Next to or directly above heaters or air conditioning vents, windows, wall vents etc. that can change the direction of airflow and cause rapid temperature fluctuations.

In very high or awkward areas (e.g. over stairwells) where it may be difficult to reach the unit (for testing, hushing etc.).

Locate away from very dusty or dirty areas as dust build-up in the optical sensor chamber can impair performance. It can also block the insect screen mesh and prevent smoke from entering the chamber.

Locate the unit at least 1m from dimmer controlled lights and wiring as some dimmers can cause interference.

Locate the unit at least 1.5m and route wiring at least 1m away from fluorescent light fittings as electrical “noise” and/or flickering may affect the unit. Do not wire into the same circuit as fluorescent lights or dimmers.

Do not locate in insect infested areas. Small insects getting into the optical sensor chamber can cause intermittent alarms. Insects and contamination on the heat sensor can increase its response time.

5. INSTALLATION

The Alarm is designed to be permanently mounted, using it’s own built-in terminal block to connect it to the mains. The mounting plate can be screwed directly to the ceiling. Alternatively it can be screwed to a standard junction box. It requires a current of 60mA. The Alarm must not be exposed to dripping or splashing. There are important markings on the underside of the alarm.

IMPORTANT PRECAUTION: Do not install alarms in new or renovated buildings until all work is completed (including floor coverings) and the building has been

17

Image 17
Contents Installer Instructions Contents Interconnect ALL Alarms Installation Guide Alarm Removal Increased Longevity and Ruggedness Reduced Nuisance AlarmsFaster Response to a wider range of fires Single Person Interconnect Test Replace Alarm IndicatorAlarm Memory Fire Risk Assessment Categories of System LD3 Minimum Protection LD2 Additional Protection LD1 Optimum Protection Alarm Type Selecting Alarm Type Improved Audibility Grade D, E & F SystemsPositioning Alarms Locations To Avoid DON’T place Heat Alarms in any of the following areasInstallation B16350-R0-Ei2100 SERIES-U&C.qxd 18/9/08 346 PM Mounting & Wiring Alarms B16350-R0-Ei2100 SERIES-U&C.qxd 18/9/08 346 PM Removeable Trunking Door for B16350-R0-Ei2100 SERIES-U&C.qxd 18/9/08 346 PM Interconnecting Alarms B16350-R0-Ei2100 SERIES-U&C.qxd 18/9/08 346 PM Relay Module Ei128R Remote Control Switch Ei1529RCRadioLINK Base Ei168RC B16350-R0-Ei2100 SERIES-U&C.qxd 18/9/08 346 PM B16350 Rev0 Ei Electronics