State Industries SUF-130-300, SUF-130-400 warranty Operating Instructions

Page 26

c.Remove the pressure regulator cover screw (Figure 16) and adjust the pressure by turning the adjusting screw with a small screwdriver. In this example, with heater running on natural gas, do not exceed 4.0" (0.996 kPa) Water Column.

Clockwise to increase gas pressure and input rate.

Counterclockwise to decrease gas pressure and input rate.

d. “Clock” the meter as in step (b) above.

e.Repeat steps (c) and (d) until the specified input rate is achieved.

f.Turn the manual gas valve to “OFF”. Replace the pressure regulator cover screw. Remove the pressure gauge or manometer from the manifold pressure tap. Replace the set screw in the manifold pressure tap. If the gas pressure regulator cannot be adjusted to give the full input rating with sufficient gas pressure at the valve, check to ensure the unit is equipped with the correct orifice.

LIGHTING AND OPERATION INSTRUCTIONS

FOR YOUR SAFETY READ BEFORE OPERATING

WARNING IF YOU DO NOT FOLLOW THESE INSTRUCTIONS EXACTLY A FIRE OR EXPLOSION MAY RESULT CAUSING PROPERTY DAMAGE, PERSONAL INJURY OR LOSS OF LIFE.

A.This appliance does not have a pilot. It is equipped with an ignition device which automatically lights the burner. Do not try to light the burner by hand.

B.BEFORE OPERATING smell all around the appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.

“WHAT TO DO IF YOU SMELL GAS”

Do not try to light any appliance.

Do not touch any electric switch; do not use any telephone in your building.

Immediately call your gas supplier from a neighbor’s

telephone. Follow the gas supplier’s instructions.

If you cannot reach your gas supplier, call the fire department.

C.Use only your hand to push in or turn the gas control knob. Never use tools. If the knob will not push in or turn by hand, don’t try to repair it, call a qualified service technician. Force or attempted repair may result in fire or explosion.

D.Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.

 

 

 

OPERATING INSTRUCTIONS

 

1.

STOP! Read the safety information above on this

9. Set thermostat to desired setting.

 

 

 

label.

 

 

 

10. If the appliance will not operate, follow the instructions

2.

Set thermostat to lowest setting.

 

“To Turn Off Gas To Appliance” and call your service

 

technician or gas supplier.

 

 

 

 

 

3.

Turn off all electric power to the appliance.

 

 

 

4.

This appliance is equipped with an ignition device which

 

 

 

automatically lights the burner. Do not try to light the

 

 

 

burner by hand.

 

 

 

5.

Push in gas control knob slightly and turn clockwise

 

 

 

to “OFF”.

 

 

 

 

 

6.

Wait five (5) minutes to clear out any gas. If

you then

 

 

 

smell gas,

STOP! Follow “B” in the safety information

 

 

 

above on

this label. If you don’t smell gas, go on to

 

 

 

the next step.

 

 

 

 

 

7.

Turn gas control knob counterclockwise

to “ON”.

 

 

8.

Turn on all electric power to the appliance.

 

 

 

 

 

 

 

 

 

 

FOR YOUR SAFETY READ BEFORE OPERATING

1.Set the thermostat to lowest setting.

2.Turn off all electric power to appliance if service is to be performed.

3.Push in gas control knob slightly and turn clockwise to “OFF”. Do not force.

26

Image 26
Contents Commercial GAS Water Heater ROUGH-IN-DIMENSIONS ForewordTable of Contents FeaturesAT a Glance Quick Installation Tips Horizontal Sidewall Venting Vertical Rooftop VentingDishwashing Machine Requirement Water Temperature Setpoint Adjustment ProcedureHigh Limit Switch E.C.O Required Ability Installation InstructionsCirculating Pump Insulation BlanketsAIR Requirements ClearancesHard Water Unconfined SpaceInstallation of Carbon Monoxide Detectors VentingCanadian Direct Vent US Horizontal Vent Direct Venting Direct Vent Terminal InstallationVent Pipe Termination 3x 4 PVC Reducer with Intake ScreenInstallation Sequence Vertical Vent Terminal InstallationInstallation of Vent System Vent Length TableControls and Switches Connection of GAS Pipe GAS PipingHOT Surface Igniter System Connections Heater Wiring Water Potable Heating and Space HeatingSUF 130-300 Wiring Diagram SUF 130-400 Wiring Diagram Sequence of Operation OperationElectronic Control OverviewAdjusting the Operating Set Point Example of a Warning Fault and Warning ConditionsChanging the Display Units Example of a Fault Advanced Diagnostics Information Access to the Current Fault or WarningViewing the Fault History Viewing Information About the HeaterOperating Instructions Prior to Start UP Required AbilityOperating Instructions Maintenance General InformationSediment Removal FlushingDraining Lime Scale RemovalVent System Powered Anode SystemDrain Valve and Access Panels Installation Diagrams Page Must be Identical Heaters Pipe Relief Valve to Open Drain Page Multiple Unit Installations Troubleshooting Motor will not RUN Motor RUNS, Burner Lights Momentarily Then Locks OUTGAS Fails to Shut OFF Replacement PartsNoisy Burner Operation Model SUF-130-300/400 NEA /PEA Limited Warranty Tank