Part 4 Trouble Shooting

18,24,30kBtu/h Model Indoor Error

Error code

Descrition

INV TPS

LED1

LED2

Indoor

(Red)

(Green)

Status

 

 

 

 

 

 

 

 

 

00

No Error

 

 

 

ON

 

 

 

 

 

 

01

Indoor Room themistor error

 

 

1time

OFF

 

 

 

 

 

 

02

Indoor in-piping sensor error

 

 

2times

OFF

 

 

 

 

 

 

03

Remote controler error

 

 

3times

OFF

 

 

 

 

 

 

04

Drain Pump error

 

 

4times

OFF

 

 

 

 

 

 

05

Communcation error between in and out

 

 

5times

OFF

 

 

 

 

 

 

06

Indoor Out-Piping sensor error

 

 

6times

OFF

 

 

 

 

 

 

07

Diffrent mode operation

 

 

times

OFF

 

 

 

 

 

 

Outdoor Error

Ex) Error Code 21 (IPM Fault)

2 Times2 Times2 Times

LED01G

(RED)

1 Sec.

1 Sec.

1 Sec.

1 Time

1 Time

1 Time

LED02G

(GREEN)

2 Sec.

2 Sec.

Error

Contents

LED01G

LED02G

Case of error

Outdoor

code

(Red)

(Green)

Status

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

21

IPM Fault (Compressor Over current)

2 times

1 time

Compressor malfunction,IPM Fault

Off

 

 

 

 

 

 

 

 

 

 

22

CT 2(Max. Current)

2 times

2 times

Current is 14A

 

 

 

 

Off

 

 

 

 

 

 

 

 

 

 

 

23

DC Link Low Volt.

2 times

3 times

DC Link volt. Is 140V

 

 

Off

 

 

 

 

 

 

 

 

 

 

 

 

24

Low / High press

2 times

4 times

Low / High press switch OPEN

Off

 

 

 

 

 

 

 

 

 

 

25

AC Low / AC High Volt.

2 times

5 times

Abnormal AC volt. Input.

Off

 

 

 

 

 

 

 

 

 

 

26

DC Compressor Position

2 times

6 times

 

 

 

 

 

Off

 

 

 

 

 

 

 

 

 

 

27

PSC Fault

2 times

7 times

 

 

 

 

 

Off

 

 

 

 

 

 

 

 

 

 

28

DC Link High Volt

2 times

8 times

Off

Off

 

 

 

 

 

 

 

 

 

 

32

Discharge Pipe Temp. High (INV)

3 times

2 times

Off

Off

 

 

 

 

 

 

 

 

 

 

33

Discharge Pipe Temp. High (Cons.)

3 times

3 times

Off

Off

 

 

 

 

 

 

 

 

 

 

Service Manual 47

Image 47
Contents SVC MANUALGeneral Contents Part 1 General Information Safety Precautions NomenclatureBe sure not to do Be sure to follow the instruction Safety PrecautionsPart 1 General Information Inspections after Repair Code Type Code of Model Meaning NomenclatureGlobal Model Name Part 2 Functions & Controls Function Description Part 2 Functions & ControlsHeating Mode Basic Mode ControlsCooling Mode Auto changeover operation Intake air Temp Setting TempHealthy Dehumidification operation Automatic operationJet Heat operation Special Mode ControlsEnergy saving operation in cooling mode Jet Cool operationForced operation Auto cleaning operationIndoor temp Operating Mode Setting temp Utility FunctionsChaos Swing Air volume controlNatural Air ControlAuto Wind Auto restart Sleep mode Auto controlSleep timer operation for cooling cycle Sleep timer operation for heating cycleHot start Protection Functions & ControlsFive Seconds Stand-by fan Two Minutes Stand-by comp1 9,12kBtu/h Model Automatic defrost2 18,24,30kBtu/h Model Starting to the defrosting operationControl algorithm of defrost completion Defrosting Control AlgorithmInverter Power Relay ControlOverheating Protection Power Module Function Heat sink sensor failure errorHeat sink temperature control CT2 control Total Current Control Over Current ProtectionCT1 control Model Cooling Heating KBtu/h 18~30 11A 12A 14A Discharge Pipe Temp Control DC Peak controlInverter Compressor 18,24,30kBtu/h Model Compressor working Constant Compressor only 30kBtu/h ModelThere can be two situations 12.2 18, 24, 30kBtu/h Model Low Ambient control12.1 9,12kBtu/h Model Operation Process Oil return control30kBtu/h ModelOil equalizing control30kBtu/h Model Operating ContionPart 3 Test Run Check before Test Run Test Run Flow chart Test Run DetailCheck before Test Run Start Test Run Flow chartEvaluation of the performance Pump Down ProcedureTest Run Detail Settlement of outdoor unitPart 4 Trouble Shooting Way Valve Liquid Side Way, 3-Way ValveSet the 2-way valve to the closed position ProcedurePumping Down Air purging of the charge hoseEvacuation All amount of refrigerant leaked Purge the air from the charge hose Mount the valve stem nuts and the service port nutGas Charging After Evacuation Connect the charge hose to the charging cylinderTrouble analysis Cycle Troubleshooting GuidePart 4 Trouble Shooting Procedure Specification Remedy Electronic Parts Troubleshooting GuideTrouble Compressor/Outdoor Fan dont operate 9~30kBtu/h Model Compressor/Outdoor Fan dont operate 18, 24, 30kBtu/h Model When indoor Fan does not operate.9~30kBtu/h Model 12kBtu/h Model Error IndicatorSelf-diagnosis Function Red Green Status 18,24,30kBtu/h Model Indoor ErrorOutdoor Error Error code DescritionPart Trouble Shooting Troubleshooting Guide9,12kBtu/h Model Description Cause of error Heat-sink Temp. is over Earth port DC Peak Error Description Cause of error Over current Error Description Cause of error Indoor fan is locked Description Cause of error Pipe TH. is short or Check Point Troubleshooting CH01, CH02, CH06Troubleshooting CH05, CH53 Part 4 Trouble ShootingCopper Comp pipe Troubleshooting CH21Comp Troubleshooting CH21, CH22 Troubleshooting CH23, CH28 Troubleshooting CH24, CH25 Troubleshooting CH26, CH27 Troubleshooting CH32, CH33, CH40 Troubleshooting CH41, CH44, CH45, CH46, CH47, CH65 Troubleshooting CH51, CH60 Troubleshooting CH61, CH62 No MFL41161601 August