LG Electronics General Wall Mounted-Inverter Type manual Part 4 Trouble Shooting

Page 57

 

 

 

Part 4 Trouble Shooting

2) Troubleshooting CH05, CH53

 

 

 

 

 

Error

Title

Cause of error

Check point & Normal condition

code

 

 

 

 

 

 

 

 

 

 

• Power input AC 208~230V. (Outdoor, Indoor)

05

 

 

• The connector for transmission is disconnected.

Communication

 

• The connecting wires are misconnected.

/

• Communication poorly

• The GND1,2 is not connected at main GND.

53

(Indoor Outdoor)

 

• The communication line is shorted at GND.

 

 

 

 

 

• Transmission circuit of outdoor PCB is abnormal.

 

 

 

• Transmission circuit of indoor PCB is abnormal.

 

 

 

 

Check Point

1. Check the input power AC 208~230V. (Outdoor, Indoor unit)

2.Check the communication wires are correctly connected.

Adjust the connection of wire

Confirm the wire of “Live”, “Neutral”

3. Check the resistance between communication line and GND. (Normal : Over 2M)

4. Check the connector for communication is correctly connected.

5. Check the connection of GND1, GND2, and main GND.

6. If one indoor unit is operated normally, outdoor PCB is no problem.

Check the another indoor unit.

* CH05 is displayed at indoor unit, CH53 is displayed at out- door unit.

Service Manual 57

Image 57
Contents SVC MANUALGeneral Contents Part 1 General Information Safety Precautions NomenclatureBe sure not to do Be sure to follow the instruction Safety PrecautionsPart 1 General Information Inspections after Repair Nomenclature Global Model NameCode Type Code of Model Meaning Part 2 Functions & Controls Function Description Part 2 Functions & ControlsBasic Mode Controls Cooling ModeHeating Mode Healthy Dehumidification operation Intake air Temp Setting TempAutomatic operation Auto changeover operationEnergy saving operation in cooling mode Special Mode ControlsJet Cool operation Jet Heat operationIndoor temp Operating Mode Setting temp Auto cleaning operationUtility Functions Forced operationAir volume control Natural Air ControlAuto WindChaos Swing Sleep timer operation for cooling cycle Sleep mode Auto controlSleep timer operation for heating cycle Auto restartFive Seconds Stand-by fan Protection Functions & ControlsTwo Minutes Stand-by comp Hot start1 9,12kBtu/h Model Automatic defrost2 18,24,30kBtu/h Model Starting to the defrosting operationControl algorithm of defrost completion Defrosting Control AlgorithmInverter Power Relay ControlOverheating Protection Power Module Heat sink sensor failure error Heat sink temperature controlFunction Total Current Control Over Current Protection CT1 controlCT2 control Model Cooling Heating KBtu/h 18~30 11A 12A 14A Discharge Pipe Temp Control DC Peak controlInverter Compressor 18,24,30kBtu/h Model Constant Compressor only 30kBtu/h Model There can be two situationsCompressor working Low Ambient control 12.1 9,12kBtu/h Model12.2 18, 24, 30kBtu/h Model Oil equalizing control30kBtu/h Model Oil return control30kBtu/h ModelOperating Contion Operation ProcessPart 3 Test Run Check before Test Run Test Run Flow chart Test Run DetailCheck before Test Run Start Test Run Flow chartTest Run Detail Pump Down ProcedureSettlement of outdoor unit Evaluation of the performancePart 4 Trouble Shooting Way Valve Liquid Side Way, 3-Way ValvePumping Down ProcedureAir purging of the charge hose Set the 2-way valve to the closed positionEvacuation All amount of refrigerant leaked Gas Charging After Evacuation Mount the valve stem nuts and the service port nutConnect the charge hose to the charging cylinder Purge the air from the charge hoseTrouble analysis Cycle Troubleshooting GuidePart 4 Trouble Shooting Procedure Specification Remedy Electronic Parts Troubleshooting GuideTrouble Compressor/Outdoor Fan dont operate 9~30kBtu/h Model Compressor/Outdoor Fan dont operate 18, 24, 30kBtu/h Model When indoor Fan does not operate.9~30kBtu/h Model Error Indicator Self-diagnosis Function12kBtu/h Model Outdoor Error 18,24,30kBtu/h Model Indoor ErrorError code Descrition Red Green StatusPart Trouble Shooting Troubleshooting Guide9,12kBtu/h Model Description Cause of error Heat-sink Temp. is over Earth port DC Peak Error Description Cause of error Over current Error Description Cause of error Indoor fan is locked Description Cause of error Pipe TH. is short or Check Point Troubleshooting CH01, CH02, CH06Troubleshooting CH05, CH53 Part 4 Trouble ShootingTroubleshooting CH21 CompCopper Comp pipe Troubleshooting CH21, CH22 Troubleshooting CH23, CH28 Troubleshooting CH24, CH25 Troubleshooting CH26, CH27 Troubleshooting CH32, CH33, CH40 Troubleshooting CH41, CH44, CH45, CH46, CH47, CH65 Troubleshooting CH51, CH60 Troubleshooting CH61, CH62 No MFL41161601 August