LG Electronics AS-W096URH0/UBH0/UWH0/UMH0 service manual Protection from total current control

Page 43

Operation

Protection from totalcurrentcontrol

CT1 control

If the operating current reaches I1, the operating frequency of the compressor decrease.

After decreasing the operating frequency by 1step, if operating current is below I1 for 60 seconds continuous- ly, the operating frequency of compressor increase by 1step.

CT2 control

If the operating current of the appliance reaches I2, the compressor stop instantly and 2 minutes later the compressor restart again.

If CT2 occurs 5 times within 1hour, the appliance turn off and display ERROR CODE 7.

 

Control table

I1:Current of operating frequency down

 

 

 

 

 

 

I2: Current of compressor cut off

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

I1

 

 

 

I2

 

 

Model

Outdoor temp 38°C

 

Outdoor temp < 38°C

 

 

 

 

 

Cooling

Heating

 

Cooling

Heating

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

AS-W096U_0 Series

6.5

8.5

 

7

9

12

 

 

 

 

 

 

 

 

 

 

2

AS-W126U_0 Series

6.5

7.5

 

7

8

10

 

 

 

 

 

 

 

 

 

 

3

AS-W096U_1 Series

5.5

7

 

6

7.5

9

 

 

 

 

 

 

 

 

 

 

4

AS-W126U_1 Series

6

7.5

 

6.5

8

10

 

 

 

 

 

 

 

 

 

 

 

 

cf. I1 is set the lowest level between intial value and in case dectection of dc paeak current.

Protection from DCPeak Current

DC Peak Current Error by a fault signal of IPM

If the operating current of IPM reaches 35A ±3A, the compressor stop instantly.

If DC PEAK occurs 5 times within 1 hour, the appliance turns off and display ERROR CODE 6.

DC Peak Current Error by the compressor lock

If the DC LINK voltage below DC 140V occurs 5 times within 1 hour while the compressor is operating, the appliance turns off and display ERROR CODE 6.

DC Peak Current Error by the Outdoor Fan Lock

If it’s 5 times within 1 hour in case of the temperature of outdoor pipe TH is over 65°C while the compressor is operating, the appliance turns off and display ERROR CODE 6.

Service Manual 43

Image 43
Contents LG Room Air Conditioner Table of Contents 2002 LG Model NameCode Type Code of Model Meaning Meaning 2003~2005Installation Safety PrecautionsThere is risk of fire, electric shock, explosion, or injury Thinner OperationBe cautious that water could not enter the product Keep level even when installing the productOperation 9k, 12k Btu Series DimensionsSymbols Used in this Manual Indoor UnitOutdoor Unit AS-W096U0 AS-W126U0 AS-W096U1 AS-W126U1 Product SpecificationsOutdoor unit InstallationSelect the best Location Indoor unitOil trap should be installed every 5~7 meters Fixing Installation PlatePiping Length and Elevation Flaring Work Drill a Hole in the WallFoamed polyethylene or equivalent is recom- mended Connecting the PipingCheck IndoorWrap the insulation material around the connecting portion For left rear piping Indoor unit installation Bad case For left piping. Follow the instruction below Good caseOutdoor unit OutdoorConnecting the Cables Circuit Grade Breaker To check the drainage Checking the DrainageDrain piping Forming the Piping Air purging Air PurgingAir purging with vacuum pump Evacuation Soap water methodFinishing the job Evaluation of the performance Prepare remote controllerTest Running Settlement of outdoor unitPump Down Pump Down ProcedureFunctions Stand by control at low temp Power relay controlActive power filter controlPSC Overheatng. ProtectionPower moduleCooling Down to 18C Heating Down to 16C Up to 30C Cancel Sleep Mode, Timer on or Timer OFF3, 4, 5, 6 Off Timer High39C Low11CLED display of indoor unit OperationLG Brand/OEM Brand Control method Protection of the evaporator pipe from frostingModel Comp. Operating frequency Cooling mode operationIntake air Temp Setting Temp Healthy Dehumidification mode operationOperating freq. step of comp Heating mode operationTemp. differences Comp. Operating frequency At beginning Fuzzy mode operationOptionalsIntake air temp Setting temp Fan speed Fuzzy operation for coolingFuzzy operation for dehumidification Fuzzy operation for HeatingChaos swing mode Jet cool mode operationJet heat mode operation Swing modeSleep timer operation for cooling cycle Sleep timer operationSleep timer operation for heating cycle Trial Operation Indoor temp Operating Mode Setting tempAuto restarting operation Forced operationProtection from DC Peak Current Protection from total current controlPortection from overheating of compressor Portection from overheating of power moduleAS-W096/126U0 Series Defrosting controlAS-W096/126U1 Series Auto ChangeoverOptional Auto CleaningLow Ambient To remove the Grille from the Chassis DisassemblyTo remove the Discharge Grille To remove the Control BoxTo remove the Evaporator To remove the Cross-Flow Fan To remove the Motor CoverElectric Control Device Schematic DiagramIndoorAS-W096U 0, AS-W126U 0 Series OutdoorAS-W096Series, AS-W126Series Indoor Unit AS-W096/126U0,1 Series Wiring DiagramAS-W126U0 Series Outdoor Unit AS-W096U0 SeriesComponents Location Indoor Main P.W.B Assembly DC PartDisplay ASSEMBLYAS-W096/126U0,1 Series Outdoor Main P.W.B Assembly AS-W096/126U0 Series Model Adopted Electrion Expansion Valve Troubleshooting GuideRefrigeration Cycle Diagram Model Capillary TubePipe Length and the Elevation Oil trap should be installed per 5~7 metersOutdoor unit Indoor unit Way Valve Liquid Side Way, 3-way ValvePurge the air from the system ProcedureAir purging Check for gas leakageAir purging of the charge hose Pumping DownSet the 2-way valve to the closed position Air purging Re-installationMount the valve stem nuts and the service port nut Re-air PurgingGas leakage Balance Refrigerant of the 3-way ValveAll amount of refrigerant leaked EvacuationPurge the air from the charge hose Gas ChargingAfter Evacuation Connect the charge hose to the charging cylinderTrouble analysis Cycle PartsSelf-diagnosis function Diagnosis Procedure Precaution in Service or CheckElectronic Parts Procedure Specification RemedyProduct doesnt operate with the remote controller Check Point Comp. on Comp. OFF Compressor/Outdoor Fan are unable to driveWhen indoor Fan does not operate Trouble 5 When the horizontal louver does not operate Heater does not operate at all Indoor Outdoor Outdoor Unit does not operate at allDC Peak ErrorError Code ➅ Trouble 8-1When compressor does not operate normallyCommunication error between Indoor and Outdoor Error Code ➄ Trouble 8-2When compressor does not oprate normallyCT Error Error Code ➆ Trouble 8-3When compressor does not oprate normallyCN-T/Block Problem of missing the connector Indoor Main PCB AssyProblem of missing the connector Outdoor Main PCB Assy Connectors Condition Problem error modeIndoor Unit Exploded ViewOutdoor Unit Description Replacement Parts ListPanel ASSY, Front SUB No A20061Z October