Baxi Potterton Condensing Combination Boiler manual Annual Servicing Inspection

Page 37

 

13.0 Servicing

 

13 .1

Annual Servicing

Case Front Panel

1. For reasons of safety and economy, it is recommended that

 

the boiler is serviced annually. Servicing must be performed by

 

a competent person in accordance with B.S. 7967-4.

 

2. After servicing, complete the relevant Service Interval Record

 

section of the Benchmark Commissioning Checklist at the rear

 

of this publication.

IMPORTANT: During routine servicing, and after any maintenance or change of part of the combustion circuit, the following must be checked:-

• The integrity of the complete flue system and the flue seals.

• The integrity of the boiler combustion circuit and relevant seals as described in Section 13.2.

• The operational gas inlet pressure as described in Section 11.2.1 to 11.2.7 and the gas rate as described in 11.2.8.

• The combustion performance as described in ‘Check the Combustion Performance’ (13.1.4 to 13.1.6 below).

 

 

3. Competence to carry out Checking Combustion

Fig. 69

 

Performance

 

 

B.S. 6798 ‘Specification for Installation & Maintenance of Gas

 

 

Fired Boilers not exceeding 70kW’ advises that:-

 

Facia Panel Securing

The person carrying out a combustion measurement should

 

Screws

 

 

have been assessed as competent in the use of a flue gas

 

 

 

 

 

 

analyser and the interpretation of the results.

 

 

The flue gas analyser used should be one meeting the

 

 

 

requirements of BS7927 or BS-EN50379-3 and be calibrated

 

 

 

in accordance with the analyser manufacturers’ requirements.

 

 

Competence can be demonstrated by satisfactory

 

 

 

completion of the CPA1 ACS assessment, which covers the

 

 

 

use of electronic portable combustion gas analysers in

 

 

 

accordance with BS 7967, Parts 1 to 4.

 

 

Check the Combustion Performance (CO/CO2 ratio)

 

 

4. Set the boiler to operate at maximum rate as described in

 

 

Section 15.1.1 to 15.1.6.

 

 

5. Remove the plug from the flue sampling point, insert the

 

 

analyser probe and obtain the CO/CO2 ratio. This must be

 

 

less than 0.004.

 

 

6. If the combustion reading (CO/CO2 ratio) is greater than

 

 

this, and the integrity of the complete flue system and

 

 

combustion circuit seals has been verified, and the inlet gas

 

 

pressure and gas rate are satisfactory either:

 

 

• Perform the ‘Annual Servicing - Inspection’ (Section 13.2) &

 

 

 

re-check

 

 

• Adjust the gas valve (Section 15.0) & re-check

 

 

• Replace the gas valve (Section 14.23) & re-check

Inner Door

13.2

Annual Servicing - Inspection

Fig. 70

 

 

Panel

 

 

1.

Ensure that the boiler is cool.

 

 

2.

Ensure that both the gas and electrical supplies to the

 

boiler are isolated.

 

3.

Slacken the screws securing the facia panel. Lift the outercase

 

panel so that its securing tabs are clear of the facia. Remove the

 

panel, allowing the facia to hinge down (Fig. 69).

 

4.

Remove the screws securing the inner door panel. Lift the

 

panel slightly to disengage it from the studs on top of the case

 

(Fig. 70).

 

 

Sump

 

 

 

5.

Unscrew the sump from the bottom of the condensate trap

 

assembly (Fig. 71) and remove any deposits from the sump and

 

trap. Clean as necessary and replace the sump.

 

Fig. 71

 

 

© Baxi Heating UK Ltd 2012

 

37

Image 37
Contents Installation & Service Instructions 0086 Scheme Members only Installer Notification GuidelinesLegislation Important Installation, Commissioning, Service & RepairCodes of Practice refer to the most recent version General Safe Manual HandlingPreparation TechniqueContents Introduction Contents of PackDescription Optional ExtrasLayout General LayoutDomestic Hot Water Mode Fig Central Heating Mode FigFrost Protection Mode Appliance OperationHeatmax Combi 24, 28 Technical DataDimensions and Fixings Information System DetailsCentral Heating Circuit BypassSystem Filling and Pressurising Safety Pressure Relief Valve FigExpansion Vessel Central Heating only Showers Domestic Hot Water Circuit FigHard Water Areas Location Site RequirementsClearances Figs Ventilation of Compartments Site RequirementGas Supply Electrical SupplyCondensate Drain 500mm min 50mm perMinimum fall RunFlue Plume Displacement KitBelow windows or openings on pitched roofs 2000 Likely flue positions requiring a flue terminal guardHorizontal Flues Flue OptionsHorizontal Flue Systems This bend is equivalent to 1 metreVertical Flue Systems Vertical FluesRoof Terminal This bend is equivalent to 1 metre Metre for each 91.5 bend Metre for each 135 bendKey Accessory Size Code No Flue AccessoriesFor Roof Terminals Flue DimensionsFlue Trim Terminal Guard FigPlume Displacement Kit Fig Plume DisplacementDetermining Permissible Lengths 28/33Example 512136830mm General Fitting Notes60Ø extension piece. It must be secured using two Elbow to allow the flue to be installed as shownUsing a suitable bit e.g mm, drill through Extension and outlet. Secure using two of the screwsUnpacking & Initial Preparation InstallationFlushing After considering the site requirementsCondensate Drain see section Fitting The BoilerWall Thickness Flue Elbow Fitting The FlueEnsure Elbow is fully engaged into Boiler Adaptor WasteY Flue25mm Extension Cut End Inner Flue Support BracketEnsure Extension is fully engaged into Boiler Adaptor Preliminary Electrical Checks Making The Electrical ConnectionsTerminal Block Cover Cable Clamp Commissioning the Boiler CommissioningCheck the Operational Working Gas Inlet Pressure Selector Switch DisplayGas Valve Completion CompletionCase Front Panel Facia Panel Annual Servicing ServicingAnnual Servicing Inspection Electrode Leads Venturi Injector Fan, Collector and Cover Assembly Threaded BushRestricter Filter Hall Effect Sensor Igniter Fig Changing ComponentsSpark and Sensing Electrodes Fig Venturi Fig Fan FigInjector Fig Gasket Venturi Injector Cover Gas Inlet Pipe Fan CollectorInsulation Fig Burner FigSafety Thermostat Fig Central Heating Temperature Sensor NTC FigDHW Temperature Sensor NTC Fig Flue/Heat Exchanger Thermostat Sensor FigPump Complete Fig Pump Head Only FigAutomatic Air Vent Fig Hall Effect Sensor Fig Pressure Gauge FigsPlate Heat Exchanger Fig Diverter Valve Motor Unit & Assembly Fig14.22 P.C.B. Fig Selector Switch FigExpansion Vessel Fig Gas Valve FigSetting the Gas Valve CO2 check Setting the Gas ValveElectrical Illustrated Wiring DiagramShort Parts List Short Parts List306 302Initial Fault Finding Checks Fault FindingError Codes Go to section ‘A’ Turn the selector switch to Error 133 flashingReset position for 5 seconds Pump runsTurn Domestic Hot Water Error 133 flashing Go to section ‘I’Open DHW tap fully Close DHW tapSwitch terminal PCB X3 connector terminals 3Fan jammed or faulty winding Replace PCB Replace waterGas at burner Replace sensor or PCB E28Replace gas valve Terminals 1Replace PCB Is there 230V at Replace safety thermostatReplace sensor Page GAS Boiler System Commissioning Checklist Service Record Brooks House, Coventry Road, Warwick. CV34 4LL

Condensing Combination Boiler specifications

The Baxi Potterton Condensing Combination Boiler is a sophisticated heating solution designed to meet the demands of modern households while promoting energy efficiency. This state-of-the-art boiler combines both heating and hot water capabilities into a compact unit, making it an ideal choice for homes with limited space.

One of the standout features of the Baxi Potterton Condensing Combination Boiler is its impressive energy efficiency. With a high energy efficiency rating, these boilers can significantly reduce energy bills and minimize carbon footprints. The condensing technology maximizes heat recovery, allowing the boiler to utilize heat that would otherwise be lost in traditional systems. By extracting more energy from the combustion process, homeowners can enjoy reliable heating and hot water without the typical energy waste associated with older boilers.

The Baxi Potterton range is engineered for easy installation and maintenance, featuring a lightweight design that simplifies the fitting process. The built-in digital control system allows homeowners to easily adjust settings for optimal comfort and energy usage. Additionally, the boiler includes a frost protection feature, making it a reliable option for homes in colder climates.

Another key characteristic of the Baxi Potterton Condensing Combination Boiler is its powerful hot water delivery system. The combination boiler provides instant hot water on demand, eliminating the need for a separate water tank. This ensures that households have a constant supply of hot water for showers, cooking, and other domestic needs, without long wait times.

Safety is a top priority with the Baxi Potterton. The boiler is equipped with multiple safety features, including pressure relief valves and safety cut-off systems, ensuring peace of mind for homeowners. The compact design further includes a quiet operation feature, which is particularly beneficial for households where noise levels need to be kept to a minimum.

In summary, the Baxi Potterton Condensing Combination Boiler is a highly efficient, compact, and user-friendly solution for home heating and hot water needs. With its advanced technology and strong emphasis on safety, it stands out as a reliable choice for modern households looking to improve energy efficiency while maintaining comfort. Whether you are replacing an old boiler or installing a new system, the Baxi Potterton offers a perfect blend of practicality and innovation.