COOLING CAPACITIES (MBtuh)
|
|
|
|
|
|
| COIL REFRIGERANT TEMPERATURE* (°F) |
|
|
|
|
| ||||||
| EVAPORATOR |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 35 |
|
| 40 |
|
|
| 45 |
|
|
| 50 |
|
| 55 |
| |
| AIR |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
UNIT |
|
|
|
|
|
| Evap |
|
|
|
|
| ||||||
CFM and |
|
|
|
|
|
|
|
|
|
|
| |||||||
SIZE | BF | 72 | 67 | 62 | 72 | 67 |
| 62 | 72 | 67 | 62 | 72 |
| 67 | 62 | 72 | 67 | 62 |
| 400 | 27 | 23 | 19 | 25 | 20 |
| 16 | 22 | 17 | 13 | 19 |
| 14 | 10 | 15 | 10 | 8 |
| 0.08 | 13 | 14 | 15 | 12 | 13 |
| 13 | 10 | 11 | 12 | 9 |
| 10 | 10 | 8 | 8 | 8 |
| 500 | 30 | 25 | 21 | 28 | 22 |
| 18 | 24 | 19 | 15 | 21 |
| 15 | 12 | 16 | 11 | 10 |
018 | 0.10 | 14 | 16 | 17 | 13 | 14 |
| 16 | 12 | 13 | 14 | 10 |
| 11 | 12 | 9 | 10 | 10 |
600 | 33 | 27 | 22 | 30 | 24 |
| 19 | 26 | 21 | 16 | 23 |
| 17 | 13 | 18 | 12 | 11 | |
|
|
| ||||||||||||||||
| 0.13 | 15 | 17 | 19 | 14 | 16 |
| 18 | 13 | 14 | 16 | 11 |
| 13 | 13 | 10 | 11 | 11 |
| 650 | 34 | 28 | 23 | 31 | 25 |
| 20 | 27 | 21 | 17 | 23 |
| 17 | 14 | 18 | 13 | 12 |
| 0.14 | 16 | 18 | 20 | 14 | 17 |
| 18 | 13 | 15 | 16 | 12 |
| 13 | 14 | 10 | 11 | 12 |
| 600 | 38 | 32 | 26 | 35 | 29 |
| 22 | 31 | 24 | 18 | 26 |
| 19 | 14 | 21 | 13 | 12 |
| 0.05 | 18 | 20 | 21 | 16 | 18 |
| 19 | 15 | 16 | 17 | 13 |
| 14 | 14 | 11 | 11 | 12 |
024 | 700 | 41 | 34 | 28 | 38 | 30 |
| 24 | 33 | 26 | 20 | 28 |
| 20 | 16 | 22 | 15 | 13 |
0.06 | 19 | 21 | 23 | 18 | 19 |
| 21 | 16 | 18 | 19 | 14 |
| 15 | 16 | 12 | 13 | 13 | |
|
|
| ||||||||||||||||
| 875 | 46 | 38 | 31 | 41 | 34 |
| 27 | 37 | 29 | 22 | 31 |
| 23 | 19 | 25 | 17 | 16 |
| 0.08 | 21 | 24 | 27 | 20 | 22 |
| 24 | 18 | 20 | 22 | 16 |
| 18 | 19 | 14 | 15 | 16 |
| 750 | 46 | 38 | 31 | 41 | 33 |
| 26 | 36 | 28 | 21 | 30 |
| 22 | 17 | 24 | 16 | 14 |
| 0.04 | 21 | 23 | 25 | 19 | 21 |
| 22 | 17 | 19 | 20 | 15 |
| 16 | 17 | 12 | 13 | 14 |
030 | 900 | 50 | 42 | 34 | 46 | 37 |
| 29 | 40 | 31 | 23 | 33 |
| 25 | 19 | 26 | 18 | 16 |
0.06 | 23 | 26 | 28 | 21 | 23 |
| 25 | 19 | 21 | 22 | 17 |
| 18 | 19 | 14 | 15 | 16 | |
|
|
| ||||||||||||||||
| 1075 | 54 | 45 | 37 | 49 | 40 |
| 32 | 43 | 34 | 26 | 37 |
| 27 | 22 | 29 | 19 | 18 |
| 0.07 | 25 | 28 | 31 | 23 | 26 |
| 28 | 21 | 23 | 25 | 18 |
| 21 | 22 | 16 | 17 | 18 |
*Saturated suction leaving evaporator coil. Sensible Heat Capacity (1000 Btuh)
Gross Cooling Capacity (1000 Btuh)
NOTES:
1.Net capacities shown include a deduction for evaporator fan motor heat.
2.Contact manufacturer for cooling capacities at conditions other than shown in table.
3.Formulas:
sensible heat cap.
1.09 x CFM
Leaving wb = wb corresponding to enthalpy of air leaving coil (hlwb)
total capacity (Btuh)
4.5 x CFM
where hewb = enthalpy of air entering coil.
4.Direct interpolation is permissible. Do not extrapolate.
5.SHC is based on 80°F db temperature of air entering coil. Below 80°F subtract (corr factor x CFM) from SHC.
Above 80°F db, add (corr factor x CFM) to SHC.
SHC CORRECTION FACTOR
|
| ENTERING AIR | |||||
| 79 | 78 | 77 | 76 | 75 | Under 75 | |
BYPASS | 81 | 82 | 83 | 84 | 85 | Over 85 | |
FACTOR |
|
| Correction Factor |
| |||
0.10 | 0.98 | 1.96 | 2.94 | 3.92 | 4.91 | Use formula | |
0.20 | 0.87 | 1.74 | 2.62 | 3.49 | 4.36 | ||
shown below | |||||||
0.30 | 0.76 | 1.53 | 2.29 | 3.05 | 3.82 | ||
|
Interpolation is permissible.
Correction Factor = 1.09 x (1 – BF) x (db – 80)
OPTIONAL
|
|
|
|
| HEATER | APPROX | |
| SIZE | NOMINAL | HEATER |
| CAPACITY | ||
|
| SHIP. | |||||
HEATER PART NUMBER |
| (MBH)* | |||||
USED | KW @ |
| WEIGHT | ||||
WITH TDR | WITH | 240V | (60 Hz) | 208V |
| 230V | (lbs) |
KFDEH0801D05 | All | 5 | 14.3 |
| 17.2 | 7 | |
KFDEH0901D75 | All | 7.5 | 20.7 |
| 25.0 | 7 | |
KFDEH1001D11 | All | 11 | 29.7 |
| 36.0 | 7 |
* Heater capacities shown here are for the largest size fan coil unit, and they do include blower motor heat.