UL 1610 and 1076 SPECIFICATIONS
Central-Station and Proprietary Burglar-Alarm Units
17.1Opening/Closing reports
The Opening/Closing Reports option must be programmed as YES. See section 5.2 of the XR10 Programming Guide
17.2Automatic bell test
This option must be programmed as YES. See section 7.3 of the XR10 Programming Guide
17.3Proprietary dialer
The Model XR10/XR20 provides Grade A proprietary service when configured as a digital dialer.
UL 1635 SPECIFICATIONS
Digital Burglar Alarm Communicator System Units
18.1Digital Dialer telephone number
Both programmed telephone numbers must begin with a D or P. See sections 3.17 and 3.18 of the XR10 Programming Guide
18.2Entry delay
The maximum entry delay used must not be more than 60 seconds. See section 6.4 of the XR10 Programming Guide
18.3Exit delay
The maximum exit delay used must not be more than 60 seconds. See section 6.5 of the XR10 Programming Guide
18.4Test frequency
The Test Frequency option must be programmed so that the XR10 sends a report once every 24 hours. See section 3.6 of the XR10 Programming Guide
18.5Automatic bell test
This option must be programmed as YES. See section 7.3 of the XR10 Programming Guide
18.6Grade B Central Station
Grade B Central Station service can be provided under UL 1635 by adding a Grade A local audible signal appliance and placing the Model XR10/XR20 panel into the Model 349A Grade A Attack Resistant Housing.
UL 365 and 609 SPECIFICATIONS
Police Station Connected and Local Burglar Alarm Units and Systems
19.1Entry delay
The maximum entry delay used must not be more than 60 seconds when using the Model 349A Grade A housing. See section 6.4 of the XR10 Programing Guide
19.2Grade A bell
A Grade A local audible signal appliance must be used.
19.3Bell cutoff
The bell cutoff time cannot be less than 15 minutes. See section 7.2 of the XR10 Programming Guide
19.4Automatic bell test
The Automatic Bell Test option must be programmed as YES. See section 7.3 of the XR10 Programming Guide
19.5Grade A Mercantile
For Grade A Mercantile and Police Station Connect operation the Model XR10/XR20 must be mounted in a Grade A attack resistant housing, (DMP Model 349A).
XR10/XR20 Installation Guide