ROUGH-IN-DIMENSIONS
GAS VALVE PIPING
SUF 130-300 1 1/4" NPT
SUF 130-400 1 1/4" NPT
TABLE 1 RECOVERY CAPACITIES.
|
|
|
|
|
|
| U.S. Gallons/Hr and Litres/Hr at TEMPERATURE RISE INDICATED |
|
| |||||||||||
| TYPE OF | INPUT | Approx. | F° | 20F° | 30F° | 40F° | 50F° | 60F° | 70F° | 80F° | 90F° | 100F° | 110° | 120F° |
| 130F° | 140F° | ||
MODEL | GAS | BTUH | KW | Capacity | C° | 11C° | 17C° | 22C° | 28C° | 33C° | 39C° | 44C° | 50C° | 56C° | 61C° | 67C° |
| 72C° | 78C° | |
SUF | NATURAL | 300,000 |
|
| 130 US Gals. | GPH | 1746 | 1164 | 873 | 699 | 582 | 499 | 436 | 388 | 349 | 318 | 291 |
| 269 | 250 |
| 88 |
| 492 Litres | LPH | 6610 | 4406 | 3304 | 2644 | 2203 | 1888 | 1652 | 1469 | 1322 | 1201 | 1102 |
| 1017 | 945 | ||
|
|
|
|
| ||||||||||||||||
SUF | PROPANE | 300,000 |
|
| 130 US Gals. | GPH | 1746 | 1164 | 873 | 699 | 582 | 499 | 436 | 388 | 349 | 318 | 291 |
| 269 | 250 |
| 88 |
| 492 Litres | LPH | 6610 | 4406 | 3304 | 2644 | 2203 | 1888 | 1652 | 1469 | 1322 | 1201 | 1102 |
| 1017 | 945 | ||
|
|
|
|
| ||||||||||||||||
SUF | NATURAL | 399,900 |
|
| 130 US Gals. | GPH | 2328 | 1552 | 1164 | 931 | 776 | 665 | 582 | 517 | 466 | 423 | 388 |
| 359 | 332 |
| 117 |
| 492 Litres | LPH | 8813 | 5875 | 4406 | 3525 | 2938 | 2518 | 2203 | 1958 | 1763 | 1602 | 1469 |
| 1356 | 1259 | ||
|
|
|
|
| ||||||||||||||||
SUF | PROPANE | 399,900 |
|
| 130 US Gals. | GPH | 2328 | 1552 | 1164 | 931 | 776 | 665 | 582 | 517 | 466 | 423 | 388 |
| 359 | 332 |
| 117 |
| 492 Litres | LPH | 8813 | 5875 | 4406 | 3525 | 2938 | 2518 | 2203 | 1958 | 1763 | 1602 | 1469 |
| 1356 | 1259 | ||
|
|
|
|
|
Recovery capacities are based on heater performance at 96% thermal efficiency for SUF 300 and 400.
FOREWORD
These designs comply with the current edition of the American
National Standard for Gas Water Heaters, Volume III,
ANSI Z21.10.3 / CSA 4.3 as an automatic circulating tank water heater, and automatic storage water heaters.
Detailed installation diagrams are found in this manual. These diagrams will serve to provide the installer with a reference for the materials and methods of piping necessary. It is highly essential that all water, gas piping and wiring be installed as shown on the
diagrams.
Particular attention should be given to the installation of thermometers at the locations indicated on the diagrams as these are necessary for checking the proper functioning of the heater.
In addition to these instructions, the equipment shall be installed in accordance with those installation regulations in force in the local area where the installation is to be made. These shall be carefully followed in all cases. Authorities having jurisdiction should be consulted before installations are made.
In the absence of local codes, the installation must comply with the current editions of the National Fuel Gas Code, ANSI Z223.1/NFPA 54 and the National Electrical Code, NFPA 70 or