DMP Electronics LT-0229 (5 97) Panel Specifications, Introduction, 1.1Power supply, 1.4Keypads

Models: LT-0229 (5 97)

1 18
Download 18 pages 60.1 Kb
Page 5
Image 5
Introduction

Introduction

Panel Specifications

1.1Power supply

Transformer Input: 16.5 VAC 40VA (Models 320 wire-in or 321 plug-in)

Standby Battery: 12 VDC 6.5Ah (40VA transformer charges up to 2 batteries)

Auxiliary Output: 12 VDC at 500mA

Bell Output: 12 VDC at 1.5 Amps

Smoke Detector Output: 12 VDC at 100mA All circuits inherent power limited

1.2Communication

Built-in SDLC Digital Dialer communication to DMP Model SCS-1 Receivers Built-in 4-2 communication to non-DMP receivers.

Built-in M2E (Radionics Modem IIe) communication to non-DMP receivers (XR20 only). Either panel can operate as a local system

1.3Panel zones

Nine 1k Ω EOL burglary zones (zones 1 to 9)

One 3.3k Ω EOL Class B powered fire zone with reset capability (zone 10)

1.4Keypads

You can connect up to four of the following supervised keypads to the XR10/XR20 panels.

16 or 32 character alphanumeric keypads

10-zone LED keypads

In addition, the following zone expanders can be added to the XR20 panel:

Four and single point zone expanders

Single point PIR and glassbreak detectors

When using the FA426 Wireless Receiver, the XR20 allows unsupervised devices to be added to address five.

1.5Outputs

The XR10/XR20 panels provide four open collector outputs rated for 50mA each. See section 12.1. A Model 300 Wire Harness is required. Open collectors don't provide voltage but instead ground a positive voltage source.

1.6Enclosure specifications

The XR10/XR20 ship in an enclosure with EOL resistors, battery leads, user's guide, and programming sheet.

Size:

12.5" W x 9.5" H x 2.75" D

Weight:

4 lbs

Color:

Gray or Black

Construction:

20 gauge cold rolled steel

Introduction

2.1Description

The DMP XR10/XR20 Command Processors are powerful 12 VDC burglary and fire communicator panels with battery backup. The XR10/XR20 provide nine on-board burglary zones and one on-board 12 VDC Class B powered fire zone. The fire zone has a reset capability to provide for 2-wire smoke detectors, relays, or other latching devices. The XR10/XR20 can communicate to one or two DMP SCS-1 Receivers using SDLC digital dialer or 4-2 reporting formats. In addition, the XR20 can communicate using the Radionics Modem IIe format.

2.2System configurations

The XR10/XR20 can be programmed to operate as either an All/Perimeter system that provides one Perimeter area and one Interior area, or as a Home/Sleep/Away system that provides one Perimeter, one Interior, and one Bedrooms area. The Bedrooms area can include any protection devices the user wants disarmed during their sleeping hours and armed in the Away mode. In addition, the XR20 can operate as a four area system.

XR10/XR20 Installation Guide

2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282

Page 1

Page 5
Image 5
DMP Electronics LT-0229 (5 97) manual Panel Specifications, Introduction, 1.1Power supply, 1.2Communication, 1.3Panel zones