Rev. A.1, 10/99 | Page- 24 |
keyswitch is in the NO position. Be sure that the keyswitch contacts are of adequate capacity to switch all the power of the panel.
FIG. 13: FIELD INSTALLATION OF BYPASS KEYSWITCH (FAIL SAFE LOCKS)
ALTERNATE ACTION
SPDT KEYSWITCH
NO
+V POWER | C |
NC
TO DC NEG
INDICATOR
PANEL BOARD | PANEL BOARD |
OPEN PAD | OPEN PAD |
E4 L4 | L1 S1 | E4 L4 | L1 S1 |
THIS CONNECTION REQUIRES SOLDERING. IDENTIFY THE 2 OPEN PADS ON EACH BOARD NEXT TO
THE TERMINALS AS SHOWN. PADS ARE INTERCONNECTED ON ALL BOARDS TO THE KEYSWITCH N.O. TERMINAL AS SHOWN.
NEXT BOARD ETC
Note that when a bypass keyswitch is used together with an emergency release pushbutton (option “PB”), the push button is bypassed at the same time the toggles are. This is done by using a two pole keyswitch. One pole operates as is shown in Figure 13 above. The second pole bypasses the PB contacts which break the negative DC input to the panel. This is to maintain the security of the locks regardless of what is done to the panel controls until the keyswitch is again returned to the “normal” position.
5.5 SWITCH BYPASS WIRING (OPTIONS "KP2" OR "MK2" FAIL SECURE LOCKS)
The option comes
14.The keyswitch removes power from all the terminal boards. This bypasses the ability of the toggles to release the locks. The panel's monitoring capability will also be disabled but the purpose of the keyswitch is to shut down the panel when the operator is absent so this is not an issue. Note that the keyswitch indicator (which operates on the same voltage) indicates that the panel is operating normally. Be sure that any field installed keyswitch has contacts of sufficient capacity to break all of the panel power. Also, make sure you terminate the lock negative wires to the panel
The reason that this option is set up to break the negative circuit instead of the positive is to preserve the ability to run separate +V inputs to each board zone. This can allow separately breakered inputs from a Securitron power supply or the installation of upstream switches.
If the installation includes remote release switches, an important change must be made from the lock wiring in Figure 4. Assuming that you wish the remote release switch to continue to function when the panel is bypassed, it will not if the job is wired as is shown in type 3 or type 4 hookups in Figure 4. The reason is that keyswitch bypass will remove DC negative from the panel and hence from the return of the fail secure locks. The solution is to run an extra DC negative wire from the power supply to the remote switch common. The wire is upstream of