Operation
Protection of theevaporatorpipefromfrosting
•If the indoor pipe temperaure is below 0°C in 7 min. after the compressor operates without pause while in cooling cycle operation mode,
➔compressor, outdoor fan are turned off.
•When indoor pipe temp. is 7°C or higher after 2 min pause of compressor
➔compressor, outdoor fan is turned on according to the condition of the room temperature.
|
|
| Indoor pipe | |
| Comp. free | temp. | ||
6˚C |
|
| 7˚C | |
Comp. Step 4 |
| |||
3˚C |
| |||
Comp. Step 2 |
| |||
0˚C |
| |||
Comp. off |
| |||
|
|
Protection of the indoorfan from dropletformation (Enclosure sweat and condensed disposaltest)
•Control condition : The system operates standard operation without this condition as follows.
Setting temperature <25°C
Indoor fan speed ≤ low speed
Outdoor temperature < 30°C
•Control method
In operation for 5~20 minutes in , , conditions, return to the previous COMP STEP after operation for 5~40 minutes at the COMP STEP 3.
34Room Air Conditioner