Hearth and Home Technologies I60 Accessories, Gas Log/Lighter Provision, Wood Burning Inserts

Page 46

12 Accessories

A. Gas Log/Lighter Provision

WARNING! Fire and/or Asphyxiation Risk! Use with solid wood fuel or decorative gas appliance only. Gas fire generates fumes.

DO NOT install unvented gas logs

Damper must be locked fully open when gas logs are installed

A certified gas log lighter or decorative gas log set can be installed in this fireplace.

Maximum input is 100,000 BTU/hr.

Decorative gas appliance must be certified to ANSI Z21.60 “Standard for Decorative Gas Appliances for Installation in Vented Fireplaces”.

Must be installed in accordance with the National Fuel

Gas Code, ANSI Z223.1.

A gas log set must incorporate a gas shutoff.

Gas Log set requires the damper to be locked fully open.

A listed automatic damper system with safety interlock may be used in this fireplace with only compatible, listed gas log sets. See damper system manufacturer’s insturctions.

Knockouts are provided on both sides of the fireplace and in refractories for 1/2 in. (13 mm) iron pipe.

Seal refractory around pipe with fireplace mortar or a non-combustible sealant.

B. Wood Burning Inserts

WARNING! Risk of Fire! Improper installation of wood in- serts may cause fireplace or chimney system to overheat.

If a wood burning insert is being installed in this fireplace, Hearth & Home Technologies recommends full reline of the chimney.

Cooling air openings at the top of the chimney must not be obstructed in any manner.

Hearth & Home Technologies recommends securing the reline at the top of the flue and using the cap certified for use with this fireplace system.

Firebox

Refractory

Seal with fireplace mortar or non-combust- ible sealant

Outer Shell

of Fireplace

Maintain air clearance to combustibles.

Combustible

Materials

Gas Line

Repack

Insulation

Knockout

Gas Line

4 in. (102 mm)

1 1/2 in. (38 mm) air space around

pipe

Combustible materials may be located at zero clearance to gas line beyond 4 in. (102 mm) from fireplace side.

Figure 12.1 Gas Line Installation

46

Heatilator • I60, I80 • 4013-250 • Rev C • 11/08

Image 46 Contents
Hot screen/mesh and glass doors will cause burns Wood Burning FireplaceFire Risk Grate Listing Label Information/LocationNumber Installer Guide Table of ContentsUser Guide Warranty Hearth & Home Technologies Limited Warranty CONDITIONS, Exclusions & Limitation of LiabilityHeatilator I60, I80 4013-250 Rev C 11/08 Non-Combustible Materials Listing and Code ApprovalsAppliance Certification Combustible MaterialsYour Fireplace Operating InstructionsHot glass will cause burns Grate Seasoned WoodStarting a Fire FirescreenOptional Components Glass DoorsVented Gas Log Sets & Gas Log Lighters Clear SpaceWood Fuel Disposal of Ashes Maintainance and ServiceChimney Inspection/Cleaning Creosote Formation and Need for RemovalInspect Grate Glass CleaningCheck Firebox Refractory Frequency As desiredTroubleshooting Guide Start Fire Problems Possible Cause SolutionGetting Started Typical Fireplace SystemDraft Design and Installation ConsiderationsNegative Pressure Locating Fireplace & Chimney Frequently open doors Central heat outlets or returnsFireplace System Requirements Tools and Supplies NeededInspect Fireplace and Components Framing & Clearances Select Fireplace LocationClearances Clearances to Combustible MaterialsSidewalls/Surrounds Frame the FireplaceThings to Consider Installation of FireplaceUnpack the Fireplace I80 only Unpack the Fireplace I60 onlyPosition the Fireplace I80 only Removing Smoke ShieldInstall the Refractory I80 only GAS KnockoutPlace Protective Metal Hearth Strips Level FireplaceInstall Outside Air Kit YESChimney Assembly Chimney Requirements Height of Chimney ComponentsUsing Offsets/Returns ExampleInstall Chimney Air Kit Assemble Chimney SectionsInstall Ceiling Firestops Installing the Ceiling FirestopInstall Attic Insulation Shield 330 mmFollowing steps should be skipped if using a chase Complete InstallationInstall Flashing Cut out Hole in RoofChimney Termination Requirements Flat RoofsChase Installations Construct the ChaseInstall Fireplace & Chimney Install Chase TopInstall Termination Cap ST1175/ST475 Square Termination CapTCT1175 Terra Cotta Cap Field Constructed Shrouds ShroudsRadiation Shield Open Top Shroud TR11/TR11T caps require radiation shieldMailbox Style Shroud radiation shield required Roofed Style Shroud radiation shield requiredHearth Extension Finishing= 1/k x inches of thickness Raised Hearth Extension Framing Hearth Extension Construction Non-combustible Sealant Flush Hearth Extension FramingFinishing Material Noncombustible FacingCombustible Mantel 19 3/4 502 mm Wood Burning Inserts AccessoriesGas Log/Lighter Provision Gas Code, Ansi Z223.1Fireplace Dimensions Reference Materials13 mm Chimney Components Catalog #15-1/4 387 mm 15-3/4 400 mm CT56 Chase Top LDS33/LDS46 Decorative Shroud This page intentionally left blank Parts Icon I60CT, I60HParts Contact Information