Part 2 Functions & Controls

5.8 Overheating Protection (Power Module)

5.8.1 9,12kBtu/h Model

If the temperature of the heat sink thermistor. reaches over Toff, the Compressor stop instantly.

The compressor operating frequency is limited according to the heat sink thermistor. (refer to below FIG.)

It will blink 4 times, when the thermistor is open or short, also when the temperature is over T off.

 

T = (T off - T on)/3

 

 

Heat Sink Temp.

 

T1 = T on + T

 

 

 

 

 

 

 

T off °C

T2 = T on + 2 * T

 

 

 

 

 

 

 

 

 

 

 

T2 °C

 

 

 

 

 

 

 

T1 °C

 

 

 

 

 

 

 

T on °C

 

 

 

 

 

 

 

COMP

Free

Fc-1

Fc-2

Fc-1

Fc-2

OFF

Free

Freq.

 

 

 

 

 

 

 

T on : 85°C(185°F) (Model by Model)

T off : 95°C(203°F) (Model by Model)

NOTE: Some Models are different by Ton, and Toff.

Service Manual 21

Image 21
Contents SVC MANUALGeneral Contents Part 1 General Information Safety Precautions NomenclatureBe sure not to do Be sure to follow the instruction Safety PrecautionsPart 1 General Information Inspections after Repair Nomenclature Global Model NameCode Type Code of Model Meaning Part 2 Functions & Controls Function Description Part 2 Functions & ControlsBasic Mode Controls Cooling ModeHeating Mode Healthy Dehumidification operation Intake air Temp Setting TempAutomatic operation Auto changeover operationEnergy saving operation in cooling mode Special Mode ControlsJet Cool operation Jet Heat operationIndoor temp Operating Mode Setting temp Auto cleaning operationUtility Functions Forced operationAir volume control Natural Air ControlAuto WindChaos Swing Sleep timer operation for cooling cycle Sleep mode Auto controlSleep timer operation for heating cycle Auto restartFive Seconds Stand-by fan Protection Functions & ControlsTwo Minutes Stand-by comp Hot start1 9,12kBtu/h Model Automatic defrost 2 18,24,30kBtu/h Model Starting to the defrosting operationControl algorithm of defrost completion Defrosting Control AlgorithmInverter Power Relay ControlOverheating Protection Power Module Heat sink sensor failure error Heat sink temperature controlFunction Total Current Control Over Current Protection CT1 controlCT2 control Model Cooling Heating KBtu/h 18~30 11A 12A 14A Discharge Pipe Temp Control DC Peak controlInverter Compressor 18,24,30kBtu/h Model Constant Compressor only 30kBtu/h Model There can be two situationsCompressor working Low Ambient control 12.1 9,12kBtu/h Model12.2 18, 24, 30kBtu/h Model Oil equalizing control30kBtu/h Model Oil return control30kBtu/h ModelOperating Contion Operation ProcessPart 3 Test Run Check before Test Run Test Run Flow chart Test Run DetailCheck before Test Run Start Test Run Flow chartTest Run Detail Pump Down ProcedureSettlement of outdoor unit Evaluation of the performancePart 4 Trouble Shooting Way Valve Liquid Side Way, 3-Way ValvePumping Down ProcedureAir purging of the charge hose Set the 2-way valve to the closed positionEvacuation All amount of refrigerant leaked Gas Charging After Evacuation Mount the valve stem nuts and the service port nutConnect the charge hose to the charging cylinder Purge the air from the charge hoseTrouble analysis Cycle Troubleshooting GuidePart 4 Trouble Shooting Procedure Specification Remedy Electronic Parts Troubleshooting GuideTrouble Compressor/Outdoor Fan dont operate 9~30kBtu/h Model Compressor/Outdoor Fan dont operate 18, 24, 30kBtu/h Model When indoor Fan does not operate.9~30kBtu/h Model Error Indicator Self-diagnosis Function12kBtu/h Model Outdoor Error 18,24,30kBtu/h Model Indoor ErrorError code Descrition Red Green StatusPart Trouble Shooting Troubleshooting Guide9,12kBtu/h Model Description Cause of error Heat-sink Temp. is over Earth port DC Peak Error Description Cause of error Over current Error Description Cause of error Indoor fan is locked Description Cause of error Pipe TH. is short or Check Point Troubleshooting CH01, CH02, CH06Troubleshooting CH05, CH53 Part 4 Trouble ShootingTroubleshooting CH21 CompCopper Comp pipe Troubleshooting CH21, CH22 Troubleshooting CH23, CH28 Troubleshooting CH24, CH25 Troubleshooting CH26, CH27 Troubleshooting CH32, CH33, CH40 Troubleshooting CH41, CH44, CH45, CH46, CH47, CH65 Troubleshooting CH51, CH60 Troubleshooting CH61, CH62 No MFL41161601 August