Trane VAV-SVX02B-EN manual Calibration, New Cross-over pressure

Page 5

Reversing Relay

Calibration

By using the “bias” adjustment on the relay, the factory-set 8.0–9.0 “cross- over” can be changed.To recalibrate, the relay should be connected as illustrated in Figure 8.

Pressure

Regulator

M

Figure 8–Recalibrating Reversing Relay

Gage

1

M C

3

Bias

Adjustment

Screw

If the new desired “cross-over” pressure is 11.0 psi, this must be applied to port #3 by adjusting the pressure regulator.The “bias” adjustment is then turned until 11.0 psi is obtained on the output gage.Turning the “bias” adjust- ment “CW” increases the output; “CCW” decreases it.

This 11.0 psi “cross-over” would yield the following operational chart:

New Cross-over pressure

Chart

Input:

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

Output:

20

19

18

17

16

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

Specifications

Maximum Pressure: 30 psig

Connections:

3/16" (4.& mm) nipples for ¼" (6.4 mm) OD polyethylene tubing

Air Consumption:

0.5 SCFH (.236 L/M) @ 20 psig

Material:

ABS

Weight: 3 ½ oz

Ambient Limits:

+40°F/+120°F operating (+4°C/+49°C)

Mounting:

In-line via air connections

Factory Settings:

9 psig in./9 psig out and 8 psig in./8 psig out

Bias Adjustment: +/-15 psi

VAV-SVX02B-EN

5

Image 5
Contents Installation Operation Maintenance Thermostat Piping ThermostatThermostat Selection and Location Operation SpecificationsOutput Pressure Input Temperature Reversing Relay Installation and OperationNew Cross-over pressure CalibrationInstallation Model 3011-Pneumatic Volume RegulatorConnections Selecting Direct- or Reverse-Acting ThermostatAdjust to obtain 0±0.1 psi at port G Adjusting the Reset SpanReverse-Acting Thermostat See for proper connections Calibration ProceduresNormally-OpenValve Normally-Open Valve Specifications SpecificationsSelecting Direct- or Reverse-Acting Thermostat Model 3501-Pneumatic Volume RegulatorReverse-Acting Thermostat Normally-Open Valve Normally-Closed Direct-Acting ThermostatOutput Sensitivity MCP-3631-Rotary Pneumatic Damper Actuator MCP-3631-Rotary Pneumatic Damper ActuatorConstantVolume Dual-Duct Calibration Constant-Volume Dual-Duct CalibrationVariable-Air-Volume Dual- Duct Calibration Variable Air Volume Dual-Duct CalibrationConstant-Volume Single- Duct VAV VCV Constant-Volume Single-Duct VAV VCV