UNIVERSAL UL and NFPA FIRE ALARM SPECIFICATIONS

Installation

19.6Mercantile Safe and Vault

When the DMP Model 349A housing is used, the XR10/XR20 provides operation as a mercantile safe and vault alarm. Bell Supervision and wiring must be in accordance with UL 681. If the Model XR10/XR20 is mounted outside the safe or vault, tamper protection and the Sentrol Model 5402 or Potter EVD listed vibration detectors should be used. The XR10/XR20 does not provide operation as a Bank Safe and vault alarm.

19.7Line security for Police Connect

Basic line security is provided when the Model XR10/XR20 is configured as a dialer system.

UNIVERSAL UL and NFPA FIRE ALARM SPECIFICATIONS

20.1Introduction

The programming and installation specifications contained in this section must be completed when installing the Model XR10/XR20 in accordance with any of the UL or NFPA fire standards. Additional specifications may be required by a particular standard.

20.2Wiring

All wiring must be in accordance with NEC, ANSI/NFPA 70.

20.3Police station phone number

The digital dialer telephone number programmed for communication must not be a police station phone number, unless that phone number is specifically provided for that purpose.

20.4System maintenance

Proper installation and regular maintenance by the installing alarm company and frequent testing by the end user is essential to ensure continuous satisfactory operation of any alarm system. Offering a maintenance program and acquainting the user with the correct procedure for use and testing of the system is also the responsibility of the installing alarm company.

20.5Audible alarm

Fire Type zones should be programmed to activate an audible alarm. The Bell Action for Fire Type zones should not be programmed as “N”. See section 7.4A in the XR10 Programming Guide (LT-0230) and XR20 Programming Guide (LT-0305).

20.6Fire zone programming

Fire zones must be programmed to activate a trouble on open conditions and an alarm on short conditions. The swinger bypass function must not be used on any fire zones. See section 8.8 in the XR10 Programming Guide (LT-0230) and XR20 Programming Guide (LT-0305).

20.7Ground Start

Ground Start phone lines must not be used for UL listed systems.

20.8UL Listed Receivers

UL has verified operation with the DMP SCS-1 Security Receiver, Sur-Gard SG-HLR2-DG, FBII CP220PB, Osborne-Hoffman Quick-Alert and Radionics D6500 receivers.

UL 985 NFPA 72 (chapter 2) SPECIFICATIONS

Household Fire Warning System Units

21.1Bell output definition

The bell output of the Model XR10/XR20 must be programmed to operate steady on burglary alarms and pulsed on fire alarms. See sections 7.4A and 7.4B of the XR10 Programming Guide (LT-0230) and XR20 Programming Guide (LT-0305).