Trane VAV-SVX02B-EN manual Model 3011-Pneumatic Volume Regulator, Installation, Connections

Page 6

Model 3011—Pneumatic Volume Regulator

Model 3011

The model 3011 PneumaticVolume Regulator (PVR) is capable of operating with normally-open or normally-closed air valves and can operate with either direct-acting (DA) or reverse-acting (RA) thermostats.

Installation

1.Attach bracket either vertically or horizontally to the illustration surface. Horizontal

is preferred, vertical is acceptable, any other position is not acceptable (see Figure 9).

2.Insert controller into its bracket. Controller may be face up, face down, face left, or face right.The controller LO and HI stat delta P must be calibrated in the same position that it is mounted.

Figure 9–Acceptable Installation Positions

Connections

Figure 10 illustrates a typical piping diagram of a normally-open or normally- closed unit.

Figure 10–Typical Piping Diagram of Normally-Open or Normally-Closed Unit

Normally-Open Unit or

 

 

 

 

Normally-Closed Unit

 

 

 

 

 

 

Volume

One-Pipe

LO

 

Remote-Installed

 

Regulator

 

 

T-Stat

 

 

 

 

 

 

 

 

Restrictor

 

 

 

 

Tee

HI

 

 

 

T

 

 

H

 

 

 

 

 

 

Actuator

B

 

LO STAT ΔP

 

 

 

 

 

 

NC

 

HI STAT ΔP

 

 

I

R

I N R

 

 

M

 

Restricted Leg

 

 

DAMPER

 

RESET SPAN

 

 

G

 

 

Airflow Sensor

 

S

 

S

 

 

 

 

 

20

 

20

Selecting Direct- or Reverse-Acting Thermostat (3011)

The model 3011 PVR must be calibrated to operate with either a direct-acting or reverse-acting thermostat.The control must also be changed when used with a normally-open or normally-closed air valve.

6

VAV-SVX02B-EN

Image 6
Contents Installation Operation Maintenance Thermostat Thermostat Selection and LocationThermostat Piping Specifications Output Pressure Input TemperatureOperation Installation and Operation Reversing RelayCalibration New Cross-over pressureConnections Model 3011-Pneumatic Volume RegulatorInstallation Selecting Direct- or Reverse-Acting ThermostatAdjusting the Reset Span Adjust to obtain 0±0.1 psi at port GCalibration Procedures Normally-OpenValve Normally-Open ValveReverse-Acting Thermostat See for proper connections Specifications SpecificationsModel 3501-Pneumatic Volume Regulator Selecting Direct- or Reverse-Acting ThermostatNormally-Open Valve Normally-Closed Direct-Acting Thermostat Reverse-Acting ThermostatOutput Sensitivity MCP-3631-Rotary Pneumatic Damper Actuator MCP-3631-Rotary Pneumatic Damper ActuatorConstant-Volume Dual-Duct Calibration ConstantVolume Dual-Duct CalibrationVariable Air Volume Dual-Duct Calibration Variable-Air-Volume Dual- Duct CalibrationConstant-Volume Single-Duct VAV VCV Constant-Volume Single- Duct VAV VCV