Baxi Potterton Condensing Combination Boiler manual Initial Fault Finding Checks, Error Codes

Page 51

NOTE: When instructed to turn the selector to the reset position turn the selector switch fully anticlockwise against the spring pressure to the reset position and hold for 5 seconds to reset the boiler.

Table Of Error Codes

E20 Central Heating NTC Fault

E28 Flue NTC Fault

E50 Hot Water NTC Fault

E110 Safety Thermostat Operated

E119 Water Pressure Switch Not Operated

E125 Circulation Fault (Primary Circuit)

E130 Flue NTC Operated

E133 Interruption Of Gas Supply or Flame Failure

E160 Fan or Fan Wiring Fault

E193 Pre-Circulation Fault

18.0Fault Finding

18.1Initial Fault Finding Checks

1.Check that gas, water and electrical supplies are available at the boiler.

2.Electrical supply = 230V ~ 50 Hz.

3.CH water system pressurised to 0.5 bar minimum when the boiler is cold.

4.The preferred minimum gas pressure is 20 mbar.

5.Carry out electrical system checks, i.e. Earth Continuity, Resistance to Earth, Short Circuit and Polarity with a suitable meter.

NOTE: These checks must be repeated after any servicing or fault finding.

6.Ensure all external controls are calling for heat and check all external and internal fuses. Before any servicing or replacement of parts, ensure the gas and electrical supplies are isolated.

18.2Error Codes

1.If a fault occurs on the boiler an error code may be shown by the facia display.

2.The codes are either two or three digit, preceded by the letter 'E'. For example, code E133 will be displayed by 'E1' alternating with '33'. E50 is shown as 'E' then '50'

E20, E28 & E50 indicate faulty or incorrect components.

E110 shows overheat of the primary water and E130 overheat of the flue system.

E119 is displayed when the primary water pressure is less than 0.5 bar.

E133 indicates that the gas supply has been interrupted, ignition has failed or the flame has not been detected.

E125 is displayed in either of two situations:-

i)If within 15 seconds of the burner lighting the boiler temperature has not changed by 1°.

ii)If within 10 minutes of the burner lighting the boiler temperature twice exceeds the selected temperature by 30°. In these instances poor primary circulation is indicated.

3.By turning the selector switch to the 'Reset' position for a minimum of 5 seconds when E110, E130 & E133 are displayed it is possible to relight the boiler.

4.If this does not have any effect, or the codes are displayed regularly further investigation is required.

© Baxi Heating UK Ltd 2012

51

Image 51
Contents Installation & Service Instructions 0086 Scheme Members only Installer Notification GuidelinesImportant Installation, Commissioning, Service & Repair LegislationCodes of Practice refer to the most recent version Technique Safe Manual HandlingGeneral PreparationContents Optional Extras Contents of PackIntroduction DescriptionLayout General LayoutAppliance Operation Central Heating Mode FigDomestic Hot Water Mode Fig Frost Protection ModeHeatmax Combi 24, 28 Technical DataDimensions and Fixings Bypass System DetailsInformation Central Heating CircuitSafety Pressure Relief Valve Fig System Filling and PressurisingExpansion Vessel Central Heating only Domestic Hot Water Circuit Fig ShowersHard Water Areas Site Requirements LocationClearances Figs Electrical Supply Site RequirementVentilation of Compartments Gas SupplyCondensate Drain 500mm min 50mm perMinimum fall RunLikely flue positions requiring a flue terminal guard Plume Displacement KitFlue Below windows or openings on pitched roofs 2000This bend is equivalent to 1 metre Flue OptionsHorizontal Flues Horizontal Flue SystemsMetre for each 91.5 bend Metre for each 135 bend Vertical FluesVertical Flue Systems Roof Terminal This bend is equivalent to 1 metreKey Accessory Size Code No Flue AccessoriesTerminal Guard Fig Flue DimensionsFor Roof Terminals Flue TrimPlume Displacement Kit Fig Plume Displacement5121368 28/33Determining Permissible Lengths Example30mm General Fitting NotesExtension and outlet. Secure using two of the screws Elbow to allow the flue to be installed as shown60Ø extension piece. It must be secured using two Using a suitable bit e.g mm, drill throughAfter considering the site requirements InstallationUnpacking & Initial Preparation FlushingCondensate Drain see section Fitting The BoilerWasteY Flue Fitting The FlueWall Thickness Flue Elbow Ensure Elbow is fully engaged into Boiler AdaptorInner Flue Support Bracket 25mm Extension Cut EndEnsure Extension is fully engaged into Boiler Adaptor Making The Electrical Connections Preliminary Electrical ChecksTerminal Block Cover Cable Clamp Commissioning the Boiler CommissioningSelector Switch Display Check the Operational Working Gas Inlet PressureGas Valve Completion CompletionCase Front Panel Facia Panel Servicing Annual ServicingAnnual Servicing Inspection Fan, Collector and Cover Assembly Threaded Bush Electrode Leads Venturi InjectorRestricter Filter Hall Effect Sensor Changing Components Igniter FigSpark and Sensing Electrodes Fig Gasket Venturi Injector Cover Gas Inlet Pipe Fan Collector Fan FigVenturi Fig Injector FigInsulation Fig Burner FigFlue/Heat Exchanger Thermostat Sensor Fig Central Heating Temperature Sensor NTC FigSafety Thermostat Fig DHW Temperature Sensor NTC FigPump Head Only Fig Pump Complete FigAutomatic Air Vent Fig Hall Effect Sensor Fig Pressure Gauge FigsPlate Heat Exchanger Fig Diverter Valve Motor Unit & Assembly Fig14.22 P.C.B. Fig Selector Switch FigExpansion Vessel Fig Gas Valve FigSetting the Gas Valve CO2 check Setting the Gas ValveElectrical Illustrated Wiring Diagram302 Short Parts ListShort Parts List 306Fault Finding Initial Fault Finding ChecksError Codes Pump runs Error 133 flashingGo to section ‘A’ Turn the selector switch to Reset position for 5 secondsClose DHW tap Error 133 flashing Go to section ‘I’Turn Domestic Hot Water Open DHW tap fullyReplace water PCB X3 connector terminals 3Switch terminal Fan jammed or faulty winding Replace PCBTerminals 1 Replace sensor or PCB E28Gas at burner Replace gas valveReplace safety thermostat Replace PCB Is there 230V atReplace sensor Page GAS Boiler System Commissioning Checklist Service Record Brooks House, Coventry Road, Warwick. CV34 4LL

Condensing Combination Boiler specifications

The Baxi Potterton Condensing Combination Boiler is a sophisticated heating solution designed to meet the demands of modern households while promoting energy efficiency. This state-of-the-art boiler combines both heating and hot water capabilities into a compact unit, making it an ideal choice for homes with limited space.

One of the standout features of the Baxi Potterton Condensing Combination Boiler is its impressive energy efficiency. With a high energy efficiency rating, these boilers can significantly reduce energy bills and minimize carbon footprints. The condensing technology maximizes heat recovery, allowing the boiler to utilize heat that would otherwise be lost in traditional systems. By extracting more energy from the combustion process, homeowners can enjoy reliable heating and hot water without the typical energy waste associated with older boilers.

The Baxi Potterton range is engineered for easy installation and maintenance, featuring a lightweight design that simplifies the fitting process. The built-in digital control system allows homeowners to easily adjust settings for optimal comfort and energy usage. Additionally, the boiler includes a frost protection feature, making it a reliable option for homes in colder climates.

Another key characteristic of the Baxi Potterton Condensing Combination Boiler is its powerful hot water delivery system. The combination boiler provides instant hot water on demand, eliminating the need for a separate water tank. This ensures that households have a constant supply of hot water for showers, cooking, and other domestic needs, without long wait times.

Safety is a top priority with the Baxi Potterton. The boiler is equipped with multiple safety features, including pressure relief valves and safety cut-off systems, ensuring peace of mind for homeowners. The compact design further includes a quiet operation feature, which is particularly beneficial for households where noise levels need to be kept to a minimum.

In summary, the Baxi Potterton Condensing Combination Boiler is a highly efficient, compact, and user-friendly solution for home heating and hot water needs. With its advanced technology and strong emphasis on safety, it stands out as a reliable choice for modern households looking to improve energy efficiency while maintaining comfort. Whether you are replacing an old boiler or installing a new system, the Baxi Potterton offers a perfect blend of practicality and innovation.