TWO TEMPERATURE - TWO HEATERS (ONE PRE-HEATER/ONE BOOSTER HEATER)

WITH OR WITHOUT BUILDING RECIRCULATION

DANGER

TEMPERATURE SETTING SHOULD NOT EXCEED SAFE TEMPERATURE AT FIXTURES. SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 3. IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT, ADD AN ANTI-SCALD VALVE FOR HOT WATER SUPPLIED TO FIXTURES

*PIPE RELIEF VALVE TO OPEN DRAIN

**140°F (60°C)TO 150°F (66°C) SHOULD BE MAXIMUM WATER

TEMPERATURE MAINTAINED IN THE PRE-HEATERS.

120°F (49°C) SHOULD BE THE MINIMUM TEMPERATURE OF

WATER IN THE PRE-HEATERS.

CONNECT CIRCULATING LINE FROM FIXTURES, IF USED,

TO COLD WATER SUPPLY LINE OF PRE-HEATER.

CONNECT CIRCULATING LINE OF 180°F (82°C) OR BOOSTED WATER, IF USED, TO INLET WATER LINE TO BOOSTER.

INSTALL IN ACCORDANCE WITH LOCAL CODES.

33

Image 33
Contents Commercial GAS Water Heater Foreword ROUGH-IN-DIMENSIONSFeatures Table of ContentsHorizontal Sidewall Venting Vertical Rooftop Venting AT a Glance Quick Installation TipsWater Temperature Setpoint Adjustment Procedure High Limit Switch E.C.ODishwashing Machine Requirement Circulating Pump Installation InstructionsRequired Ability Insulation BlanketsHard Water ClearancesAIR Requirements Unconfined SpaceVenting Installation of Carbon Monoxide DetectorsCanadian Direct Vent US Horizontal Vent Vent Pipe Termination Direct Vent Terminal InstallationDirect Venting 3x 4 PVC Reducer with Intake ScreenVertical Vent Terminal Installation Installation SequenceVent Length Table Installation of Vent SystemControls and Switches GAS Piping HOT Surface IgniterConnection of GAS Pipe System Connections Water Potable Heating and Space Heating Heater WiringSUF 130-300 Wiring Diagram SUF 130-400 Wiring Diagram Electronic Control OperationSequence of Operation OverviewAdjusting the Operating Set Point Fault and Warning Conditions Changing the Display UnitsExample of a Warning Access to the Current Fault or Warning Example of a Fault Advanced Diagnostics InformationViewing Information About the Heater Viewing the Fault HistoryPrior to Start UP Required Ability Operating InstructionsOperating Instructions General Information MaintenanceDraining FlushingSediment Removal Lime Scale RemovalPowered Anode System Drain Valve and Access PanelsVent System Installation Diagrams Page Must be Identical Heaters Pipe Relief Valve to Open Drain Page Multiple Unit Installations Troubleshooting Motor RUNS, Burner Lights Momentarily Then Locks OUT Motor will not RUNReplacement Parts Noisy Burner OperationGAS Fails to Shut OFF Tank Model SUF-130-300/400 NEA /PEA Limited Warranty