LG Electronics AS-W126URH0/UBH0/UWH0/UMH0/UCH0, AS-W126URH1/UBH1/UWH1/UMH1 service manual

Page 17

Installation

4.Indoor unit installation

Hook the indoor unit onto the upper portion of the installation plate.(Engage the two hooks of the rear top of the indoor unit with the upper edge of the installation plate.) Ensure that the hooks are properly seated on the installation plate by moving it left and right.

Press the lower left and right sides of the unit against the installation plate until the hooks engage into their slots(clicking sound).

Connecting the piping to the indoor unit and drain hose to drain pipe.

1.Align the center of the pipes and sufficiently tighten the flare nut by hand.

2.Tighten the flare nut with a wrench.

Outside diameter

Torque

 

 

 

mm

inch

kg.m

Ø6.35

1/4

1.8

Ø9.52

3/8

4.2

Ø12.7

1/2

5.5

3.When extending the drain hose at the indoor unit, install the drain pipe.

Connecting

cable

Drain hose

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor unit tubing

Flare nut Pipes

 

 

 

 

 

 

 

 

 

 

Open-end wrench (fixed)

Flare nut

Wrench

Connection pipe

Indoor unit tubing

Drain pipe

Indoor unit drain hose

Adhesive Vinyl tape(narrow)

Wrap the insulation material around the connecting portion.

1.Overlap the connection pipe insulation material and the indoor unit pipe insulation material. Bind them together with vinyl tape so that there may be no gap.

2.Wrap the area which accommodates the rear piping housing section with vinyl tape.

3.Bundle the piping and drain hose together by wrap- ping them with vinyl tape for enough to cover where they fit into the rear piping housing section.

Plastic bands Insulation material

Connection pipe

Indoor unit pipe

Vinyl tape (wide)

Wrap with vinyl tape

Connecting cable

Pipe

Vinyl tape(narrow)

Wrap with vinyl tape

Pipe

Vinyl tape(wide)

Drain hose

Service Manual 17

Image 17
Contents LG Room Air Conditioner Table of Contents Code Type Code of Model Meaning LG Model Name2002 Meaning 2003~2005Installation Safety PrecautionsThere is risk of fire, electric shock, explosion, or injury Thinner OperationBe cautious that water could not enter the product Keep level even when installing the productOperation Symbols Used in this Manual DimensionsIndoor Unit 9k, 12k Btu SeriesOutdoor Unit AS-W096U0 AS-W126U0 AS-W096U1 AS-W126U1 Product SpecificationsSelect the best Location InstallationIndoor unit Outdoor unitPiping Length and Elevation Fixing Installation PlateOil trap should be installed every 5~7 meters Flaring Work Drill a Hole in the WallCheck Connecting the PipingIndoor Foamed polyethylene or equivalent is recom- mendedWrap the insulation material around the connecting portion For left rear piping Indoor unit installation Bad case For left piping. Follow the instruction below Good caseOutdoor unit OutdoorConnecting the Cables Circuit Grade Breaker Drain piping Checking the DrainageTo check the drainage Forming the Piping Air purging with vacuum pump Air PurgingAir purging Finishing the job Soap water methodEvacuation Test Running Prepare remote controllerSettlement of outdoor unit Evaluation of the performancePump Down Pump Down ProcedureFunctions Active power filter controlPSC Power relay controlOverheatng. ProtectionPower module Stand by control at low temp3, 4, 5, 6 Off Timer Cancel Sleep Mode, Timer on or Timer OFFHigh39C Low11C Cooling Down to 18C Heating Down to 16C Up to 30CLG Brand/OEM Brand OperationLED display of indoor unit Control method Protection of the evaporator pipe from frostingModel Comp. Operating frequency Cooling mode operationIntake air Temp Setting Temp Healthy Dehumidification mode operationTemp. differences Comp. Operating frequency Heating mode operationOperating freq. step of comp Intake air temp Setting temp Fan speed Fuzzy mode operationOptionalsFuzzy operation for cooling At beginningFuzzy operation for dehumidification Fuzzy operation for HeatingJet heat mode operation Jet cool mode operationSwing mode Chaos swing modeSleep timer operation for heating cycle Sleep timer operationSleep timer operation for cooling cycle Auto restarting operation Indoor temp Operating Mode Setting tempForced operation Trial OperationProtection from DC Peak Current Protection from total current controlPortection from overheating of compressor Portection from overheating of power moduleAS-W096/126U1 Series Defrosting controlAS-W096/126U0 Series Low Ambient Auto CleaningAuto ChangeoverOptional To remove the Grille from the Chassis DisassemblyTo remove the Evaporator To remove the Control BoxTo remove the Discharge Grille To remove the Cross-Flow Fan To remove the Motor CoverIndoorAS-W096U 0, AS-W126U 0 Series Schematic DiagramElectric Control Device OutdoorAS-W096Series, AS-W126Series Indoor Unit AS-W096/126U0,1 Series Wiring DiagramAS-W126U0 Series Outdoor Unit AS-W096U0 SeriesComponents Location Indoor Main P.W.B Assembly DC PartDisplay ASSEMBLYAS-W096/126U0,1 Series Outdoor Main P.W.B Assembly AS-W096/126U0 Series Refrigeration Cycle Diagram Troubleshooting GuideModel Capillary Tube Model Adopted Electrion Expansion ValveOutdoor unit Indoor unit Oil trap should be installed per 5~7 metersPipe Length and the Elevation Way Valve Liquid Side Way, 3-way ValveAir purging ProcedureCheck for gas leakage Purge the air from the systemSet the 2-way valve to the closed position Pumping DownAir purging of the charge hose Mount the valve stem nuts and the service port nut Re-installationRe-air Purging Air purgingGas leakage Balance Refrigerant of the 3-way ValveAll amount of refrigerant leaked EvacuationAfter Evacuation Gas ChargingConnect the charge hose to the charging cylinder Purge the air from the charge hoseTrouble analysis Cycle PartsSelf-diagnosis function Diagnosis Procedure Precaution in Service or CheckElectronic Parts Procedure Specification RemedyProduct doesnt operate with the remote controller Check Point Comp. on Comp. OFF Compressor/Outdoor Fan are unable to driveWhen indoor Fan does not operate Trouble 5 When the horizontal louver does not operate Heater does not operate at all Indoor Outdoor Outdoor Unit does not operate at allDC Peak ErrorError Code ➅ Trouble 8-1When compressor does not operate normallyCommunication error between Indoor and Outdoor Error Code ➄ Trouble 8-2When compressor does not oprate normallyCT Error Error Code ➆ Trouble 8-3When compressor does not oprate normallyProblem of missing the connector Outdoor Main PCB Assy Problem of missing the connector Indoor Main PCB AssyConnectors Condition Problem error mode CN-T/BlockIndoor Unit Exploded ViewOutdoor Unit Description Replacement Parts ListPanel ASSY, Front SUB No A20061Z October