State Industries Power Vent/Power Direct Vent Gas Models instruction manual Figure F

Page 24

5.Secure assembly to roof structure as shown in Figure E using field supplied metal strapping or equivalent support material.

NOTE: Ensure termination height is above the roof surface or anticipated snow level (1 ft. in U.S.A. or 1-1/2 ft. in Canada) as shown in Figure C.

6. Install rain cap and small diameter pipe assembly in roof penetration assembly, Ensure small diameter pipe i s c e m e n t e d a n d b o t t o m e d i n Y c o n c e n t r i c f i t t i n g .

7.Cement water heater combustion air intake and vent pipes to concentric vent termination assembly. See Figure E for proper pipe attachment.

8.Operate heater through 1 heat cycle to ensure combustion air and vent pipes are properly connected to concentric vent termination connections.

NOTE: All vent terminations must be the same height when installing multiple unit venting. If assembly is too short to meet height requirement, the 2 pipes supplied in the kit may be replaced by using same diameter, field supplied SDR-26 PVC (D2241) pipe. Do not extend the 21-1/8” dimension outer pipe to be more than 60 inches, see Figure B.

CAUTION

Do not use field-supplied couplings to extend pipes. Airflow restriction will occur and the heater pressure switch may cause intermittent operation.

PROCEDURE 2 SIDE WALL TERMINATION, see Figure F.

Figure F.

1. Determine best location for termination kit.

NOTE: Consideration for the following should be used when determining an appropriate location for the termination kit:

• Termination kit positioned where the vent vapors will n o t d a m a g e p l a n t s / s h r u b s o r a i r c o n d i t i o n i n g equipment.

Termination kit positioned so it will not be affected by wind eddy that may allow recirculation of combustion products, or airborne leaves, or light snow.

Termination kit positioned where it will not get damaged or be subjected to foreign objects, such as stones, balls, etc.

Termination kit positioned where the vent vapors will not be objectionable.

NOTE: See the venting information (pages 16-20) in this manual for additional vent location requirements.

2.Cut 1 hole (5 in. diameter)

3.Partially assemble concentric vent termination kit .

a)Cement the Y concentric fitting to larger diameter kit pipe, see Figure A.

b)Cement the rain cap to the smaller diameter kit pipe, see Figure A.

NOTE: Instead of cementing the smaller pipe to the rain cap, a

field-supplied stainless steel screw may be used to secure the 2 components together when field disassembly is desired for

cleaning, see Figure D.

WARNING

When using alternate screw assembly method, drill clearance hole in rain cap and pilot hole in vent pipe for screw being used. Failure to drill adequate holes may cause cracking of PVC components, allowing combustion products to be recirculated. Failure to follow this warning could result in personal injury or death.

WARNING

Do not operate the heater with rain cap removed or recirculation of combustion products may occur. Water may also collect inside larger combustion-air pipe and flow to the burner enclosure. Failure to follow this warning could result in product damage or improper operation, personal injury or death.

4.Install Y concentric fitting and pipe assembly through structure’s hole.

NOTE: Do not allow insulation or other materials to accumulate inside pipe assembly when installing through hole.

5.Install rain cap and small diameter pipe assembly in Y concentric fitting and large pipe assembly. Ensure small diameter pipe is bottomed and cemented in Y concentric fitting.

6.Secure assembly to structure as shown in Figure G using field- supplied metal strapping or equivalent support material.

NOTE: Ensure termination location clearance dimensions are as shown in the diagrams found in Figure 15 A through D. When extending the length of the 4” pipe, the added length beyond 21-1/8” must be deducted from the maximum equivalent feet of vent pipe.

NOTE: If assembly needs to be extended to allow side wall thickness requirement, the 2 pipes supplied in the kit may be replaced by using same diameter, field- supplied SDR-26 PVC (D2241) pipe. Do not extend 21 1/8” dimension more than 60 in. (See Figure B.)

CAUTION

Do not use field-supplied couplings to extend pipes. Airflow restriction will occur and the heater pressure switch may cause intermittent operation.

7.Cement heater combustion-air and vent pipes to concentric vent termination assembly. See Figure G for proper pipe attachment.

24

Image 24
Contents Whenever maintenance adjustment or service is required 197834-000Safe INSTALLATION, USE and Service Important DefinitionsGeneral Safety General Safety Table of Contents IntroductionReplacement Parts and Deliming Products GET to Know Your Water Heater GAS ModelsInstallation Considerations Rough-In-DimensionsRecovery capacity based on 96% thermal efficiency All models Maximum Supply Pressure 14 inches W.C .48kPaDirectly BELOW. Keep Clear of ALL Obstructions Water Piping Mixing Valve Usage Facts to Consider About the Location Insulation Blankets Combustion AIR and VentilationAppliances in Unconfined Spaces Appliances in Confined SpacesALL AIR from Inside Buildings See ALL AIR from Outdoors See Figures 7, 8Installing the NEW Water Heater Chemical Vapor CorrosionWater Piping Closed Water SystemsTemperature-Pressure Relief Valve Valve and Pipe Insulation if suppliedHigh Altitude Installations Gas PipingSediment Traps Venting Filling the Water HeaterVent Pipe Termination Power Vent Canadian Power VentVent Hoods MAY be Extremely HOT During Operation Direct Vent Canadian Direct VentInstallations Planning the Vent SystemCondensate Installation of Vent System Vent Terminal INSTALLATION, SidewallSequence of INSTALLATIONS, a Direct Vent Terminal Installation ImportantInstallation Sequence Vertical Vent Terminal InstallationVent Terminals Supplied with Heater Must be Used Installation of Vent SYSTEM, Sidewall Installation of Vertical Vent SystemConcentric Vent Installation KIT ComponentsSafety Considerations Installation Procedure 1 Roof TERMINATION, see Figure CProcedure 2 Side Wall TERMINATION, see Figure F Figure FMULTI-CONCENTRIC Vent Terminations Figure gVent Pipe Preparation Step B Step EStep F Step GBlower Prover Switch Blocked Exhaust SwitchBlocked Intake Switch ON/OFF SwitchPower Vent Wiring Schematic Figure ON/OFF Switch Do not try to light the burner by handWhat to do if YOU Smell GAS Do not TRY to Light the Burner by HandTemperature Regulation HI Limit Switch E.C.OUsing the Electronic Controller OverviewOperating States ActionDisplay Action Fault and Warning Conditions Access to the Current Fault or WarningChanging the Display Units DisplayViewing the Fault History Viewing Information About the HeaterFor Your Information Start UP ConditionsOperational Conditions Periodic Maintenance Burner CleaningVenting System Inspection Burner Operation and InspectionTemperature-Pressure Relief Valve Operation Anode ROD InspectionDraining Service Leakage CheckpointsTroubleshooting Guidelines ProblemsPage Page Limited Warranty

Power Vent/Power Direct Vent Gas Models specifications

State Industries offers a range of power vent and power direct vent gas models that cater to various residential and commercial heating needs. These models are designed for efficiency, safety, and convenience, making them a popular choice among consumers seeking reliable water heating solutions.

One of the standout features of State Industries' power vent models is their ability to vent directly through walls or roofs, enabling installation in locations where traditional venting methods may pose challenges. This flexibility makes them ideal for homes without suitable chimney access. The power vent system employs a fan to push exhaust gases out, ensuring efficient operation even in cases where vertical venting is not feasible.

The power direct vent models take this a step further by utilizing sealed combustion technology. This means they draw air for combustion from outside the home, which significantly reduces the risk of backdrafts and improves indoor air quality. The dual-venting system of these models also enhances their efficiency, as it allows for better control of air flow and exhaust.

State Industries incorporates advanced technologies in their gas models, including electronic ignition systems that eliminate the need for a standing pilot light. This feature not only enhances energy efficiency but also adds convenience for users. Moreover, these models come equipped with LED indicators that provide real-time status updates, enabling users to monitor their units easily.

Durability and reliability are hallmarks of State Industries products. The tanks are constructed with high-quality materials and feature protective coatings that inhibit corrosion, ensuring a long lifespan. In addition to this, many models are backed by extended warranties, providing peace of mind for consumers.

Energy efficiency is a critical characteristic of these gas models, with many units meeting or exceeding energy efficiency standards set by the Environmental Protection Agency (EPA). This results in lower utility bills and a reduced environmental impact. With adjustable temperature settings, users can optimize their water heating experience while conserving energy.

In conclusion, State Industries' power vent and power direct vent gas models stand out for their flexibility in installation, advanced technologies, and energy-efficient operation. Whether for residential or commercial use, these models offer high performance and reliability, ensuring that users enjoy a consistent and efficient hot water supply.