Thermostat Selection and Location

In general, both one- and two-pipe thermostats have a gain of 2.5 psi per degree Fahrenheit, unless special thermostats are used that provide a different gain. The major difference between them is that a one-pipe thermostat is considered a low- capacity thermostat and a two-pipe thermostat is considered a high- capacity thermostat.

When selecting between one-pipe and two-pipe thermostats consider the following:

Use one-pipe thermostat when:

￿tubing runs are less than 50 feet from thermostat to controller.

￿a single thermostat will control no more than three controllers.

￿slower response is desired from the thermostat.

Use two-pipe thermostat when:

￿tubing runs exceed 50 feet from thermostat to controller.

￿a single thermostat will control four or more controllers.

￿high capacity air is required due to restrictions in the air line.

Thermostat Piping

The two-pipe thermostat (Figure 1) includes a restrictor (internally). Attach supply air line and output pressure (branch) line to the thermostat.

The one-pipe thermostat (Figure 2) requires an external restrictor tee. Connect main air supply to restricted leg of restrictor tee. Connect branch line from restrictor tee to the thermostat.

Figure 1–Two-Pipe Remote Thermostat (Reverse-Acting)

Tee

Two-Pipe

Remote-Mounted

T-Stat

(Reverse-Acting)

S

520

1

 

)

.9)

 

.4

3

 

0

 

(137

(1

 

Figure 2–Typical One-PipeThermostat (Reverse-Acting)

 

 

 

 

 

 

Restrictor

 

One-Pipe

 

 

Tee

Tee

 

 

 

 

Remote-Mounted

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T-Stat

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Reverse-Acting)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S

 

Restricted Leg

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20

 

 

 

 

Fan

(137.9)

 

 

 

 

P.E.

 

 

 

 

Switch±1

 

 

 

 

 

(N.O.)

 

 

 

 

 

 

 

 

 

 

 

 

9PSI

(62.06 kPa)

2

VAV-SVX02B-EN

Image 2
Contents Installation Operation Maintenance Thermostat Piping ThermostatThermostat Selection and Location Operation SpecificationsOutput Pressure Input Temperature Installation and Operation Reversing RelayCalibration New Cross-over pressureConnections Model 3011-Pneumatic Volume RegulatorInstallation Selecting Direct- or Reverse-Acting ThermostatAdjusting the Reset Span Adjust to obtain 0±0.1 psi at port GReverse-Acting Thermostat See for proper connections Calibration ProceduresNormally-OpenValve Normally-Open Valve Specifications SpecificationsModel 3501-Pneumatic Volume Regulator Selecting Direct- or Reverse-Acting ThermostatNormally-Open Valve Normally-Closed Direct-Acting Thermostat Reverse-Acting ThermostatOutput Sensitivity MCP-3631-Rotary Pneumatic Damper Actuator MCP-3631-Rotary Pneumatic Damper ActuatorConstant-Volume Dual-Duct Calibration ConstantVolume Dual-Duct CalibrationVariable Air Volume Dual-Duct Calibration Variable-Air-Volume Dual- Duct CalibrationConstant-Volume Single-Duct VAV VCV Constant-Volume Single- Duct VAV VCV