Model 3011—Pneumatic

Volume Regulator

Use the following procedure to set-up the PVR:

1.Select damper action (NO or NC). Loosen damper selection switch screw and align to either the NO or NC pointer with damper pointer and tighten screw.

2.Now determine the type of thermostat that will be used. If a direct-acting thermostat is used, the reset start pressure is typically 8 psi. If a reverse-acting thermostat is used, the reset start pressure is typically 3 psi (see Figure 11).

3.With an accurate gage (0-10 psi) connected to port “G”, regulate the thermostat pressure to port “T” to desired start point pressure.

4.Adjust reset start to indicate 0 psi on port “G” and continuing adjusting to indicate a pressure slightly higher than 0 psi, (i.e., 0.1 psi).

Figure 11–Adjusting Reset Start

Adjust to obtain 0±0.1 psi at port G

B

 

 

 

CN

I

 

 

 

NO

N CR

 

 

 

 

 

psi

M

DAMPER

 

 

 

 

0

10

 

G

 

 

 

 

 

Connect 0±10 psi Gage

Factory-set at 5 psi

Adjustable (0±10 psi)

IN

Connect Hand Pump

Input desired LO stat pressure at t-stat port

0±20 psi

RESET START Handpump

LO STAT ΔP

HI STAT ΔP

CR

RESET SPAN

NOTE: The arrows on the damper selector must be aligned exactly or the range of the controller will be limited .0 psi

Adjusting the Reset Span (3011)

The reset span is factory-set at 5 psi.This is the thermostat pressure difference from which the PVR delivers flow from minimum to maximum setpoints.This range is not normally changed unless a special control scheme is used where control operation must be changed.

To field adjust a different reset span, follow these steps:

1.Connect an accurate gage to port “G”.

2.Apply 20 psi to port “T”.

3.Adjust reset span to indicate the desired span on port “G” (see Figure 12).

4.LO-stat and HI-stat delta P must now be readjusted (see following calibration procedure)

Figure 12– Adjusting Reset Span

H

B

NC

I C

NO

M

DAMPER

G

PSI

0 10

Apply 20 psi

T

RESET START

LO STAT P

HI STATP

I

R

RESET SPAN

Adjust to obtain desired reset span

VAV-SVX02B-EN

7

Image 7
Contents Installation Operation Maintenance Thermostat Selection and Location ThermostatThermostat Piping Output Pressure Input Temperature SpecificationsOperation Reversing Relay Installation and OperationNew Cross-over pressure CalibrationSelecting Direct- or Reverse-Acting Thermostat Model 3011-Pneumatic Volume RegulatorInstallation ConnectionsAdjust to obtain 0±0.1 psi at port G Adjusting the Reset SpanNormally-OpenValve Normally-Open Valve Calibration ProceduresReverse-Acting Thermostat See for proper connections Specifications SpecificationsSelecting Direct- or Reverse-Acting Thermostat Model 3501-Pneumatic Volume RegulatorReverse-Acting Thermostat Normally-Open Valve Normally-Closed Direct-Acting ThermostatOutput Sensitivity MCP-3631-Rotary Pneumatic Damper Actuator MCP-3631-Rotary Pneumatic Damper ActuatorConstantVolume Dual-Duct Calibration Constant-Volume Dual-Duct CalibrationVariable-Air-Volume Dual- Duct Calibration Variable Air Volume Dual-Duct CalibrationConstant-Volume Single- Duct VAV VCV Constant-Volume Single-Duct VAV VCV