LG Electronics AS-W096URH0/UBH0/UWH0/UMH0 Power relay control, Stand by control at low temp

Page 31

Functions

Outdoor Unit

Power relay control

• If power is on, it will operate to chage capacitor on controller and power relay will operate after about 2~5sec.

Stand by control at low temp.

If outdoor temp. is below 0°C, preheater is operating for 1~5min.

At the initial, It will be operated compressor after 1min. for preheating.

Active power filter control(PSC)

The active power filter is designed to correct power factor(cos θ ) and to regulate DC link voltage.

It will be operated PFC circuit when the compressor freq. is over 30Hz and wattage is over 450 watt.

Comp. Freq. control

The final operating freq. of comp. is set the lowest freq. that limited outdoor temp., discharge pipe temp., heat-sink temp., target freq., owing to CT.

Overheatng. Protection(Power module)

• When the temp. of power module increases to 85°C, controller decreases Freq. of Comp.

Freq. speed control(up/down speed)

• It will be changed the drive freq. of comp. according to temp. of indoor and outdoor.

V/F control

• It will be changed the drive voltage of comp. according to operating frequency.

Total current control (over current protection)

DC peak current control

4 way valve control

• It is only operated in the heating operation mode except defrosting operation.

Outdoor fan motor control

High speed

-Although fan motor speed is middle, it will change high speed in case of below AC193V, over 45°C of outdoor temp., and over fc, fh of comp. Freq.

Middle speed

-Nomal mode

Low speed

-Although fan motor speed is middle, it will change Low speed in case of over AC 270V, over 21°C (Heating Mode) of outdoor temp. below 24°C (Cooling Mode) of outdoor temp.

Discharge pipe temp. control

Low ambient

Service Manual 31

Image 31
Contents LG Room Air Conditioner Table of Contents 2002 LG Model NameCode Type Code of Model Meaning Meaning 2003~2005Installation Safety PrecautionsThere is risk of fire, electric shock, explosion, or injury Thinner OperationBe cautious that water could not enter the product Keep level even when installing the productOperation 9k, 12k Btu Series DimensionsSymbols Used in this Manual Indoor UnitOutdoor Unit AS-W096U0 AS-W126U0 AS-W096U1 AS-W126U1 Product SpecificationsOutdoor unit InstallationSelect the best Location Indoor unitOil trap should be installed every 5~7 meters Fixing Installation PlatePiping Length and Elevation Flaring Work Drill a Hole in the WallFoamed polyethylene or equivalent is recom- mended Connecting the PipingCheck IndoorWrap the insulation material around the connecting portion For left rear piping Indoor unit installation Bad case For left piping. Follow the instruction below Good caseOutdoor unit OutdoorConnecting the Cables Circuit Grade Breaker To check the drainage Checking the DrainageDrain piping Forming the Piping Air purging Air PurgingAir purging with vacuum pump Evacuation Soap water methodFinishing the job Evaluation of the performance Prepare remote controllerTest Running Settlement of outdoor unitPump Down Pump Down ProcedureFunctions Stand by control at low temp Power relay controlActive power filter controlPSC Overheatng. ProtectionPower moduleCooling Down to 18C Heating Down to 16C Up to 30C Cancel Sleep Mode, Timer on or Timer OFF3, 4, 5, 6 Off Timer High39C Low11CLED display of indoor unit OperationLG Brand/OEM Brand Control method Protection of the evaporator pipe from frostingModel Comp. Operating frequency Cooling mode operationIntake air Temp Setting Temp Healthy Dehumidification mode operationOperating freq. step of comp Heating mode operationTemp. differences Comp. Operating frequency At beginning Fuzzy mode operationOptionalsIntake air temp Setting temp Fan speed Fuzzy operation for coolingFuzzy operation for dehumidification Fuzzy operation for HeatingChaos swing mode Jet cool mode operationJet heat mode operation Swing modeSleep timer operation for cooling cycle Sleep timer operationSleep timer operation for heating cycle Trial Operation Indoor temp Operating Mode Setting tempAuto restarting operation Forced operationProtection from DC Peak Current Protection from total current controlPortection from overheating of compressor Portection from overheating of power moduleAS-W096/126U0 Series Defrosting controlAS-W096/126U1 Series Auto ChangeoverOptional Auto CleaningLow Ambient To remove the Grille from the Chassis DisassemblyTo remove the Discharge Grille To remove the Control BoxTo remove the Evaporator To remove the Cross-Flow Fan To remove the Motor CoverElectric Control Device Schematic DiagramIndoorAS-W096U 0, AS-W126U 0 Series OutdoorAS-W096Series, AS-W126Series Indoor Unit AS-W096/126U0,1 Series Wiring DiagramAS-W126U0 Series Outdoor Unit AS-W096U0 SeriesComponents Location Indoor Main P.W.B Assembly DC PartDisplay ASSEMBLYAS-W096/126U0,1 Series Outdoor Main P.W.B Assembly AS-W096/126U0 Series Model Adopted Electrion Expansion Valve Troubleshooting GuideRefrigeration Cycle Diagram Model Capillary TubePipe Length and the Elevation Oil trap should be installed per 5~7 metersOutdoor unit Indoor unit Way Valve Liquid Side Way, 3-way ValvePurge the air from the system ProcedureAir purging Check for gas leakageAir purging of the charge hose Pumping DownSet the 2-way valve to the closed position Air purging Re-installationMount the valve stem nuts and the service port nut Re-air PurgingGas leakage Balance Refrigerant of the 3-way ValveAll amount of refrigerant leaked EvacuationPurge the air from the charge hose Gas ChargingAfter Evacuation Connect the charge hose to the charging cylinderTrouble analysis Cycle PartsSelf-diagnosis function Diagnosis Procedure Precaution in Service or CheckElectronic Parts Procedure Specification RemedyProduct doesnt operate with the remote controller Check Point Comp. on Comp. OFF Compressor/Outdoor Fan are unable to driveWhen indoor Fan does not operate Trouble 5 When the horizontal louver does not operate Heater does not operate at all Indoor Outdoor Outdoor Unit does not operate at allDC Peak ErrorError Code ➅ Trouble 8-1When compressor does not operate normallyCommunication error between Indoor and Outdoor Error Code ➄ Trouble 8-2When compressor does not oprate normallyCT Error Error Code ➆ Trouble 8-3When compressor does not oprate normallyCN-T/Block Problem of missing the connector Indoor Main PCB AssyProblem of missing the connector Outdoor Main PCB Assy Connectors Condition Problem error modeIndoor Unit Exploded ViewOutdoor Unit Description Replacement Parts ListPanel ASSY, Front SUB No A20061Z October