Emerson 1HDEZ-1521 installation instructions Installation Test, Check System Operation

Page 20

Advanced Installer Menu

Installation Test

Performs an equipment test to verify proper installation and performance.

Only operable on communicating systems with ClimateTalk™.

ADVANCED INSTALLER MENU

Check System Operation

Heating System

1.Press SYSTEM button until Heat is displayed.

2.Pressto adjust thermostat setting above room temperature.The heating system should begin to operate and the display will indicate Heat On.

3.If the heating system has additional stages, adjust the thermostat setting to F (C) or more above the actual temperature. The next heat stage will energize.

4.Pressto adjust thermostat setting below room temperature. The heating system should stop operating.

Cooling System

1.Press SYSTEM button until COOL is displayed.

2.Pressto adjust thermostat setting below room temperature. The cooling system should begin to operate and the display will indicate Cool On.

3.If the cooling system has additional stages, adjust the temperature to F

(C) or more below the actual. The second cool stage will energize within

10 seconds.

4.Pressto adjust thermostat setting above room temperature. The cooling system should stop operating.

Fan Operation

1.Press FAN button until Fan On is displayed. The fan should begin to operate.

2.Press FAN button to change the display to Fan Auto. The fan should stop operating as long as there is no call for heat or cool.

20

Image 20
Contents Emerson Inspire Index Applications and Specifications Configuration Applications Maximum Options StagesInstallation Equipment Control Equipment Control Terminals Operation / Function HM2Wiring to Typical Connection of a Single Stage or Multi-Stage System Wiring Guide for Equipment Accessories Fan Thermostat Power System Thermostat and Equipment Control WiringAdvanced Installer Menu Items on the Advanced Installer Menu areEquipment Control Communicating DevicesCommunicating Devices Rev Valve IndoorOutdoor HUM USB Upload Faults StatusFound. Installation Failed Dual Fuel Setpoint outdoor sensor required Thermostat SummaryHeat Pump Lockout outdoor sensor required Aux Lockout Temperature outdoor sensor required Humidity Display AdjustHeat Cycle Rate Cool Cycle RateInstallation Test Check System OperationClock and Display Settings Display SettingsMain Menu Navigating through your thermostat menusHeating Program Time and Day DisplayOutdoor Temp Display Humidity DisplayFactory Pre-Programmed Heating and Cooling Schedule Thermostat SettingsCooling Program Main Menu Main Menu Main Menu Main Menu Troubleshooting Reset OperationSymptom Possible Cause Correction Action No Cool Temperature Display AdjustTemperature Heat, Cool or FanSystem Communication Codes Equipment Control Fault CodesNumber Displayed 7 Segment LED Page Part no -7343B