Model 3011—Pneumatic Volume Regulator
Model 3011
The model 3011 PneumaticVolume Regulator (PVR) is capable of operating with
Installation
1.Attach bracket either vertically or horizontally to the illustration surface. Horizontal
is preferred, vertical is acceptable, any other position is not acceptable (see Figure 9).
2.Insert controller into its bracket. Controller may be face up, face down, face left, or face right.The controller LO and HI stat delta P must be calibrated in the same position that it is mounted.
Figure 9–Acceptable Installation Positions
Connections
Figure 10 illustrates a typical piping diagram of a normally-open or normally- closed unit.
Figure 10–Typical Piping Diagram of Normally-Open or Normally-Closed Unit
|
|
|
| |
|
|
|
| |
|
| Volume | ||
LO |
| |||
| Regulator | |||
|
| |||
|
|
|
| |
|
|
|
| Restrictor |
|
|
|
| Tee |
HI |
|
|
| T |
|
| H |
| |
|
|
|
| |
| Actuator | B |
| LO STAT ΔP |
|
|
|
| |
|
| NC |
| HI STAT ΔP |
|
| I | R | I N R |
|
| M |
| Restricted Leg |
|
| DAMPER |
| RESET SPAN |
|
| G |
|
|
Airflow Sensor |
| S |
| S |
|
|
| ||
|
| 20 |
| 20 |
Selecting Direct- or Reverse-Acting Thermostat (3011)
The model 3011 PVR must be calibrated to operate with either a
6 |