Trane VAV-SVX02B-EN manual Specifications, Operation, Output Pressure Input Temperature

Page 3

Thermostat

Specifications

TP970 Series PneumaticT-stats

Maximum Safe Air Pressure:

25psi (172 kPa)

Maximum Safe AirTemperature: 150°F (66°C)

Throttling Range: 2–10°F(1–5°C)

Gain:

2.5 psi/°F Adjustable

Operation

Pneumatic thermostats modulate output air pressure in response to room air temperature. Pneumatic thermo- stats fall into two categories: direct- acting or reverse-acting.This section describes how thermostat output pressure responds to changes in room temperature.

Figure 3 graphically illustrates the relationship between room temperature and output pressure of a direct-acting thermostat.The graph in Figure 3 shows that as the room temperature increases, so does the output pressure of the thermostat.

Figure 3–Direct-Acting

Thermostat Response

Output Pressure

Input Temperature

Figure 4 illustrates the pressure/ temperature characteristics for a reverse-acting thermostat. As room temperature increases, the thermostat output pressure decreases.

Figure 4–Reverse-Acting

Thermostat Response

Output Pressure

Input Temperature

A thermostat in proper working order will be able to output a pressure ranging from approximately .5 psi to supply air pressure depending on distance from indicated setpoint.

VAV-SVX02B-EN

3

Image 3
Contents Installation Operation Maintenance Thermostat Thermostat Selection and LocationThermostat Piping Specifications Output Pressure Input TemperatureOperation Reversing Relay Installation and OperationNew Cross-over pressure CalibrationSelecting Direct- or Reverse-Acting Thermostat Model 3011-Pneumatic Volume RegulatorInstallation ConnectionsAdjust to obtain 0±0.1 psi at port G Adjusting the Reset SpanCalibration Procedures Normally-OpenValve Normally-Open ValveReverse-Acting Thermostat See for proper connections Specifications SpecificationsSelecting Direct- or Reverse-Acting Thermostat Model 3501-Pneumatic Volume RegulatorReverse-Acting Thermostat Normally-Open Valve Normally-Closed Direct-Acting ThermostatOutput Sensitivity MCP-3631-Rotary Pneumatic Damper Actuator MCP-3631-Rotary Pneumatic Damper ActuatorConstantVolume Dual-Duct Calibration Constant-Volume Dual-Duct CalibrationVariable-Air-Volume Dual- Duct Calibration Variable Air Volume Dual-Duct CalibrationConstant-Volume Single- Duct VAV VCV Constant-Volume Single-Duct VAV VCV