Hearth and Home Technologies EL42 Series, EL36 Series Accessories, Gas Log/Lighter Provision

Page 44

12 Accessories

A. Gas Log/Lighter Provision

WARNING! Fire and/or Asphyxiation Risk! Use with solid wood fuel or decorative gas appliance only. Gas fire generates fumes.

DO NOT install unvented gas logs

Damper must be locked fully open when gas logs are installed

A certified gas log lighter or decorative gas log set can be installed in this fireplace.

Maximum input is 100,000 BTU/hr.

Decorative gas appliance must be certified to ANSI Z21.60 “Standard for Decorative Gas Appliances for Installation in Vented Fireplaces”.

Must be installed in accordance with the National Fuel

Gas Code, ANSI Z223.1.

A gas log set must incorporate a gas shutoff.

Gas Log set requires the damper to be locked fully open.

A listed automatic damper system with safety interlock may be used in this fireplace with only compatible, listed gas log sets. See damper system manufacturer’s insturctions.

Knockouts are provided on both sides of the fireplace and in refractories for 1/2 in. (13 mm) iron pipe.

Seal refractory around pipe with fireplace mortar or a non-combustible sealant.

B. Wood Burning Inserts

WARNING! Risk of Fire! Improper installation of wood in- serts may cause fireplace or chimney system to overheat.

If a wood burning insert is being installed in this fireplace, Hearth & Home Technologies recommends full reline of the chimney.

Cooling air openings at the top of the chimney must not be obstructed in any manner.

Hearth & Home Technologies recommends securing the reline at the top of the flue and using the cap certified for use with this fireplace system.

Firebox

Refractory

Seal with fireplace mortar or non-combust- ible sealant

Outer Shell

of Fireplace

Maintain air clearance to combustibles.

Combustible

Materials

Gas Line

Repack

Insulation

Knockout

Gas Line

4 in. (102 mm)

1 1/2 in. (38 mm) air space around

pipe

Combustible materials may be located at zero clearance to gas line beyond 4 in. (102 mm) from fireplace side.

Figure 12.1 Gas Line Installation

44

Heatilator • EL36/EL42 • 4044-132 • Rev V • 11/08

Image 44
Contents Wood Burning Fireplace OperationHot screen/mesh and glass doors will cause burns Fire RiskNumber Listing Label Information/LocationGrate User Guide Table of ContentsInstaller Guide Warranty Hearth & Home Technologies Limited Warranty CONDITIONS, Exclusions & Limitation of LiabilityHeatilator EL36/EL42 4044-132 Rev V 11/08 Listing and Code Approvals Appliance CertificationNon-Combustible Materials Combustible MaterialsHot glass will cause burns Operating InstructionsYour Fireplace Seasoned Wood Starting a FireGrate FirescreenGlass Doors Vented Gas Log Sets & Gas Log LightersOptional Components Clear SpaceWood Fuel Maintainance and Service Chimney Inspection/CleaningDisposal of Ashes Creosote Formation and Need for RemovalGlass Cleaning Check Firebox RefractoryInspect Grate Frequency As desiredTroubleshooting Guide Start Fire Problems Possible Cause SolutionInstaller Guide Getting StartedNegative Pressure Design and Installation ConsiderationsDraft Locating Fireplace & Chimney Frequently open doors Central heat outlets or returnsInspect Fireplace and Components Tools and Supplies NeededFireplace System Requirements Select Fireplace Location Mm all configurationsFraming & Clearances Clearances Clearances to Combustible MaterialsFrame the Fireplace Fireplace Outside Model # Opening DimensionsSidewalls/Surrounds Installation of Fireplace Things to ConsiderPosition the Fireplace Place Protective Metal Hearth StripsFt min. from top of uppermost chimney section to air inlet YESInstall Outside Air Kit Outside Air InstallationChimney Assembly Maintain minimum height of chimney above roofChimney Requirements Height of Chimney ComponentsUsing Offsets/Returns ExampleInstall Chimney Air Kit Assemble Chimney SectionsInstall Ceiling Firestops Installing the Ceiling FirestopInstall Attic Insulation Shield Prepare Attic Insulation ShieldComplete Installation Install FlashingFollowing steps should be skipped if using a chase Cut out Hole in RoofChimney Termination Requirements Flat RoofsChase Installations Construct the ChaseGas line holes and other openings should be caulked with Chase should be constructed in the manner of allInstall as per Sections 7 Install Fireplace & ChimneyInstall Chase Top Install Termination Cap ST375 Square Termination CapTS345/TS345P Square Termination Cap TCT375 Terra Cotta CapShrouds Radiation ShieldField Constructed Shrouds Open Top Shroud TR342 caps require radiation shieldMailbox Style Shroud radiation shield required Roofed Style Shroud radiation shield requiredFinishing Hearth Extension= 1/k x inches of thickness Refer to .2 for hearth extension insulation alternativesRaised Hearth Extension Framing Minimum betweenNon-combustible Sealant Noncombustible Finishing MaterialsFinishing Material In. Micore or equivilent insulationCombustible Mantel Clearances to Mantels or other Combustibles above FireplaceOutside Di- mensions ModelAccessories Gas Log/Lighter ProvisionWood Burning Inserts Gas Code, Ansi Z223.1Fireplace Dimensions Reference Materials1321 mm 406 mm 1676 mm 508 mm 13 mmID4 Insulated Duct Mm i.d 1067 mm UD4 Uninsulated Duct Air Kit PartsChimney Components Catalog #Effective Outside Height Diameter 10-1/2 121 mm 267 mm 10-1/2 267 mm305 mm 27-3/8 24-5/8 695 mm 625 mm 305 mm 24-5/8 625 mm 787 mm10-7/8 276 mm Rev V 11/08 Service PartsHeatilator EL36/EL42 EL42 Contact Information