PACKAGED TERMINAL AIR CONDITIONERS
ELECTRICAL & INSTALLATION • QUICK REFERENCE
Electrical Specifications
| Type | Model # | BTUs | Voltage | Rated | MCA* | MOP** |
|
|
|
|
| Amps |
|
|
PTAC | A/C | LP070CED | 7,600 | 230/208 - | 2.7/2.9 | 11.3 | 20 |
| A/C | LP090CED | 9,000 | 230/208 - | 3.6/3.9 | 13.2 | 20 |
| A/C | LP120CED | 11,800 | 230/208 - | 4.8/5.2 | 13.2 | 20 |
| A/C | LP150CED | 14,300 | 230/208 - | 6.5/7.1 | 13.2 | 20 |
PTHP | H/C | LP070HED | 7,600 | 230/208 - | 2.7/2.9 | 11.3 | 20 |
| H/C | LP090HED | 9,100 | 230/208 - | 3.6/3.9 | 13.2 | 20 |
| H/C | LP120HED | 12,100 | 230/208 - | 5.0/5.4 | 13.2 | 20 |
| H/C | LP150HED | 14,300 | 230/208 - | 6.7/7.3 | 13.2 | 20 |
NOTE: Please see local electrical codes for proper wire specifications.
*Minimum Circuit Ampacity
**Maximum Overcurrent Protection
Trim Molding |
| Caulk |
(if desired) |
| (4 sides) |
Room Side |
| 13 3/4" |
16" | Outside | |
Box and |
|
|
Receptacle |
| 42" |
16"
13 3/4"
38