Carrier 48HC Plan for Sequence of Unit Installation, Inspect unit, Provide Unit Support

Page 10

48HC

Step 2 — Plan for Sequence of Unit Installation

The support method used for this unit will dictate different sequences for the steps of unit installation. For example, on curb-mounted units, some accessories must be installed on the unit before the unit is placed on the curb. Review the following for recommended sequences for installation steps.

Curb-mounted installation —

Install curb

Install field-fabricated ductwork inside curb

Install thru-base service connection fittings (affects curb and unit)

Rig and place unit Remove top skid Install outside air hood Install smoke detector tube Install combustion air hood Install flue hood

Install gas piping

Install condensate line trap and piping Make electrical connections

Install other accessories

Pad-mounted installation —

Prepare pad and unit supports Rig and place unit

Remove duct covers and top skid

Install smoke detector return air sensor tube

Install field-fabricated ductwork at unit duct openings Install outside air hood

Install combustion air hood Install flue hood

Install gas piping

Install condensate line trap and piping Make electrical connections

Install other accessories

Frame-mounted installation —

Frame-mounted applications generally follow the sequence for a curb installation. Adapt as required to suit specific installation plan.

Step 3 — Inspect unit

Inspect unit for transportation damage. File any claim with transportation agency.

Confirm before installation of unit that voltage, amperage and circuit protection requirements listed on unit data plate agree with power supply provided.

Locate the carton containing the outside air hood parts; see Figs. 5 and 12. Do not remove carton until unit has been rigged and located in final position.

Step 4 — Provide Unit Support

Roof Curb Mount —

Accessory roof curb details and dimensions are shown in Figs. 6, 7 and 8. Assemble and install accessory roof curb in accordance with instructions shipped with the curb.

NOTE: The gasketing of the unit to the roof curb is critical for a watertight seal. Install gasket supplied with the roof curb as shown in Figs. 6, 7 and 8. Improperly applied gasket can also result in air leaks and poor unit performance.

Curb should be level. This is necessary for unit drain to function properly. Unit leveling tolerances are show in Fig. 9. Refer to Accessory Roof Curb Installation Instructions for additional information as required.

Install insulation, cant strips, roofing felt, and counter flashing as shown. Ductwork must be attached to curb and not to the unit. Thru-the-base power connection must be installed before the unit is set on the roof curb. If field-installed thru-the-roof curb gas connections are desired remove knockout in basepan located in the gas section, see Fig. 5 for location. Gas connections and power connections to the unit must be field installed after the unit is installed on the roof curb.

If electric and control wiring is to be routed through the basepan, remove knockouts in basepan located in control box area of access panel; see Fig. 1, 2, or 3 for basepan knockout locations for location. Attach the service connections to the basepan.

Hood Carton Location

(rear access panel)

Control Box

Access Panel

Filter and

Indoor Coil

Access Panel

Indoor Blower

Access Panel

Gas Heat

Access PanelCompressor

(each side)

C11154

Fig. 5 - Typical Access Panel and Compressor Locations

Slab Mount (Horizontal Units Only) —

Provide a level concrete slab that extends a minimum of 6–in. (150 mm) beyond unit cabinet. Install a gravel apron in front of condenser coil air inlet to prevent grass and foliage from obstructing airflow.

NOTE: Horizontal units may be installed on a roof curb if required.

Alternate Unit Support (In Lieu of Curb or Slab Mount) —

A non-combustible sleeper rail can be used in the unit curb support area. If sleeper rails cannot be used, support the long sides of the unit with a minimum of 4 equally spaced 4-in. x 4-in. (102 mm x 102 mm) pads on each side. Locate pads so that they support the rails. Make sure to avoid the fork openings.

10

Image 10
Contents Installation Instructions Safety Considerations Unit Dimensional Drawing 17 Size Unit C10897 Unit Dimensional Drawing 20 and 24 Size Units C10893 Unit Dimensional Drawing 28 Size Unit C10901 Plan for Unit Location Operating WeightsRoof Mount Inspect unit Plan for Sequence of Unit InstallationProvide Unit Support Roof Curb Details 17 Size Unit Roof Curb Details 20 and 24 Size Units Roof Curb Details 28 Size Unit Field Fabricate Ductwork Rig and Place UnitHorizontal Duct Connection Install Outside Air Hood Factory OptionPositioning on Curb To assemble the outside air hood Install Flue Hood and Combustion Air HoodInstall Gas Piping Gas Supply LineTypical 3/4-in NPT Field Supplied Piping Parts Natural Gas Supply Line Pressure RangesFactory-Option Thru-Base Connections Orifice HoleField Power Supply Install External Condensate Trap and LineMake Electrical Connections Units with Factory-Installed Disconnect All UnitsPowered Convenience Outlet Wiring Thermostat Field Control WiringUnits without Thru-Base Connections Unit without Thru-Base Connection KitTransformer Connection for 208-v Power Supply Typical Low-Voltage Control ConnectionsTo connect the Carrier humidistat HL38MG029 Humidi-MiZerRControl ConnectionsHumidi-MiZer Space RH Controller To connect the Thermidistat device 33CS2PPRH-01OAT RRS Srtn PremierLinkt Factory-Option PremierLink ControllerPremierLink Wiring Schematic PremierLink Wiring Schematic with Humidi-MiZerR EconoMi$er2 Supply Air Temperature SAT SensorField Connections PremierLink Sensor UsageSpace Sensor Mode Thermostat ModeConfigure the Unit for Thermostat Mode Space SensorsEconomizer Controls Indoor Air Quality CO2 SensorSpace Relative Humidity Sensor Installation To wire the sensorPower Exhaust output Filter Status SwitchSupply Fan Status Switch Smoke Detector/Fire Shutdown FSDCCN Communication Bus Connecting CCN Bus Color Code RecommendationsRecommended Cables RTU Open Control System RTU Open Multi-Protocol Control BoardRTU Open System Control Wiring Diagram RTU Open System Control Wiring Diagram with Humidi-MiZerR RTU Open Controller Inputs and Outputs Type of I/O Connection PIN Name Numbers Dedicated InputsSpace Temperature SPT Sensors RTU Open T-55 Sensor ConnectionsSpace Relative Humidity Sensor Typical Wiring Relative Humidity Sensors Space or Duct MountedDuct Relative Humidity Sensor Typical Wiring Connecting Discrete InputsCommunication Wiring Protocols GeneralLocal Access RTU Open TroubleshootingLEDs Outdoor Air Enthalpy ControlDifferential Enthalpy Control Return Air Sensor Tube Installation WiringSmoke Detectors Smoke Detector Test Magnet To install the return air sensor sampling tubeUnit Wire/Fuse or Hacr Breaker Sizing Data Additional Application DataUnit NOM IFM FAN Motor Exhaust Unbalanced 3-Phase Supply Voltage EconoMi$er IV Occupancy Switch Adjust Factory-Installed OptionsInstall Accessories Pre-Start and Start-Up48HC Catalog No 48HC---11SI

48HC specifications

The Carrier 48HC is a highly efficient rooftop HVAC unit designed for commercial applications that prioritize both performance and energy savings. This unit embodies Carrier's commitment to innovation by integrating advanced technologies and features that address the modern demands of building climate control.

One of the standout features of the Carrier 48HC is its exceptional energy efficiency. Employing the latest in variable-speed compressor technology, the unit adjusts its output based on the specific cooling needs of the space, which not only enhances comfort levels but also significantly reduces energy consumption. This feature is crucial for businesses looking to lower their operational costs while minimizing their environmental impact.

The Carrier 48HC is also equipped with a comprehensive range of control options. Through its intelligent control systems, users can utilize features such as demand ventilation, which optimizes indoor air quality while maintaining energy efficiency. The integration with building management systems (BMS) further enhances operational effectiveness, allowing real-time monitoring and adjustments from a centralized point.

Additionally, the 48HC is designed with durability in mind. Its robust construction resists harsh weather conditions and ensures long-lasting performance. The unit features advanced corrosion-resistant materials and coatings, which prolong its lifespan and reduce maintenance needs. This durability makes the 48HC a reliable choice for varying environments, whether it’s an industrial setting or a more delicate commercial space.

The unit’s compact design also deserves mention, as it facilitates easier installation on rooftops without taking up excessive space. The modular design allows for customization, enabling businesses to tailor their systems to fit specific heating and cooling requirements.

In terms of comfort, the Carrier 48HC employs efficient air distribution technology that ensures even airflow throughout the space. This greatly enhances occupant comfort by eliminating hot or cold spots, promoting a consistent indoor climate.

Finally, the 48HC complies with stringent environmental regulations and standards. With options for environmentally-friendly refrigerants, it supports businesses in their sustainability efforts while operating effectively under current regulations.

In summary, the Carrier 48HC stands out in the crowded HVAC market due to its advanced technology, energy efficiency, durability, and adaptability for commercial applications, making it a top choice for those looking to invest in a reliable and effective climate control solution.