on the OAQ sensor. See Fig. 46. Connect the 4 to 20 mA terminal to RTU Open terminal J4-5. Connect the SIG COM terminal to RTU Open terminal J4-6. See Fig. 64.

OAQ Sensor/RH Sensor

4-20mA J4-5

SIG COM J4-6 24 VAC

C10739

Fig. 64 - RTU Open / Outdoor CO2 Sensor

(33ZCSENCO2) Connections

Space Relative Humidity Sensor or Humidistat —

 

Humidi-MiZerRControl Wiring: In units equipped

 

with the Humidi-MiZer option there are two pink (PNK)

 

wires loose in the control box used to control the

 

dehumidification function of the unit. These pink wires

 

are meant to be tied to a space humidistat or thermidistat

 

on an electromechanical unit. On RTU Open equipped

 

units these pink wires must be connected to J11-7 & 8 to

 

allow the Open board to operate the dehumidification

 

function for the unit. Disconnect the J11 Phoenix style

 

connector from the board and use the plug screws to

 

secure the pink wires in pins 7 and 8, reconnect the plug

 

to the board at J11.

 

Relative Humidity Sensors (Space or Duct Mounted):

 

The accessory space humidity sensor (33ZCSENSRH-01)

 

 

or duct humidity sensor (33ZCSENDRH-01) is used to

 

measure the relative humidity of air within the space or

48HC

return air duct. The RH reading is used to control the

Humidi-MiZer option of the rooftop unit. For wiring

 

distances up to 500 ft (152 m), use a 3-conductor, 18 or

 

20 AWG shielded cable. The shield must be removed

 

from the sensor end of the cable and grounded at the unit

 

end. The current loop power for sensor is provided by the

 

RTU Open controller as 24vdc. Refer to the instructions

 

supplied with the RH sensor for the electrical

 

requirements and terminal locations. RTU Open

 

configurations must be changed after adding an RH

 

sensor. See Fig. 65 and 66 for typical RH sensor wiring.

 

S J4-1 or J4-4 = 24vdc loop power

 

S J4-2 or J4-5 = 4-20mA signal input

 

NOTE: The factory default for dehumidification control

 

is normally open humidistat.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MOUNTING

HOLES

 

WIRING

Io Vin Gnd Vo

OPENING

SW2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

5

4

3

2

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Vin -

J4-1 or J4-4

24Vdc

Io -

J4-2 or J4-5

-20mA output

C11087

Fig. 65 - Space Relative Humidity Sensor Typical Wiring

41

Image 41
Contents Installation Instructions Safety Considerations Unit Dimensional Drawing 17 Size Unit C10897 Unit Dimensional Drawing 20 and 24 Size Units C10893 Unit Dimensional Drawing 28 Size Unit C10901 Roof Mount Operating WeightsPlan for Unit Location Provide Unit Support Plan for Sequence of Unit InstallationInspect unit Roof Curb Details 17 Size Unit Roof Curb Details 20 and 24 Size Units Roof Curb Details 28 Size Unit Rig and Place Unit Field Fabricate DuctworkPositioning on Curb Install Outside Air Hood Factory OptionHorizontal Duct Connection Install Gas Piping Install Flue Hood and Combustion Air HoodTo assemble the outside air hood Gas Supply LineNatural Gas Supply Line Pressure Ranges Typical 3/4-in NPT Field Supplied Piping PartsOrifice Hole Factory-Option Thru-Base ConnectionsMake Electrical Connections Install External Condensate Trap and LineField Power Supply All Units Units with Factory-Installed DisconnectPowered Convenience Outlet Wiring Units without Thru-Base Connections Field Control WiringThermostat Unit without Thru-Base Connection KitTypical Low-Voltage Control Connections Transformer Connection for 208-v Power SupplyHumidi-MiZer Space RH Controller Humidi-MiZerRControl ConnectionsTo connect the Carrier humidistat HL38MG029 To connect the Thermidistat device 33CS2PPRH-01OAT RRS Srtn PremierLink Controller PremierLinkt Factory-OptionPremierLink Wiring Schematic PremierLink Wiring Schematic with Humidi-MiZerR Field Connections Supply Air Temperature SAT SensorEconoMi$er2 PremierLink Sensor UsageThermostat Mode Space Sensor ModeSpace Sensors Configure the Unit for Thermostat ModeIndoor Air Quality CO2 Sensor Economizer ControlsTo wire the sensor Space Relative Humidity Sensor InstallationSupply Fan Status Switch Filter Status SwitchPower Exhaust output Smoke Detector/Fire Shutdown FSDRecommended Cables Connecting CCN Bus Color Code RecommendationsCCN Communication Bus RTU Open Multi-Protocol Control Board RTU Open Control SystemRTU Open System Control Wiring Diagram RTU Open System Control Wiring Diagram with Humidi-MiZerR Type of I/O Connection PIN Name Numbers Dedicated Inputs RTU Open Controller Inputs and OutputsRTU Open T-55 Sensor Connections Space Temperature SPT SensorsRelative Humidity Sensors Space or Duct Mounted Space Relative Humidity Sensor Typical WiringConnecting Discrete Inputs Duct Relative Humidity Sensor Typical WiringGeneral Communication Wiring ProtocolsRTU Open Troubleshooting Local AccessDifferential Enthalpy Control Outdoor Air Enthalpy ControlLEDs Smoke Detectors WiringReturn Air Sensor Tube Installation Unit Wire/Fuse or Hacr Breaker Sizing Data To install the return air sensor sampling tubeSmoke Detector Test Magnet Additional Application DataUnit NOM IFM FAN Motor Exhaust Unbalanced 3-Phase Supply Voltage Install Accessories Adjust Factory-Installed OptionsEconoMi$er IV Occupancy Switch Pre-Start and Start-Up48HC Catalog No 48HC---11SI

48HC specifications

The Carrier 48HC is a highly efficient rooftop HVAC unit designed for commercial applications that prioritize both performance and energy savings. This unit embodies Carrier's commitment to innovation by integrating advanced technologies and features that address the modern demands of building climate control.

One of the standout features of the Carrier 48HC is its exceptional energy efficiency. Employing the latest in variable-speed compressor technology, the unit adjusts its output based on the specific cooling needs of the space, which not only enhances comfort levels but also significantly reduces energy consumption. This feature is crucial for businesses looking to lower their operational costs while minimizing their environmental impact.

The Carrier 48HC is also equipped with a comprehensive range of control options. Through its intelligent control systems, users can utilize features such as demand ventilation, which optimizes indoor air quality while maintaining energy efficiency. The integration with building management systems (BMS) further enhances operational effectiveness, allowing real-time monitoring and adjustments from a centralized point.

Additionally, the 48HC is designed with durability in mind. Its robust construction resists harsh weather conditions and ensures long-lasting performance. The unit features advanced corrosion-resistant materials and coatings, which prolong its lifespan and reduce maintenance needs. This durability makes the 48HC a reliable choice for varying environments, whether it’s an industrial setting or a more delicate commercial space.

The unit’s compact design also deserves mention, as it facilitates easier installation on rooftops without taking up excessive space. The modular design allows for customization, enabling businesses to tailor their systems to fit specific heating and cooling requirements.

In terms of comfort, the Carrier 48HC employs efficient air distribution technology that ensures even airflow throughout the space. This greatly enhances occupant comfort by eliminating hot or cold spots, promoting a consistent indoor climate.

Finally, the 48HC complies with stringent environmental regulations and standards. With options for environmentally-friendly refrigerants, it supports businesses in their sustainability efforts while operating effectively under current regulations.

In summary, the Carrier 48HC stands out in the crowded HVAC market due to its advanced technology, energy efficiency, durability, and adaptability for commercial applications, making it a top choice for those looking to invest in a reliable and effective climate control solution.