APC ACSC101 manual Commissioning, Inspection Checklists, Initial inspection checklist, Ensure that

Page 9

Commissioning

Warning: APC authorized personnel must perform the following procedures.

Electrical Hazard: Perform Lockout/Tagout procedures on the cooling unit before servicing the cooling unit. Failure to remove power before servicing this equipment could result in serious injury or death.

After installation is complete, verify that all components are working properly and that the cooling unit is ready to begin operation.

Inspection Checklists

Initial inspection checklist

The initial inspection ensures that the cooling unit has been properly installed, the location of the cooling unit has been properly prepared, and the cooling unit is free of damage.

Warning: The cooling unit operates under pressure. Take proper safety precautions when connecting gauges or servicing piping.

Warning: Do not operate the cooling unit with any cover, guard, door, or panel removed unless the instructions indicate otherwise. Then, proceed with extreme caution. Warning: Do not run service utilities in front of the fan outlets.

Caution: The vapor barrier minimizes moisture infiltration. Without a vapor barrier, it will be difficult to maintain the humidity in the room.

Caution: Do not introduce unconditioned outside air into the space.

Note: A minimum of 900 mm (36 in) of clear floor space in front of and behind the cooling unit is required for service access. To roll the cooling unit out of the row, there must be a minimum of 1200 mm (48 in) of clear floor space in front of or behind the cooling unit. Out-of-row service requires 760 mm (30 in) of side clearance in addition to the front and rear clearance.

Ensure that:

The installation procedure is complete according to the installation manual.

The walls, floor, and ceiling of the room where the cooling unit is located are sealed with a vapor barrier.

There is no evidence of damage to the cooling unit.

The cooling unit is level and joined to the adjacent racks or secured to the floor.

The clearance around the cooling unit is in accordance with local and national codes and regulations as well as the installation manual.

InRow SC Operation

3

Image 9
Contents Operation 동봉된 CD 안에 한국어 매뉴얼이 있습니다 Contents Network Management Card Maintenance American Power Conversion Legal Disclaimer Cross-reference symbol used in this manual Symbols used in this manualGeneral Information OverviewSafety Initial inspection checklist Inspection ChecklistsCommissioning Ensure thatMechanical inspection checklist Electrical inspection checklistStart-up inspection checklist User interface inspection checklistFinal inspection checklist While the cooling unit is operating, ensure thatDisplay Interface OperationScrolling status screens Using the Display InterfaceStatus Screen Name Status Information Displayed Main menu screensNavigating the sub-menus Navigating the main menuPassword entry Using the Path statementStop the cooling unit Start the cooling unitCooling unit configuration General ConfigurationContacts View the state of input and output contactsEdit the normal state of input and output contacts Configure the cooling group Cooling Group ConfigurationIdentify the cooling unit Configure ModbusControl the Environment SetpointsSupply Air Thresholds Run hoursService intervals Display Settings Password & time-outDate and time Display units Configure displayConfigure network Network ConfigurationCooling unit status View Status ReadingsCooling group status About the cooling unitModel Event Log Respond to AlarmsDisplayed Alarm Message Severity Action Required Alarm messages and suggested actionsThreshlds screen Configure Unit Discrete I/O screen. See page 17 for more TCP/IP configuration methods Quick ConfigurationNetwork Management Card OverviewAPC Device IP Configuration Wizard Bootp & Dhcp configurationIni file utility NetworkTCP/IPBoot ModeDHCP onlyAdvancedDHCP Cookie Is Remote access to the control console Local access to the control consoleChoose Network from the Control Console menu Control consoleWeb interface Access a Configured Network Management CardTelnet and SSH Modbus Simple Network Management Protocol SnmpRecover From a Lost Password Monthly Preventive Maintenance MaintenanceCleanliness EnvironmentElectrical MechanicalFunctional tests Quarterly Preventive MaintenanceSemi-Annual Preventive Maintenance Problem Possible Cause Corrective Action TroubleshootingProblem Possible Cause One-Year Factory Warranty WarrantyTerms of warranty Non-transferable warranty ExclusionsWarranty claims Page Page 2009 990-2684A-001

ACSC101, ACSC100 specifications

The APC ACSC100 and ACSC101 are power distribution units designed to manage and protect electronic equipment in data centers and critical infrastructure environments. Known for their reliability and efficiency, these models provide an essential solution for organizations that depend on constant power supply and equipment availability.

One of the main features of the APC ACSC100 and ACSC101 is their modular design. This flexibility allows for tailored configurations based on the user's unique requirements, making them suitable for diverse environments, from small server rooms to large-scale data centers. The units can accommodate a variety of input and output configurations, which helps in optimizing space and enhancing power management strategies.

These models are equipped with advanced technologies that enhance their performance. For instance, the ACSC100 and ACSC101 incorporate intelligent monitoring systems that provide real-time insights into power usage and distribution. This allows system administrators to monitor the performance remotely, ensuring that any potential issues can be addressed promptly before they escalate into more significant problems.

Another prominent characteristic of these power distribution units is their high level of protection. They come with built-in surge suppression and fault protection, safeguarding critical equipment against power surges and electrical faults. This feature is especially vital in environments where sensitive electronic components are in operation.

Moreover, the APC ACSC series incorporates energy-efficient designs. These models comply with various industry standards aimed at reducing energy consumption while maximizing output, contributing to a lower carbon footprint. Their efficiency not only helps in cutting operational costs but also aligns with sustainability goals that many organizations are striving to achieve.

User-friendly interfaces are a highlight of the ACSC100 and ACSC101. They feature intuitive LCD screens that simplify configuration and monitoring processes. This ease of use reduces the likelihood of human error during setup and operation, making them accessible even for those with limited technical expertise.

In summary, the APC ACSC100 and ACSC101 are cutting-edge power distribution solutions built for reliability, efficiency, and protection. Their modular design, advanced monitoring technology, robust safety features, energy efficiency, and user-friendly interface make them ideal choices for businesses seeking dependable power management systems in critical environments. With these models, organizations can ensure that their electronic assets are well-protected and efficiently managed, leading to enhanced operational continuity.