INSTALLATION REQUIREMENTS FOR THE COMMONWEALTH OF MASSACHUSETTS

For all side wall terminated, horizontally vented power vent, direct vent, and power direct vent gas fueled water heaters installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven

(7)feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:

INSTALLATION OF CARBON MONOXIDE DETECTORS

At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the sidewall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors.

In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.

In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements provided that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.

APPROVED CARBON MONOXIDE DETECTORS

Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and CSA certified.

SIGNAGE

A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, “GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL

OBSTRUCTIONS.”

INSPECTION

The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a) 1 through 4.

EXEMPTIONS

The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:

1.The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented” in the most current edition of NFPA 54 as adopted by the Board; and

2.Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building, or structure used in whole or in part for residential purposes.

MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED

When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:

1.Detailed instructions for the installation of the venting system design or the venting system components; and

2.A complete parts list for the venting system design or venting system.

MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED

When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies “special venting systems,” the following requirements shall be satisfied by the manufacturer:

1.The referenced “special venting system” instructions shall be included with the appliance or equipment installation instructions; and

2.The “special venting systems” shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed installation instructions.

A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.

VENTING

WARNING

THE INSTRUCTIONS IN THIS SECTION ON VENTING MUST BE FOLLOWED TO AVOID CHOKED COMBUSTION OR RECIRCULATION OF FLUE GASES. SUCH CONDITIONS CAUSE SOOTING OR RISKS OF FIRE AND ASPHYXIATION.

Heater must be protected from freezing downdrafts during shutdown periods.

Image 8
Contents Commercial GAS Water Heater ROUGH-IN-DIMENSIONS ForewordTable of Contents FeaturesAT a Glance Quick Installation Tips Horizontal Sidewall Venting Vertical Rooftop VentingDishwashing Machine Requirement Water Temperature Setpoint Adjustment ProcedureHigh Limit Switch E.C.O Installation Instructions Circulating PumpRequired Ability Insulation BlanketsClearances Hard WaterAIR Requirements Unconfined SpaceInstallation of Carbon Monoxide Detectors VentingCanadian Direct Vent US Horizontal Vent Direct Vent Terminal Installation Vent Pipe TerminationDirect Venting 3x 4 PVC Reducer with Intake ScreenInstallation Sequence Vertical Vent Terminal InstallationInstallation of Vent System Vent Length TableControls and Switches Connection of GAS Pipe GAS PipingHOT Surface Igniter System Connections Heater Wiring Water Potable Heating and Space HeatingSUF 130-300 Wiring Diagram SUF 130-400 Wiring Diagram Operation Electronic ControlSequence of Operation OverviewAdjusting the Operating Set Point Example of a Warning Fault and Warning ConditionsChanging the Display Units Example of a Fault Advanced Diagnostics Information Access to the Current Fault or WarningViewing the Fault History Viewing Information About the HeaterOperating Instructions Prior to Start UP Required AbilityOperating Instructions Maintenance General InformationFlushing DrainingSediment Removal Lime Scale RemovalVent System Powered Anode SystemDrain Valve and Access Panels Installation Diagrams Page Must be Identical Heaters Pipe Relief Valve to Open Drain Page Multiple Unit Installations Troubleshooting Motor will not RUN Motor RUNS, Burner Lights Momentarily Then Locks OUTGAS Fails to Shut OFF Replacement PartsNoisy Burner Operation Model SUF-130-300/400 NEA /PEA Limited Warranty Tank

SUF-130-300, SUF-130-400 specifications

State Industries, a renowned leader in the manufacturing of high-efficiency commercial water heaters, has established a strong reputation with its SUF-130-400 and SUF-130-300 models. These units are engineered for optimal performance and energy savings, making them ideal choices for various applications in industries such as hospitality, healthcare, and manufacturing.

The SUF-130-400 model offers an impressive 400,000 BTU per hour input, ensuring rapid heating and consistent hot water supply even during peak demand periods. This model is designed with a durable stainless-steel construction, providing longevity and resistance to corrosion, which is essential for demanding environments. It features a high-efficiency burner that maximizes combustion efficiency and minimizes emissions, making it a sustainable choice for businesses looking to reduce their environmental impact.

On the other hand, the SUF-130-300 model, with a slightly lower input of 300,000 BTU per hour, is perfect for smaller operations that still require a reliable and efficient hot water solution. Despite its lower capacity, this model does not compromise on performance. It incorporates advanced insulation technology that significantly reduces heat loss, enhancing overall operational efficiency and reducing energy costs.

Both models utilize a proven electronic ignition system, ensuring reliable starting and reducing the need for constant pilot light maintenance. This technology is enhanced by a highly responsive digital control system that allows users to easily monitor and adjust temperatures as needed, further promoting intuitive operation and energy savings.

Safety is a priority with these units, as they are equipped with built-in safety mechanisms including flame roll-out switches and pressure relief valves, ensuring safe operation even under the most rigorous conditions. Additionally, the easy-access design facilitates straightforward maintenance and servicing, minimizing downtime and allowing for quick responses to any operational issues.

In conclusion, the State Industries SUF-130-400 and SUF-130-300 models represent the pinnacle of efficiency and reliability in commercial water heating. Their robust construction, advanced technology, and user-friendly features make them an excellent investment for any business requiring consistent hot water supply without compromising on performance or energy efficiency. These models are poised to meet the challenges of modern water heating needs while ensuring sustainability and safety.