APC ACSC100, ACSC101 manual Quarterly Preventive Maintenance, Functional tests

Page 44

Quarterly Preventive Maintenance

*Perform all the Monthly Preventive Maintenance items and the items below. Prepared By: _________________________________

Model Number: ______________________________

Serial Number: _______________________________

Date: _________________

Mechanical

Electrical Hazard: Turn off the cooling unit and disconnect all power sources. Perform Lockout/ Tagout procedures before performing any electrical or mechanical service. Wear appropriate personal protective equipment when checking hazardous voltages.

‰Verify that the fan hardware is tight.

‰Clean/replace filters.

‰Clean condensate pans.

‰Clean condensate drain line.

‰Remove any debris from condensate floats.

‰Clean dust from door perforations.

‰Clean dust from fan bezels.

Functional tests

‰Verify the cooling operation mode is functioning properly.

38

InRow SC Operation

Image 44
Contents Operation 동봉된 CD 안에 한국어 매뉴얼이 있습니다 Contents Network Management Card Maintenance American Power Conversion Legal Disclaimer Symbols used in this manual Cross-reference symbol used in this manualGeneral Information OverviewSafety Inspection Checklists Initial inspection checklistCommissioning Ensure thatElectrical inspection checklist Mechanical inspection checklistUser interface inspection checklist Start-up inspection checklistFinal inspection checklist While the cooling unit is operating, ensure thatOperation Display InterfaceUsing the Display Interface Scrolling status screensStatus Screen Name Status Information Displayed Main menu screensNavigating the main menu Navigating the sub-menusUsing the Path statement Password entryStart the cooling unit Stop the cooling unitGeneral Configuration Cooling unit configurationEdit the normal state of input and output contacts ContactsView the state of input and output contacts Cooling Group Configuration Configure the cooling groupConfigure Modbus Identify the cooling unitSupply Air Control the EnvironmentSetpoints Run hours ThresholdsService intervals Date and time Display SettingsPassword & time-out Configure display Display unitsNetwork Configuration Configure networkView Status Readings Cooling unit statusModel Cooling group statusAbout the cooling unit Respond to Alarms Event LogAlarm messages and suggested actions Displayed Alarm Message Severity Action RequiredThreshlds screen Configure Unit Discrete I/O screen. See page 17 for more Quick Configuration TCP/IP configuration methodsNetwork Management Card OverviewIni file utility APC Device IP Configuration WizardBootp & Dhcp configuration NetworkTCP/IPBoot ModeDHCP onlyAdvancedDHCP Cookie Is Local access to the control console Remote access to the control consoleControl console Choose Network from the Control Console menuAccess a Configured Network Management Card Web interfaceTelnet and SSH Simple Network Management Protocol Snmp Modbus Recover From a Lost Password Maintenance Monthly Preventive MaintenanceCleanliness EnvironmentMechanical ElectricalQuarterly Preventive Maintenance Functional testsSemi-Annual Preventive Maintenance Troubleshooting Problem Possible Cause Corrective ActionProblem Possible Cause Warranty One-Year Factory WarrantyTerms of warranty Non-transferable warranty ExclusionsWarranty claims Page Page 990-2684A-001 2009