DMP Electronics LT-0229 (5 97) Powered Zone for 2-WireSmoke Detectors, Installation, Condition

Models: LT-0229 (5 97)

1 18
Download 18 pages 60.1 Kb
Page 12
Image 12
Condition

Installation

10.2Operational parameters

Each burglary protection zone detects three conditions: open, normal, and short. The parameters for each are listed below:

Condition

Resistance on zone

Voltage on right terminal

Open

over 1300 ohms

over 2.0 VDC

Normal

600 to 1300 ohms

1.2 to 2.0 VDC

Short

under 600 ohms

under 1.2 VDC

 

1K

 

 

1K

 

 

1K

 

NORMALLY CLOSED CONTACTS

NORMALLY OPEN CONTACTS

 

 

 

 

 

 

 

 

COMBINATION: NORMALLY OPEN AND

 

 

 

 

 

 

NORMALLY CLOSED CONTACTS

 

 

 

 

 

 

 

 

 

 

 

Figure 3: Protection zone contact wiring

10.3Zone response time

A condition must be present on a zone for 500 milliseconds before it's detected by the XR10/XR20 panel. Ensure detection devices used on the protection zones are rated for use with this delay.

10.4Keyswitch arming zone

Momentary keyswitches

You can use a momentary keyswitch on a zone programmed as an Arming type for use in arming and disarming the system without a code.

How it works

When the Arming zone is placed into a shorted codition from a normal condition, the panel disarms any areas that are armed. If all areas are disarmed, the panel arms all areas.

If the Arming zone changes from normal to open while any area is armed, an alarm is indicated. If all areas are disarmed, only a trouble is indicated.

Powered Zone for 2-Wire Smoke Detectors

11.1Terminals 25 and 26

A resettable 2-wire Class B powered zone is provided on terminals 25 (positive) and 26 (negative) of the panel. For programming purposes, the zone number is 10. The zone uses a Model 309, 3.3k Ω EOL resistor (provided with the panel) and has an operating range of 8.8 to 14.2 VDC.

Power is dropped from zone 10 any time a Sensor Reset is performed on the panel. Whenever non-Fire and non-Supervisory zone types are used on zone 10, make the appropriate adjustments to the zone's Armed Action to prevent false alarms from occurring.

The UL compatibility identifier is: A.

Manufacturer

Model

Detector

Base

Base

# of

I D

I D

Detectors

 

 

 

Detection Systems

DS282

B

None

N/A

10

Detection Systems

DS282TH

B

None

N/A

10

Detection Systems

DS250

B

MB2W

A

10

Detection Systems

DS250TH

B

MB2W, MB2WL

A

10

Detection Systems

DS250HD

B

MB2W, MB2WL

A

10

Sentrol/ESL

429AT

S09A

None

N/A

12

DMP/Hochiki

SLK-835

HD-5

HSB-200, HSB-200N

HB-55

7

DMP/Hochiki

SLK-835H

HD-5

HSB-200, HSB-200N

HB-55

7

Hochiki

SLK-12

HD-4

HSB-12-1, HSB-12-1N

HB-80

20

Figure 4: Compatible 2-wire smoke detectors

XR10/XR20 Installation Guide

2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282

Page 8

Page 12
Image 12