LG Electronics AS-W096URH1/UBH1/UWH1/UMH1 Re-air Purging, Re-installation, Air purging

Page 62

Troubleshooting Guide

Re-air Purging

(Re-installation)

Indoor unit

Liquid side

 

Closed

Outdoor unit

3-Way valve

Gas side

Closed

3-Way valve

Gas cylinder

Lo

R22

OPEN

CLOSE

• Procedure

(1)Confirm that both the liquid side valve and the gas side valve are set to the closed position.

(2)Connect the charge set and a gas cylinder to the service port of the Gas side valve.

Leave the valve on the gas cylinder closed.

(3)Air purging.

Open the valves on the gas cylinder and the charge set. Purge the air by loosening the flare nut on the liquid side valve approximately 45° for 3 seconds then closing it for 1 minute; repeat 3 times.

After purging the air, use a torque wrench to tighten the flare nut on liquid side valve.

(4)Check for gas leakage.

Check the flare connections for gas leakage.

(5)Discharge the refrigerant.

Close the valve on the gas cylinder and dis- charge the refrigerant until the gauge indicates 3 to 5 kg/cm2g.

(6)Disconnect the charge set and the gas cylin- der, and set the Liquid side and Gas side valves to the open position.

Be sure to use a hexagonal wrench to operate the valve stems.

(7)Mount the valve stem nuts and the service port nut.

Use torque wrench to tighten the service port nut to a torque of 1.8 kg.m.

Be sure to check for gas leakage.

CAUTION: Do not leak the gas in the air during Air Purging.

62Room Air Conditioner

Image 62
Contents LG Room Air Conditioner Table of Contents Code Type Code of Model Meaning LG Model Name2002 2003~2005 MeaningSafety Precautions InstallationThere is risk of fire, electric shock, explosion, or injury Operation ThinnerKeep level even when installing the product Be cautious that water could not enter the productOperation Indoor Unit DimensionsSymbols Used in this Manual 9k, 12k Btu SeriesOutdoor Unit Product Specifications AS-W096U0 AS-W126U0 AS-W096U1 AS-W126U1Indoor unit InstallationSelect the best Location Outdoor unitPiping Length and Elevation Fixing Installation PlateOil trap should be installed every 5~7 meters Drill a Hole in the Wall Flaring WorkIndoor Connecting the PipingCheck Foamed polyethylene or equivalent is recom- mendedWrap the insulation material around the connecting portion For left rear piping Indoor unit installation For left piping. Follow the instruction below Good case Bad caseOutdoor Outdoor unitConnecting the Cables Circuit Grade Breaker Drain piping Checking the DrainageTo check the drainage Forming the Piping Air purging with vacuum pump Air PurgingAir purging Finishing the job Soap water methodEvacuation Settlement of outdoor unit Prepare remote controllerTest Running Evaluation of the performancePump Down Procedure Pump DownFunctions Overheatng. ProtectionPower module Power relay controlActive power filter controlPSC Stand by control at low tempHigh39C Low11C Cancel Sleep Mode, Timer on or Timer OFF3, 4, 5, 6 Off Timer Cooling Down to 18C Heating Down to 16C Up to 30CLG Brand/OEM Brand OperationLED display of indoor unit Protection of the evaporator pipe from frosting Control methodCooling mode operation Model Comp. Operating frequencyHealthy Dehumidification mode operation Intake air Temp Setting TempTemp. differences Comp. Operating frequency Heating mode operationOperating freq. step of comp Fuzzy operation for cooling Fuzzy mode operationOptionalsIntake air temp Setting temp Fan speed At beginningFuzzy operation for Heating Fuzzy operation for dehumidificationSwing mode Jet cool mode operationJet heat mode operation Chaos swing modeSleep timer operation for heating cycle Sleep timer operationSleep timer operation for cooling cycle Forced operation Indoor temp Operating Mode Setting tempAuto restarting operation Trial OperationProtection from total current control Protection from DC Peak CurrentPortection from overheating of power module Portection from overheating of compressorAS-W096/126U1 Series Defrosting controlAS-W096/126U0 Series Low Ambient Auto CleaningAuto ChangeoverOptional Disassembly To remove the Grille from the ChassisTo remove the Evaporator To remove the Control BoxTo remove the Discharge Grille To remove the Motor Cover To remove the Cross-Flow FanIndoorAS-W096U 0, AS-W126U 0 Series Schematic DiagramElectric Control Device OutdoorAS-W096Series, AS-W126Series Wiring Diagram Indoor Unit AS-W096/126U0,1 SeriesOutdoor Unit AS-W096U0 Series AS-W126U0 SeriesIndoor Main P.W.B Assembly DC Part Components LocationDisplay ASSEMBLYAS-W096/126U0,1 Series Outdoor Main P.W.B Assembly AS-W096/126U0 Series Model Capillary Tube Troubleshooting GuideRefrigeration Cycle Diagram Model Adopted Electrion Expansion ValveOutdoor unit Indoor unit Oil trap should be installed per 5~7 metersPipe Length and the Elevation Way, 3-way Valve Way Valve Liquid SideCheck for gas leakage ProcedureAir purging Purge the air from the systemSet the 2-way valve to the closed position Pumping DownAir purging of the charge hose Re-air Purging Re-installationMount the valve stem nuts and the service port nut Air purgingBalance Refrigerant of the 3-way Valve Gas leakageEvacuation All amount of refrigerant leakedConnect the charge hose to the charging cylinder Gas ChargingAfter Evacuation Purge the air from the charge hoseCycle Parts Trouble analysisSelf-diagnosis function Precaution in Service or Check Diagnosis ProcedureProcedure Specification Remedy Electronic PartsProduct doesnt operate with the remote controller Compressor/Outdoor Fan are unable to drive Check Point Comp. on Comp. OFFWhen indoor Fan does not operate Trouble 5 When the horizontal louver does not operate Heater does not operate at all Outdoor Unit does not operate at all Indoor OutdoorTrouble 8-1When compressor does not operate normally DC Peak ErrorError Code ➅Trouble 8-2When compressor does not oprate normally Communication error between Indoor and Outdoor Error Code ➄Trouble 8-3When compressor does not oprate normally CT Error Error Code ➆Connectors Condition Problem error mode Problem of missing the connector Indoor Main PCB AssyProblem of missing the connector Outdoor Main PCB Assy CN-T/BlockExploded View Indoor UnitOutdoor Unit Replacement Parts List DescriptionPanel ASSY, Front SUB No A20061Z October