SPECIFICATIONS Continued
UNITS WITH 
  | UNIT SIZE  | 
  | 024005 | 024075 | 024011 | 
  | 030005 | 030075 | 030011 | 
  | 
  | RATINGS & PERFORMANCES  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | Nominal Capacity (Btuh)*  | 
  | 24,000  | 24,000  | 24,000  | 
  | 30,000  | 30,000  | 30,000  | 
  | 
  | Nominal Airflow (CFM)  | 
  | 
  | 870  | 
  | 
  | 
  | 1080  | 
  | 
  | 
  | Electric Heating Output (kw @240v)  | 
  | 5.0  | 7.5  | 11.0  | 
  | 5.0  | 7.5  | 11.0  | 
  | 
  | Electric Heating Capacity (MBH @208/230v)  | 14.0/16.9  | 20.4/24.7  | 29.4/35.7  | 
  | 14.3/17.2  | 20.7/25.0  | 29.7/36.0  | 
  | |
  | ELECTRICAL | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | Unit   | 
  | 
  | 
  | ||||||
  | Operating Voltage Range  | 
  | 
  | 
  | ||||||
  | Internal Circuit Protection  | 
  | 
  | 
  | 
  | None  | 
  | 
  | 
  | |
  | Full Load Amps  | 
  | 18.1/20.0  | 27.1/30.0  | 39.8/44.0  | 
  | 18.1/20.0  | 27.1/30.0  | 39.8/44.0  | 
  | 
  | Minimum Ampacity for Wire Sizing  | 
  | 24.5/26.9  | 35.8/39.4  | 51.6/56.9  | 
  | 25.2/27.5  | 36.4/40.0  | 52.3/57.5  | 
  | 
  | Minimum Wire Size†  | 
  | 10/10  | 8/8  | 6/6  | 
  | 10/10  | 8/8  | 6/6  | 
  | 
  | Maximum Wire Length (Ft)†  | 
  | 112/112  | 117/117  | 122/122  | 
  | 112/112  | 117/117  | 125/125  | 
  | 
  | Maximum Fuse Size (Amps or Ckt Bkr)  | 
  | 25/30  | 40/40  | 60/60  | 
  | 30/30  | 40/40  | 60/60  | 
  | 
  | Control Transformer 24V (Va)  | 
  | 
  | 
  | 
  | 40  | 
  | 
  | 
  | |
  | INDOOR COIL | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | Rows & Fins Per In.  | 
  | 
  | 
  | 3 & 14  | 
  | 
  | 
  | ||
  | Height x Width (In.)  | 
  | 
  | 18 x 17.8  | 
  | 
  | 
  | 22 x 17.8  | 
  | 
  | 
  | Face Area (Sq Ft)  | 
  | 
  | 2.23  | 
  | 
  | 
  | 2.73  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | |||||
  | 
  | 
  | 
  | TXV  | 
  | 
  | 
  | |||
  | Piston Number‡  | 
  | 
  | 63  | 
  | 
  | 
  | 70  | 
  | 
  | 
  | Condensate Drain Connection   | 
  | 
  | 
  | 3/4 FPT  | 
  | 
  | 
  | ||
  | INDOOR BLOWER & MOTOR | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | Wheel Diameter x Width (In.)  | 
  | 
  | 
  | 10 x 6  | 
  | 
  | 
  | ||
  | Filter   | 
  | 
  | 
  | 16 x 20 x 1  | 
  | 
  | 
  | ||
  | Blower Motor HP  | 
  | 
  | 1/5  | 
  | 
  | 
  | 1/3  | 
  | 
  | 
  | Blower Motor Speeds & Type  | 
  | 
  | 
  | 2 (PSC)  | 
  | 
  | 
  | ||
  | Full Load Amps  | 
  | 
  | 1.5  | 
  | 
  | 
  | 2.0  | 
  | 
  | 
  | OPTIONAL EQUIPMENT (P/N’s) | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | Louvered Wall Panel with Frame  | (6 Pack)  | 
  | 
  | KFBLG0106LGL  | 
  | 
  | 
  | ||
  | Electric Heat Package  | 
  | 
  | See ‘‘Optional   | 
  | 
  | ||||
* Rated in accordance with U.S. Government DOE test procedures and/or ARI Standard 
†Use copper wire only. Use 75°C in this application. When using 
ductors, instead of wire sizes shown in table above per NEC 1996 Article 
‡Check outdoor unit for required piston size.
††018 Size with