Ei Electronics Ei261DENRC, Ei261ENRC What Happens When Your CO Alarm Detects Carbon Monoxide ?

Page 8

B16132-R0-261ENRC-UC-ENG 7/11/07 11:52 AM Page 8

2.3 WHAT HAPPENS WHEN YOUR CO ALARM DETECTS CARBON MONOXIDE ?

When the Alarm detects potentally dangerous levels of CO, it flashes the red alarm light and then sounds a loud alarm if the CO persists. The digital display (Model Ei261DENRC only) indicates the CO level in parts per million (ppm) CO.

Table B below shows how the CO Alarm reacts to different levels of CO gas and exposure time. At higher levels of CO the alarm turns on sooner. The rate of flashing of the red light indicates the level of CO.

Table B: CO Alarm Response

CO Level

Red

Horn sounds

(ppm)

Alarm Light

within

0

Off *

Off

50

1 Flash / 2 Seconds

60 to 90 minutes

100

2 Flashes / Second

10 to 40 minutes

300

4 Flashes / Second

3 minutes

*unless it has been in alarm (see 2.4 CO Alarm Memory overleaf)

If your CO Alarm sounds follow the instructions on page 5.

When ventilation is provided by leaving windows and doors open, the CO build up may have dissipated by the time help arrives and the alarm may have stopped sounding. Although your problem may appear temporarily solved, it is crucial that the source of the CO is determined and appropriate repairs made.

8

Image 8
Contents Mains Powered Carbon Monoxide Alarms B16132-R0-261ENRC-UC-ENG 7/11/07 1152 AM Contents Important Information What to do When the Alarm Sounds What is Carbon Monoxide ? Symptoms of Carbon Monoxide PoisoningCarbon Monoxide the Silent Killer High levels of CO in a house can be caused byInhalation Time approx and Symptoms Developed Table a Effects of Carbon Monoxide PoisoningWhat Happens When Your CO Alarm Detects Carbon Monoxide ? Never Ignore the Alarm CO Alarm MemoryUnsuitable Locations Alarm PositioningIdeally a Carbon Monoxide CO Alarm should be Installed B16132-R0-261ENRC-UC-ENG 7/11/07 1152 AM B16132-R0-261ENRC-UC-ENG 7/11/07 1152 AM Location in room with a fuel burning appliance Location in rooms with Installation Alarm InstallationInstallation Procedure B16132-R0-261ENRC-UC-ENG 7/11/07 1152 AM Surface Wiring Interconnecting Testing Testing with Carbon Monoxide Do not paint the CO Alarm HOW to Distinguish Between CO Alarm & Smoke Alarm WarningsMaintenance HOW to Disconnect and Remove the Alarm Sensor Module ReplacementLimitations of CO Alarms HOW to Protect Your Family B16132-R0-261ENRC-UC-ENG 7/11/07 1152 AM Getting Your CO Alarm Serviced Five Year GuaranteeTechnical Specifications B16132-R0-261ENRC-UC-ENG 7/11/07 1152 AM Alarm Beeps and Amber Light Flashes Every 40 Seconds TroubleshootingAlarm does not Work When the Test Button is Pressed Alarm Sounds for no Apparent Reason Test/Hush Button does not Silence AlarmsAccessories CheckB16132-R0-261ENRC-UC-ENG 7/11/07 1152 AM Ei Electronics